Miller Electric Blue Star 3500 manual Power Required To Start Motor, KVA/HP x HP x

Page 41

11-8. Power Required To Start Motor

4

 

 

AC MOTOR

 

2

1

 

 

 

 

VOLTS

230

AMPS

2.5

 

 

 

 

 

3

 

CODE

M

Hz

60

 

 

 

HP

1/4

PHASE 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single-Phase Induction Motor Starting Requirements

Motor Start

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Code

G

 

H

 

J

K

L

M

 

N

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KVA/HP

6.3

 

7.1

8.0

9.0

10.0

11.2

 

12.5

 

14.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

kVA/HP x HP x 1000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

= STARTING AMPERAGE

 

 

 

 

 

 

 

VOLTS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EXAMPLE: Calculate the starting amperage required for a 230 V, 1/4

 

 

HP motor with a motor start code of M.

 

 

 

 

 

 

 

Volts = 230

HP = 1/4 Using Table, Code M results in kVA/HP = 11.2

11.2 x 1/4 x 1000

= 12.2 A

Starting the motor requires 12.2 amperes.

 

230

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1Motor Start Code

2Running Amperage

3Motor HP

4Motor Voltage

To find starting amperage:

Step 1: Find code and use table to find kVA/HP. If code is not listed, multiply running amperage by six to find starting amperage.

Step 2: Find Motor HP and Volts.

Step 3: Determine starting amper- age (see example).

Welding generator amperage out- put must be at least twice the motor’s running amperage.

S-0624

11-9. How Much Power Can Generator Supply?

1

2

1Limit Load To 90% Of Generator Output

Always start non-resistive (motor) loads in order from largest to small- est, and add resistive loads last.

2 5 Second Rule

If motor does not start within 5 seconds, turn off power to prevent motor damage. Motor requires more power than generator can supply.

Ref. ST-800 396-A / S-0625

Return To Table Of Contents

OM-491 Page 37

Image 41
Contents Description OM-498Processes From Miller to You Table of Contents Page Arc Welding Hazards Symbol UsageEngine Hazards Compressed Air Hazards California Proposition 65 Warnings Principal Safety StandardsEMF Information Radiation can cause interference− Consignes DE Sécurité − Lire Avant Utilisation Signification des symbolesUN Choc Électrique peut tuer LES Fumées ET LES GAZ peuvent être dangereuxDES Particules Volantes peuvent blesser les yeux LE Soudage peut provoquer un in- cendie ou une explosionDES Pièces Chaudes peuvent provoquer des brûlures graves LE Bruit peut affecter l’ouïeDES Organes Mobiles peuvent provoquer des blessures ’EXPLOSION DE LA Batterie peutLA Chaleur DU Moteur peut pro- voquer un incendie ’AIR Comprimé peut provoque r des blessuresInformation sur les champs électromagnétiques Principales normes de sécuritéSymbol Definitions − SpecificationsWeld, Power, And Engine Specifications − DefinitionsFuel Consumption Kohler-Powered Units Dimensions, Weights, And Operating AnglesDimensions Weight Kohler-Powered UnitsExceeding duty cycle can damage unit and void warranty Fuel Consumption Honda-Powered UnitsDuty Cycle 100% Duty Cycle at 80 Amperes CC/DCVolt-Ampere Curves Generator Power CurveGrounding Generator To Truck Or Trailer Frame − InstallationInstalling Welding Generator Use ground device as stated in electrical codes Grounding Generator When Supplying Building SystemsConnecting The Battery Honda Electric-Start Models Only Engine Prestart Checks Honda-Powered Units+ − OilSelecting Weld Cable Sizes Connecting To Weld Output Terminals− Operating the Welding Generator Controls Kohler-Powered Units60 Hz Choke Control LeverRecoil-Start 2Electric-Start Controls Honda-Powered Units See SectionWork like a Pro Description Of Controls Honda-Powered Units See Section120 V x 10 a + 240 V x 9 a = 3.5 kVA/ KW OM-498 Generator Power Panel 495 218 USA− Operating Auxiliary Equipment Generator Power Panel 495 Optional Generator Power PanelsCanada South Africa South America Australia Europe AsiaIt exceeds 3500W Generator Power Panel RatingsWire Load Plug Wired For 120/240Plex receptacle shares a load with One half of the 240 V receptacle− Maintenance Overload Protection Honda-Powered Units Only Maintenance LabelWeld/Power Speed Adjustment Adjusting Engine Speed Kohler-Powered UnitsTop View Idle Speed Adjustment Stop engine. Close fuel valve Top ViewThrottle Control Lever Adjustment Screw Adjusting Engine Speed Honda-Powered UnitsStop engine. Close fuel valve Tools Needed 3/8Troubleshooting − TroubleshootingGenerator Power WeldingViscosity oil for operating temperature Check battery voltage Honda electric-start models onlyEngine Make starting difficultCircuit Diagram For Welding Generator − Electrical DiagramsWiring Diagram For Generator Power Panels 1 Wiring Diagram For Generator Power Panels 2 OM-491 − Generator Power GuidelinesSelecting Equipment How Much Power Does Equipment Require? Grounding When Supplying Building Systems Earth ground if supplying Volts 115 Amps Resistive LoadApproximate Power Requirements For Farm/Home Equipment Approximate Power Requirements For Industrial MotorsIndustrial Motors Rating Starting Watts Running Watts Farm/Home Equipment Rating Starting Watts Running WattsContractor Rating Starting Watts Running Watts Approximate Power Requirements For Contractor EquipmentHow Much Power Can Generator Supply? Power Required To Start MotorSingle-Phase Induction Motor Starting Requirements KVA/HP x HP xTypical Connections To Supply Standby Power Current Load Watts Amperes Selecting Extension Cord Use Shortest Cord Possible− Stick Welding Smaw Guidelines Stick Welding ProcedureWeld current starts when electrode touches work- piece Striking an Arc − Tapping Technique Electrode and Amperage Selection ChartStriking an Arc − Scratch Start Technique Good Weld Bead Characteristics Poor Weld Bead CharacteristicsPositioning Electrode Holder 10-30 9090 End View of Work AngleElectrode Movement During Welding Conditions That Affect Weld Bead ShapeLap Joint Butt JointsTee Joint 16 in 1.6 mm Tack WeldsTroubleshooting − Excessive Spatter Troubleshooting − PorosityWeld Test Possible Causes Corrective ActionsTroubleshooting − Excessive Penetration Troubleshooting − Incomplete FusionTroubleshooting − Lack Of Penetration Troubleshooting − Distortion Troubleshooting − Burn-ThroughTroubleshooting − Waviness Of Bead 31−Fig − Parts ListDia Part Generator Power Panel 495 South Africa Australia Generator Power Panel 495 Generator Power Panel 495 315 USACanada Europe AmericaGenerator Power Panel 495 279 Canada Generator Power Panel 495 218 USAGenerator Power Panel 495 253 South Africa Generator Power Panel 495 289 AustraliaWork like a Pro Page TM-188 304 Invision 354MP Material Thickness Reference ChartSupport ServiceYour distributor also gives For assistance in filing or settling claims, contact Miller Electric Mfg. CoYour distributor and/or equipment manufacturer’s Transportation Department