Acnodes Q5RF SERIES user manual Air Duct System, Condensate Drainage, Elbow, Unpacking the Unit

Page 5
Air Duct System

Air Duct System

Air ducts must be installed in accordance with the standards of the National Fire Protection Association “Standard for Installation of Air Conditioning and Ventilation Systems” (NFPA 90A),“Standard for Installation of ResidenceType Warm Air Heating and Air Conditioning Systems” (NFPA 90B), these instructions, and all applicable codes. NFPA publications are avaialable by writing to: National Fire Protection Association, Batterymarch Park, Quincy, ME 02269 or visit www.NFPA.org on the web.

Design the duct work according to methods described by the Air Conditioning Contractors of America (ACCA).

The supply duct system, including the number and type of registers, will have much more effect on the performance of the system than any other factor. The duct must be suffi ciently large to conduct an adequate amount of air to each register. See Figure 4 (page 6).

Duct work should be attached directly to the unit fl anges for horizontal applications.

If roof curb is installed, the ducts must be attached to the curb hangers, not the unit.

For highly resistive duct systems it may be necessary to add an additional return air duct and or supply to achieve maximum performance and prevent coil icing and refrigerant fl ood back

Unconditioned Spaces

All duct work passing through unconditioned space must be properly insulated to minimize duct losses and prevent condensation.Use insulation with an outer vapor barrier. Refer to local codes for insulation material requirements.

The heat pump system will not cool or heat the home if air is lost to the outside through leaks in the duct system. Ducts that are collapsed or restricted by foreign objects will also prevent adequate air flow.

Condensate Drainage

A 3/4” condensate fi tting extends out of the side of the unit (Figure 2). The drain trap, shipped in the electrical compartment, must be installed to prevent water from collecting inside the unit.

1.Thread the elbow provided with the unit into the drain connection until hand tight.

2.Connect the condensate tubing onto the fitting, forming a trap near the drain connection.

3.Route the condensate tube from the trap to a suitable drain. NOTE: For proper drainage, make sure the trap is level to the ground and tubing outlet is below trap level.

Elbow

P-Trap

Figure 2. Drain Trap

HEAT PUMP INSTALLATION

Unpacking the Unit

It is recommended that the unit be unpacked at the installation site to minimize damage due to handling.

Condensate Drainage CAUTION:

Do not tip the unit on its side. Oil may enter the compressor cylinders and cause starting trouble. If unit has been set on its side, restore to upright position and do not run for several hours.Then run unit for a few seconds. Do this three or four times with five minutes between runs.

1.Remove the bands from around the unit.

2.Unfold the top and bottom cap fl anges.

3.Carefully remove the top cap and tube.

Minimum Clearances

Minimum clearances MUST be maintained from adjacent structures to provide room for proper servicing and air circulation. DO NOT install unit in a confi ned or recessed area that will allow discharge air from the unit to re-circulate into the condenser air inlet, through the coil. See Figure 3 (page 6).

Service Access Clearance:

 

Blower access panel side

24”

Electrical compartment access panel side ...

12”

Clearance between overhang and

 

top of unit

72”

Clearance around condenser coil area to

 

wall or shrubs (excludes duct panel side) ..

12”

Clearances to Combustibles:

 

Combustible Base (Wood or Class A, B, or C

 

roof Covering material)

0”

Supply and Return Air Ducts

0”

Duct Connection side

0”

5

Image 5
Contents KEEP IN A SAFE PLACE FOR FUTURE REFERENCE DO NOT DESTROY. PLEASE READ CAREFULLY ANDQ5RF SERIES Single Package Heat Pump - 2 Stage, R-410AUSER INFORMATION INSTALLER INFORMATIONRefrigerant Charging Charts for IMPORTANT SAFETY INFORMATIONABOUT THE HEAT PUMP USER INFORMATIONOperating Instructions Figure 1. Digital ThermostatSAFETY INFORMATION INSTALLER INFORMATIONBefore You Install this Unit GENERAL INFORMATIONAir Duct System Figure 2. Drain Trap HEAT PUMP INSTALLATIONCondensate Drainage ElbowLocating & Installing the Return Air Assembly Installing Return & Supply Air FittingsMake sure the filter is readily accessible Figure 3. Minimum Unit ClearancesFigure 7. Supply Damper Locating & Installing the Supply DampersFigure 6. Return Air Box Figure 8. Power Entry Pre-ElectricalChecklistELECTRICAL CONNECTIONS Line Voltage2-SpeedOutdoor Fan Motor Select Models Overcurrent ProtectionBlower Speed Ambient Sensor MountingJumper Demand Defrost ControlMinimum Time TerminateAccessory AccessoryINDOOR THERMOSTAT SUB-BASEStart-UpProcedure STARTUP & ADJUSTMENTS Pre-StartChecklistAnti Short Cycle Timer Test Forced Defrost Mode Field TestCharging an R-410AUnit in Heating Mode Adjustment of Refrigerant ChargeUNIT MAINTENANCE Figure 11. Charging Chart for 2 ton Units Refrigerant Charging Charts forFigure 12. Charging Chart for 3 ton Units Q5RF-X24KCHARGING CHARTFigure 13. Charging Chart for 4 ton Units Refrigerant Charging Charts forFigure 14. Charging Chart for 5 ton Units Q5RF-X48KCHARGING CHARTShaded boxes indicate flooded conditions Q5RF-X60KK Q5RF-X48K60HZ/SINGLE PHASE WIRING DIAGRAM¢711065«¤ 208/230V60HZ/SINGLE PHASE WIRING DIAGRAM¢711066#¤ 208/230VHigh Pressure Switch COMPONENT FUNCTIONS Low Pressure Switch¢709158D¤ Model Q5RF