Indoor Unit (Body) XMS1272
Control PCB
Part No.
Controls
Control Circuit Fuse
Remote Control Unit
Fan
Microprocessor
250V 3A
Type |
|
Q'ty ... Dia. and Length | inch (mm) |
Turbo
1 ...
Fan Motor |
|
|
|
| ||
| Type |
|
|
| DC Motor | |
| Model ... Q'ty |
|
|
| ||
| No. of Poles |
|
|
| 8 | |
| Rough Measure RPM (Cool) |
| 470 | |||
| Rating | Voltage / Nominal Output | DC280V / 23W | |||
| Coil Resistance |
|
| Ohm | - | |
| (Ambient Temp. 68 °F (20 °C)) |
|
| |||
| Safety Device |
|
|
|
| |
|
| Type |
|
|
| Thermal Fuse |
|
| Over- Current Protection |
| Yes | ||
|
| Over- Heat Protection |
| Yes | ||
| Run Capacitor |
|
| Micro F | - | |
|
|
|
|
| VAC | - |
|
|
|
|
| ||
Drain Pump |
|
|
|
| ||
| Model ... Q'ty |
|
|
| ||
| Rating |
| Voltage, Hz |
| AC208 to 240V, 60Hz | |
|
|
|
| Input | W | 10.8 |
| Coil Resistance |
|
| Ohm | 333 +/- 10% | |
| (Ambient Temp. 68 °F (20 °C)) |
|
| |||
| Safety Device |
| Type |
| Thermal Fuse | |
|
|
|
| Open | °F (°C) | 293 (145) |
|
|
|
|
|
|
|
Heat Exchanger Coil |
|
|
|
| ||
| Coil |
|
|
| Aluminum Plate Fin / Copper Tube | |
| Rows |
|
|
| 2 | |
| Fins per inch |
|
|
| 18.1 | |
| Face Area |
|
| ft2 (m2) | 2.94 (0.273) | |
|
|
|
|
|
| DATA SUBJECT TO CHANGE WITHOUT NOTICE. |
Indoor Unit (Panel) |
|
|
| |||
|
|
|
|
|
|
|
Flap Motor |
|
|
|
| ||
| Type |
|
|
| Stepping Motor | |
| Model ... Q'ty |
|
|
| ||
| Rating |
|
|
| DC 12V | |
| Coil Resistance |
|
| Ohm | Each Pair of Terminal : 380 +/- 7% | |
| (Ambient Temp. 77 °F (25 °C)) |
|
| |||
|
|
|
|
|
| DATA SUBJECT TO CHANGE WITHOUT NOTICE. |
15