Acnodes Q5RF SERIES user manual Refrigerant Charging Charts for, Cooling Mode of Operation

Page 14
Refrigerant Charging Charts for

Refrigerant Charging Charts for

Cooling Mode of Operation

 

 

 

 

 

 

Q5RF-X24K CHARGING CHART

 

 

 

 

 

 

600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

550

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

525

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R em ove refrigerant

w hen above curve

 

 

 

 

 

 

 

 

475

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(PSIG)

450

 

 

 

 

 

 

 

 

 

 

 

 

 

 

425

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESSURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

375

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LIQUID

350

 

 

 

 

 

 

 

 

 

 

 

 

 

 

325

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Add refrigerant

w hen below curve

 

 

 

300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

275

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

225

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70

75

80

85

90

95

100

105

110

115

120

125

130

135

140

 

 

 

 

 

 

 

LIQUID TEMPERATURE (F)

 

 

 

 

 

Figure 11. Charging Chart for 2 ton Units

 

 

 

 

 

 

Q5RF-X36K CHARGING CHART

 

 

 

 

 

 

600

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

550

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

525

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

500

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R em ove refrigerant

w hen above curve

 

 

 

 

 

 

 

 

475

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(PSIG)

450

 

 

 

 

 

 

 

 

 

 

 

 

 

 

425

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESSURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

400

 

 

 

 

 

 

 

 

 

 

 

 

 

 

375

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LIQUID

350

 

 

 

 

 

 

 

 

 

 

 

 

 

 

325

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Add refrigerant

w hen below curve

 

 

 

300

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

275

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

250

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

225

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

70

75

80

85

90

95

100

105

110

115

120

125

130

135

140

 

 

 

 

 

 

 

LIQUID TEMPERATURE (F)

 

 

 

 

 

 

Figure 12. Charging Chart for 3 ton Units

14

Image 14
Contents Q5RF SERIES DO NOT DESTROY. PLEASE READ CAREFULLY ANDKEEP IN A SAFE PLACE FOR FUTURE REFERENCE Single Package Heat Pump - 2 Stage, R-410ARefrigerant Charging Charts for INSTALLER INFORMATIONUSER INFORMATION IMPORTANT SAFETY INFORMATIONOperating Instructions USER INFORMATIONABOUT THE HEAT PUMP Figure 1. Digital ThermostatBefore You Install this Unit INSTALLER INFORMATIONSAFETY INFORMATION GENERAL INFORMATIONCondensate Drainage Figure 2. Drain Trap HEAT PUMP INSTALLATIONAir Duct System ElbowMake sure the filter is readily accessible Installing Return & Supply Air FittingsLocating & Installing the Return Air Assembly Figure 3. Minimum Unit ClearancesFigure 7. Supply Damper Locating & Installing the Supply DampersFigure 6. Return Air Box ELECTRICAL CONNECTIONS Pre-ElectricalChecklistFigure 8. Power Entry Line VoltageBlower Speed Overcurrent Protection2-SpeedOutdoor Fan Motor Select Models Ambient Sensor MountingMinimum Time Demand Defrost ControlJumper TerminateINDOOR THERMOSTAT AccessoryAccessory SUB-BASEAnti Short Cycle Timer Test STARTUP & ADJUSTMENTS Pre-StartChecklistStart-UpProcedure Forced Defrost Mode Field TestCharging an R-410AUnit in Heating Mode Adjustment of Refrigerant ChargeUNIT MAINTENANCE Figure 12. Charging Chart for 3 ton Units Refrigerant Charging Charts forFigure 11. Charging Chart for 2 ton Units Q5RF-X24KCHARGING CHARTFigure 14. Charging Chart for 5 ton Units Refrigerant Charging Charts forFigure 13. Charging Chart for 4 ton Units Q5RF-X48KCHARGING CHARTShaded boxes indicate flooded conditions Q5RF-X48K Q5RF-X60KK¢711065«¤ WIRING DIAGRAM60HZ/SINGLE PHASE 208/230V¢711066#¤ WIRING DIAGRAM60HZ/SINGLE PHASE 208/230V¢709158D¤ COMPONENT FUNCTIONS Low Pressure SwitchHigh Pressure Switch Model Q5RF