Carrier 50CR installation instructions Select and Install Ductwork, Electrical Operation Hazard

Page 9

Step 5—Select and Install Ductwork

The design and installation of the duct system must be in accordance with the standards of the NFPA for installation of non-residence type air conditioning and ventilating systems, NFPA 90A or residence type, NFPA 90B and/or local codes and ordinances.

Select and size ductwork, supply-air registers, and return air grilles according to ASHRAE (American Society of Heating, Refrigeration, and Air Conditioning Engineers) recommendations.

The unit has duct flanges on the supply- and return-air openings on the side of the unit.

!WARNING

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal injury or death.

For vertical supply and return units, tools or parts could drop into ductwork, therefore, install a 90 degree turn in the return ductwork between the unit and the conditioned space. If a 90 degree elbow cannot be installed, then a grille of sufficient strength and density should be installed to prevent objects from falling into the conditioned space. Units with electric heaters require 90 degree elbow in supply duct.

When designing and installing ductwork, consider the following:

1.All units should have field-supplied filters or accessory filter rack installed in the return-air side of the unit. Recommended sizes for filters are shown in Table 1.

2.Avoid abrupt duct size increases and reductions. Abrupt change in duct size adversely affects air performance.

IMPORTANT: Use flexible connectors between ductwork and unit to prevent transmission of vibration. Use suitable gaskets to ensure weather tight and airtight seal. When electric heat is installed, use fireproof canvas (or similar heat resistant material) connector between ductwork and unit discharge connection. If flexible duct is used, insert a sheet metal sleeve inside duct. Heat resistant duct connector (or sheet metal sleeve) must extend 24-in. from electric heater element.

3.Size ductwork for max cooling air quantity (400 cfm/ton).

4.Seal, insulate, and weatherproof all external ductwork. Seal, insulate and cover with a vapor barrier all ductwork passing through conditioned spaces. Follow latest Sheet Metal and Air Conditioning Contractors National Association (SMACNA) and Air Conditioning Contractors Association (ACCA) minimum installation standards for residential heating and air conditioning systems.

5.Secure all ducts to building structure. Flash, weatherproof, and vibration-isolate duct openings in wall or roof according to good construction practices.

CONVERTING HORIZONTAL DISCHARGE UNITS TO DOWNFLOW (VERTICAL) DISCHARGE UNITS

!WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or death.

Before installing or servicing system, always turn off main power to system. There may be more than one disconnect switch.Turn off accessory heater power switch if applicable.

1.Open all electrical disconnects and install lockout tag before starting any service work.

2.Remove side duct covers to access bottom return and supply knockouts.

NOTE: These panels are held in place with tabs similar to an electrical knockout.

3.Use a screwdriver and hammer to remove the panels in the bottom of the composite unit base.

4.Ensure the side duct covers are in place to block off the horizontal air openings (See Fig. 11).

Step 6—Provide for Condensate Disposal

NOTE: Ensure that condensate-water disposal methods comply with local codes, restrictions, and practices.

The units dispose of condensate through a 3/4 in. NPT female fitting that exits on the compressor end of the unit. Condensate water can be drained directly onto the roof in rooftop installations (where permitted) or onto a gravel apron in ground level installations. Install a field-supplied condensate trap at end of condensate connection to ensure proper drainage. Make sure that the outlet of the trap is at least 1 in. lower than the drain-pan condensate connection to prevent the pan from overflowing. Prime the trap with water. When using a gravel apron, make sure it slopes away from the unit.

If the installation requires draining the condensate water away from the unit, install a field-supplied 2-in. trap at the condensate connection to ensure proper drainage. Condensate trap is available as an accessory or is field-supplied. Make sure that the outlet of the trap is at least 1 in. lower than the unit drain-pan condensate connection to prevent the pan from overflowing. Connect a drain trough using a minimum of field-supplied 3/4 -in. PVC or field-supplied 3/4 -in. copper pipe at outlet end of the 2 -in. trap (See Fig. 12). Do not undersize the tube. Pitch the drain trough downward at a slope of at least 1 in. for every 10 ft. of horizontal run. Be sure to check the drain trough for leaks. Prime the trap at the beginning of the cooling season start-up.

50CR

9

Image 9
Contents Table of Contents Installation InstructionsElectrical Shock Hazard Safety ConsiderationsEquipment Damage Hazard IntroductionRoof Curb for Small Cabinet Roof Curb for Large Cabinet Unit Leveling Tolerances 50CR024-036 Unit Dimensions 50CR042-060 Unit Dimensions Inspection Rig and Place UnitUnit Falling Hazard Property Damage HazardRigging Bracket Under Unit Rain Lip Select and Install Ductwork Electrical Operation HazardProvide for Condensate Disposal Physical Data Unit 50CR Typical InstallationConnecting Ground Lead to Ground Screw Routing Power Leads Into UnitRouting Control Power Wires HIGH-VOLTAGE ConnectionsElectrical Data-50CR Electrical Data Legend Wiring Schematics-50CR Single Phase Wiring Schematics-50CR Three Phase Line Power Connections Accessory InstallationPRE-START-UP FIRE, EXPLOSION, Electrical Shock Hazard START-UPUnit Start-Up Status Code 37, Heater Output Sensed on When not Energized Status Code 45, Control Board Test FaultStatus Code 44, Motor Communication Fault Verify Motor Winding SectionStatus Code 41, Blower Motor Fault Status Code 36, Heater Output not Sensed When EnergizedStatus Code 16, System Communication Fault Status Code 25, Invalid Motor / Model SelectionStart-Up Adjustments Sequence of OperationCheck for Refrigerant Leaks Typical Heat Pump Operation, Cooling Mode Defrost Control Electric Heat Pressure Drop Table Small Cabinet Maintenance Personal Injury and Unit Damage HazardUnit Operation Hazard Indoor Blower and Motor Air FilterOutdoor Coil, Indoor Coil, and Condensate Drain Pan Outdoor FanPressure Switches Indoor AirflowMetering Devices-TXV & Accurater Piston High-Pressure Switch EXPLOSION, FIRE, Electrical Shock HazardPersonal INJURY, Unit Operation Hazard Troubleshooting LOSS-OF-CHARGE SwitchSTART-UP Checklist System InformationObserve all warnings, cautions, and bold text Troubleshooting Chart Head pressure too low Troubleshooting Chart Cont’dSTART-UP Checklist