9-3. Grounding When Supplying Building Systems

 

 

 

 

 

 

 

 

1

Equipment Grounding

1

2

 

Terminal

2

Grounding Cable

GND/PE

 

 

Use #10 AWG or larger insulated

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

copper wire.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

Ground Device

 

 

 

 

 

 

 

 

Y Ground generator to system

 

 

 

 

 

 

 

 

 

earth ground if supplying

 

 

 

 

 

 

 

 

 

power to a premises (home,

 

 

 

 

 

 

 

 

 

shop, farm) wiring system.

Use ground device as stated in electrical codes.

23

ST-800 576-B

9-4. How Much Power Does Equipment Require?

3

2

1

3

VOLTS 115 AMPS 4.5

Hz 60

1 Resistive Load

A light bulb is a resistive load and requires a constant amount of pow- er.

2 Non-Resistive Load

Equipment with a motor is a non-re- sistive load and requires approxi- mately six times more power while starting the motor than when run- ning (see Section 9-8).

3 Rating Data

Rating shows volts and amperes, or watts required to run equipment.

AMPERES x VOLTS = WATTS

EXAMPLE 1: If a drill uses 4.5 amperes at 115 volts, calculate its running power requirement in watts.

4.5 A x 115 V = 520 W

The load applied by the drill is 520 watts.

EXAMPLE 2: If three 200 watt flood lamps are used with the drill from Example 1, add the individual loads to calculate total load.

(200 W + 200 W + 200 W) + 520 W = 1120 W

The total load applied by the three flood lamps and drill is 1120 watts.

S-0623

OM-477 Page 39

Image 43
Contents Processes OM-477Description From Miller to You Table of Contents Page ARC Rays can burn eyes and skin Symbol UsageArc Welding Hazards Electric Shock can killEngine Hazards Engine Heat can cause fire Battery Explosion can BlindMoving Parts can cause injury Engine Exhaust Gases can killARC Welding can cause interference Principal Safety StandardsEMF Information Radiation can cause interferenceLES Fumé ES ET LES GAZ peuvent ê tre dangereux Signification des symbolesConsignes DE SÉ Curité Lire Avant Utilisation UN Choc É Lectrique peut tuerLE Bruit peut affecter l’ouïe LE Soudage peut provoquer un in- cendie ou une explosionDES Particules Volantes peuvent blesser les yeux DES PIÈ CES Chaudes peuvent provoquer des brû lures gravesLA Chute DE L’APPAREIL peut blesser DES Organes Mobiles peuvent provoquer des blessures’EXPLOSION DE LA Batterie peut LA Chaleur DU Moteur peut pro- voquer un incendieConsignes relatives aux stimulateurs cardiaques Principales normes de sé curitéInformation sur les champs é lectromagné tiques LE Soudage À L’ARC risque de provoquer des interfé rencesDefinitions SpecificationsSymbols And Definitions Weld, Power, And Engine SpecificationsFuel Consumption Dimensions, Weights, And Operating AnglesDimensions WeightDuty Cycle And Overheating AC Auxiliary PowerMinutes Welding Minutes Resting 5 KVA/KW Single-Phase Auxiliary Power Plant No Weld Load Optional AC Power Plant Curves12.5 KVA/KW Three-Phase Auxiliary Power Plant No Weld Load 100 Volt-Ampere CurvesDC Volts CC/DC Standard AC Amperes CV/DC Models with Optional CV-3 ModuleInstalling Muffler InstallationInstalling Welding Generator Connecting The Battery13 mm Full Gasoline Capacity 9 qt 8.5 L Engine Prestart ChecksTop View 10 100% Duty Cycle Connecting To Weld Output TerminalsSelecting Weld Cable Sizes 100 ft 30 m Or LessStop engine Remote 14 Receptacle RC3 Information Optional, See SectionTerminal Strip 3T Connections Optional Socket InformationFront Panel Controls See Section Operating Welding GeneratorStop engine and fix trouble if either warning light goes on Ampere Range SwitchDo not switch under load Description Of Front Panel Controls See SectionExample Combination remote amperage control Remote Control OptionalVolt Duplex And Optional Gfci Receptacles Operating Auxiliary EquipmentX 10 a + 120 V x 5 a = 3.0 kVA/kW Volt Duplex Receptacle OptionalFront Connecting Optional Auxiliary Power PlantMaintenance and Troubleshooting Maintenance Label Overload Protection Servicing Air CleanerTo Clean air filter Do not clean housing with air hoseStandard filter Changing Engine Oil And FilterStop engine and let cool Standard Oil Filter Cation makes it difficult to changeChanging Fuel Filter Inspecting And Cleaning Optional Spark Arrestor MufflerStop engine and let cool 1850 rpm Max Adjusting Engine Weld/Power SpeedAdjusting Governor Sensitivity Adjusting Engine Idle SpeedTrouble Remedy Adjusting Optional High Altitude CarburetorTroubleshooting WeldingAuxiliary Power See engine manual Coolant temperature gets too high see SectionCheck Engine Control switch, and replace if necessary EngineOM-477 Circuit Diagram For Welding Generator For Standard Models Electrical DiagramsOM-477 193 967-A Selecting Equipment Auxiliary Power GuidelinesGrounding Generator To Truck Or Trailer Frame Amperes x Volts = Watts Grounding When Supplying Building SystemsHow Much Power Does Equipment Require? Earth ground if supplyingFarm/Home Equipment Rating Starting Watts Running Watts Approximate Power Requirements For Industrial MotorsApproximate Power Requirements For Farm/Home Equipment Industrial Motors Rating Starting Watts Running WattsContractor Rating Starting Watts Running Watts Approximate Power Requirements For Contractor EquipmentKVA/HP x HP x Power Required To Start MotorHow Much Power Can Generator Supply? Single-Phase Induction Motor Starting Requirements240 120 Ground Typical Connections To Supply Standby PowerCurrent Load Watts Amperes Selecting Extension Cord Use Shortest Cord PossibleOM-477 114 113 112 111 110 109 108 107 106 105 104 103 102 101 100 Parts ListIncludes 39 43 Dia Part Description Mkgs Quantity 025 2523 GeneratorGenerator -1 Item Includes 2539CB1,2 139 Control Box w/Components -3 Item Your distributor also gives ServiceSupport Miller Electric Mfg. Co Owner’s Record