10-3. Run-In Procedure Using Resistance Grid
|
| ! | Stop engine. |
|
| ! Do not touch hot exhaust | |
|
|
| pipe, engine parts, or load |
6 |
|
| bank/grid. |
| ! | Keep exhaust and pipe away | |
|
| ||
| 2 |
| from flammables. |
| NOTICE − Do not perform | ||
|
| ||
|
| procedure at less than 20 volts weld | |
|
| output and do not exceed duty | |
|
| cycle or equipment damage may | |
|
| occur. | |
|
| 1 | Resistance Grid |
| 1 | Use grid sized for generator rated | |
| output. | ||
|
| Turn Off grid. | |
|
| 2 | Welding Generator |
|
| Place A/V range switch in maxi- | |
|
| mum position, A/V control in mini- | |
|
| mum position, and Output Selector | |
|
| switch (if present) in either DC | |
|
| position. | |
|
| 3 | Weld Cables |
|
| Connect grid to generator weld | |
|
| output terminals using proper size | |
|
| weld cables with correct connec- | |
|
| tors (polarity is not important). | |
|
| 4 | Voltmeter |
|
| 5 | |
3 | 5 | Connect voltmeter and ammeter as | |
shown, if not provided on generator. | |||
|
| Start engine and run for several | |
|
| minutes. | |
|
| Set grid switches and then ad- | |
|
| just generator A/V control so | |
4 |
| load equals rated voltage and | |
| current of the generator (see | ||
|
| ||
|
| nameplate, rating label, or the | |
|
| specifications section in this | |
|
| manual). | |
+ |
| Check generator and meters after | |
|
| first five minutes then every fifteen | |
|
| minutes to be sure generator is | |
|
| loaded properly. | |
|
| NOTICE − Check oil level frequent- | |
|
| ly during |
It is recommended to run the weld- ing generator for two hours mini- mum and up to four hours under load. Place A/V control in minimum position, then shut down grid to remove load. Run engine several minutes at no load.
! Stop engine and let cool.
6 Engine Exhaust Pipe
Repeat procedure if wetstacking is present.