(2)Removing the corner cover and indicator cover
a)While lightly pressing the cen- ter of the corner cover, pull up the tab for the screw hole. Use the same procedure to remove the indicator cover. (Fig.
Corner cover
Indicator cover
1 Press
2 Pull up
Fig.
3-6-2. Installing the Ceiling Panel
(1)Hang the temporary latches on the inside of the ceil- ing panel to the receptacle on the unit to temporarily attach the ceiling panel in place. (Fig.
●The ceiling panel must be installed in the correct direction relative to the unit. Align the REF. PIPE and DRAIN marks on the ceiling panel corner with the correct positions on the unit.
(2)Align the panel installation holes and the unit screw holes. (Fig.
(3)Tighten the supplied special screws at the 4 panel installation locations so that the panel is attached tightly to the unit.
●Check that the wiring connectors are not caught between the unit and the ceiling panel.
(4)Check that the panel is attached tightly to the ceiling. (Fig.
●At this time, make sure that there are no gaps between the unit and the ceiling panel, or between the ceiling panel and the ceiling surface.
●If there is a gap between the panel and the ceiling, leave the ceiling panel attached and make fine adjustments to the installation height of the unit to eliminate the gap with the ceiling.
CAUTION
Temporary latches
Temporary latch
Fig.
Refrigerant tubing joint
Drainage check
Ceiling panel | REF.PIPE mark |
DRAIN mark
Panel installation hole
(4 locations)
Special screws
Fig.
| Do not allow |
Indoor unit | gaps |
Ceiling surface | Ceiling panel |
Fig.
If the screws are not sufficiently tightened, trouble such as that shown in the figure below may occur. Be sure to tighten
the screws securely.
Air leakage
Air leakage from ceiling surface
Staining
Condensation, water leakage
If a gap remains between the ceiling surface and the ceiling panel even after the screws are tightened, adjust the height of the unit again.
Adjust so that there are no gaps.
Fig.
The height of the unit can be adjusted from the ceiling panel corner hole, with the ceiling panel attached, to an extent that does not affect the unit levelness,
the drain hose, or other elements.
9