Acnodes Q5RF SERIES ¢709158D¤, COMPONENT FUNCTIONS Low Pressure Switch, High Pressure Switch

Page 20
COMPONENT FUNCTIONS

COMPONENT FUNCTIONS

Low Pressure Switch

The low pressure switch is factory installed and located in the suction line internal to the unit.The switch is designed to protect the compressor if a loss of charge occurs. Under normal conditions, the switch is closed.

If the suction pressure falls below 5 psig, then the switch will open and de-energize the unit.The switch will close again once the suction pressure increases above 20 psig. The low pressure switch interrupts the thermostat inputs to the unit. NOTE: When the switch opens and then closes, there will be a 5 minute short cycling delay before the unit can energize.

High Pressure Switch

The high pressure switch is factory installed and located in the compressor discharge line internal to the unit.The switch is designed to de- energize the system when very high pressures occur during abnormal conditions.Under normal conditions, the switch is closed.

If the discharge pressure rises above 650 psig, the switch will open and de-energize the unit. The switch will close again once the discharge pressure decreases to 460 psig. The high pressure switch interrupts the thermostat inputs to the unit. NOTE: When the switch opens and then closes, there will be a 5 minute short cycling delay before the unit can energize.

Model Q5RF

Wire Color/Speed Tap

Motor Speed

Air Flow

(@ 0.3 in WC)

 

 

 

 

 

 

 

 

T1

Low

560

 

Orange/T2

Medium/Low*

600

 

 

 

 

X24K

Black/T3

Medium**

800

 

Red/T4

Medium/High***

1,040

 

T5

High

1,250

 

Orange/T1

Low*

600

 

T2

Medium/Low

750

X36K

Black/T3

Medium**

1,200

 

Red/T4

Medium/High***

1,420

 

 

 

 

 

T5

High

1,520

 

 

 

 

 

Orange/T1

Low*

1,030

 

 

 

 

 

T2

Medium/Low

1,240

X48K

 

 

 

Red/T3

Medium***

1,400

 

Black/T4

Medium/High**

1,530

 

T5

High

1,680

 

Orange/T1

Low

1,060

 

T2

Medium/Low*

1,200

X60K

 

 

 

Red/T3

Medium***

1,500

 

 

 

 

 

Black/T4

Medium/High**

1,760

 

 

 

 

 

T5

High

1,970

*Denotes Factory Set Low Speed Cooling/ Heating

**Denotes Factory Set High Speed Cooling/ Heating

***Denotes Factory Set Electric Heating Speed

Table 4. Motor Lead Connection

INSTALLER: PLEASE LEAVE THESE INSTALLATION INSTRUCTIONS WITH THE HOMEOWNER.

¢709158D¤ 7091580

 

 

Specifications and illustrations

 

 

 

 

subject to change without

O’Fallon, MO

7091580

notice or incurring obligations.

Printed in U.S.A. (02/10)

Image 20
Contents DO NOT DESTROY. PLEASE READ CAREFULLY AND KEEP IN A SAFE PLACE FOR FUTURE REFERENCEQ5RF SERIES Single Package Heat Pump - 2 Stage, R-410AINSTALLER INFORMATION USER INFORMATIONRefrigerant Charging Charts for IMPORTANT SAFETY INFORMATIONUSER INFORMATION ABOUT THE HEAT PUMPOperating Instructions Figure 1. Digital ThermostatINSTALLER INFORMATION SAFETY INFORMATIONBefore You Install this Unit GENERAL INFORMATIONFigure 2. Drain Trap HEAT PUMP INSTALLATION Air Duct SystemCondensate Drainage ElbowInstalling Return & Supply Air Fittings Locating & Installing the Return Air AssemblyMake sure the filter is readily accessible Figure 3. Minimum Unit ClearancesFigure 7. Supply Damper Locating & Installing the Supply DampersFigure 6. Return Air Box Pre-ElectricalChecklist Figure 8. Power EntryELECTRICAL CONNECTIONS Line VoltageOvercurrent Protection 2-SpeedOutdoor Fan Motor Select ModelsBlower Speed Ambient Sensor MountingDemand Defrost Control JumperMinimum Time TerminateAccessory AccessoryINDOOR THERMOSTAT SUB-BASESTARTUP & ADJUSTMENTS Pre-StartChecklist Start-UpProcedureAnti Short Cycle Timer Test Forced Defrost Mode Field TestCharging an R-410AUnit in Heating Mode Adjustment of Refrigerant ChargeUNIT MAINTENANCE Refrigerant Charging Charts for Figure 11. Charging Chart for 2 ton UnitsFigure 12. Charging Chart for 3 ton Units Q5RF-X24KCHARGING CHARTRefrigerant Charging Charts for Figure 13. Charging Chart for 4 ton UnitsFigure 14. Charging Chart for 5 ton Units Q5RF-X48KCHARGING CHARTShaded boxes indicate flooded conditions Q5RF-X48K Q5RF-X60KKWIRING DIAGRAM 60HZ/SINGLE PHASE¢711065«¤ 208/230VWIRING DIAGRAM 60HZ/SINGLE PHASE¢711066#¤ 208/230VCOMPONENT FUNCTIONS Low Pressure Switch High Pressure Switch¢709158D¤ Model Q5RF