Sanyo XMS1272 Installation Site Selection, Additional Materials Required for Installation

Page 75

1-5. Additional Materials Required for Installation

1.Refrigeration (armored) tape

2.Insulated staples or clamps for connecting wire (See local codes.)

3.Putty

4.Refrigeration lubricant

5.Clamps or saddles to secure refrigerant tubing

2. Installation Site Selection

2-1. Indoor Unit

WARNING

AVOID:

To prevent abnormal heat generation and the possibility of fire, do not place obstacles, enclosures and grilles in front of or surrounding the air conditioner in a way that may block air flow.

direct sunlight.

nearby heat sources that may affect performance of the unit.

areas where leakage of flammable gas may be expected.

placing or allowing any obstructions near the air conditioner inlet or outlet.

installing in rooms that contain instant-on (rapid-start) fluorescent lamps. (These may prevent the air conditioner from receiving signals.)

places where large amounts of oil mist exist.

installing in locations where there are devices that generate high-frequency emissions.

DO:

select an appropriate position from which every corner of the room can be uniformly cooled.

select a location that will hold the weight of the unit.

select a location where tubing and drain hose have the shortest run to the outside.

allow room for operation and maintenance as well as unrestricted air flow around the unit. (Fig. 1)

install the unit within the maximum elevation difference (H1, H2, H3, H4) above or below the outdoor unit and within a total tubing length (L1+L2+L3, L1+L2+L3+L4) from the outdoor unit as detailed in Table 3 and Fig. 2.

 

3.3 ft.

 

3.3 ft.

 

 

(1m)

 

(1m)

 

 

3.3 ft.

 

3.3 ft.

 

 

3.3 ft.

(1m)

 

 

(1m)

 

 

 

(1m)

 

 

 

 

 

 

 

 

Fig. 1

 

 

 

INDOOR Tubing length (L1)

 

 

 

UNIT (1)

 

INDOOR

 

 

 

 

 

 

 

 

UNIT (2)

 

 

Elevation

L2

 

 

 

difference (H1)

OUTDOOR

 

H2

 

 

UNIT

 

 

 

 

L3

 

 

H4

INDOOR

L4

INDOOR

H3

 

UNIT (4)

UNIT (3)

 

Fig. 2

CAUTION

Air delivery will be degraded if the distance from the floor to the ceiling is greater than 10 ft. (3 m).

4

Image 75
Contents 17,500BTU / h 11,900BTU / hSafety Precautions Prohibit Table of Contents STK-RCS-7TWSUA Applicable MULTI-OUTDOOR Units Indoor Air Intake Temp Outdoor Air Intake Temp Operating RangeSpecifications Unit SpecificationsIndoor Unit XMS0972 & PNR-XS1872 Indoor Unit XMS0972 & PNR-XS1872208V XMS1272 & PNR-XS1872 XMS1272 & PNR-XS1872 XS1872 & PNR-XS1872 XS1872 & PNR-XS1872 Indoor Unit Panel Major Component SpecificationsIndoor Unit Indoor Unit Body XMS0972Indoor Unit Body XMS1272 Indoor Unit Body XS1872 ModelPT2M-51H-S3 Other Component SpecificationsModelKTEC-35-S98 Indoor heat exchanger sensor534 Dimensional DataRefrigerant Flow Diagram Refrigerant Flow DiagramIndoor Unit XS1872 & PNR-XS1872 Indoor unit Electrical Data 5250-469008FA2 Remove the air intake grill MaintenanceDisassembly Procedure Disconnect the connectors in the control boxRemove the ceiling panel Remove the power box and control box Remove the indoor air temperature sensorScrew Ground cable CN07 ScrewCN03 CN09 CN06 Remove the main body lower section Remove the heat exchanger sensor Remove the drain pump and float switchRemove the heat exchanger Remove the turbo fan and fan motorPAM- control FunctionsOperation Functions Emergency operationLamp colors Timer backupFreeze prevention Protective FunctionsTroubleshooting Precautions before Performing Inspection or RepairMethod of Self-Diagnostics Self-diagnostics Lamps Replace the circuit board or the fuse Using the TEST/T-RUN terminalsChecking the Indoor and Outdoor Units Replace the controllerCondition E01 Serial Communication Error Identification ProcedureBefore the Operation Off Blinking IlluminatedTerminal board Outdoor Unit Condition E12 Indoor Fan Motor Trouble Diagnosis of Fan MotorLocations most susceptible to noise Trouble Correction Noise Malfunction and Electromagnetic InterferenceNoise malfunction Electromagnetic interferenceXMS0972 & PNR-XS1872 XMS1272 & PNR-XS1872 Pub. OI-85264181141000 Sanyo Mode D’EMPLOIContents FeaturesProduct Information Alert SymbolsInstallation Location Safety InstructionsUnit Display and Operation Button Names of PartsSymbols Remote Control Unit DisplayRemote Control Unit Sensor HR. Timer button 1-HOUR OFF TimerTemperature setting buttons Temp Mode selector buttonUsing the Remote Control Unit Operation with the Remote Control Unit Automatic fan speedManual fan speed How it works? Setting the TimerCooling and DRY Mode Special Remarks1030 pm 710 am 1100 am Present time Operation IndicationDo not Using the 1-HOUR OFF TimerAdjusting the Airflow Direction Tips for Energy SavingCleaning the main unit and remote control unit Care and CleaningWhen the air conditioner is not running Cleaning the flapsCare After a prolonged idle period How to remove the filterHow to remove the air intake grille Air filterTroubleshooting Wired Remote ControllerOperating Range XS1872 & PNR-XS1872 Pub. OI-85264181108001 Sanyo XS1271 XS1872OI-108-2-EG Important Multiple use is applied for the model XS1872 only OI-108-4-EG OI-108-5-EG OI-108-6-EG OI-108-7-EG OI-108-8-EG OI-108-9-EG OI-108-10-EG OI-108-11-EG OI-108-12-EG OI-108-13-EG OI-108-14-EG OI-108-15-EG Appendix C Installation Instructions For Indoor Unit Contents…In a Room For safe installation and trouble-free operation, you mustPlease Read Before Starting …In a Ceiling or WallOptional Copper Tubing Kit Tools Required for Installation not suppliedAccessories Supplied with Unit Table GeneralAdditional Materials Required for Installation Installation Site SelectionH1, H2, H3, H4 Embedding the Tubing and WiringPlacing the Unit Inside the Ceiling How to Install the Indoor UnitPreparation for Suspending Suspending the Indoor UnitFastener is on the side Installing the Drain PipingDo not install an air bleeder as Attach so that the hose band10a Checking the DrainageIndoor unit Gaps Ceiling surface Ceiling panel Installing the Ceiling PanelAttaching the air-intake grille Wiring the Ceiling Panel and the IndicatorWiring Instructions General precautions on wiring Checking After InstallationWhen Removing the Ceiling Panel for Servicing Adjusting the Auto FlapHow to connect wiring to the terminal For Indoor Unit For Outdoor Unit For solid core wiring or F-cableFor stranded wiring How to Test Run the Air Conditioner Mounting on a Wall Remote Control Unit Installation PositionRear side Remote control unit mount To take out the remote control unit, pull it forwardAddress Setting of the Remote Control Unit Address SwitchInstallation Check Sheet Connecting a Home Automation DeviceSTK-RCS-7TWSUA Pub. OI-85264181139000 Sanyo STK-RCS-7TWSUADo not cool or heat the room too much Hot Start Heating System SET button Timer and Present Time setting buttonsAuto Timer Select buttonAutomatic Operation Only for COOL/DRY/HEAT Model Heating Mode Only for COOL/DRY/HEAT Model Remote Control Unit DisplayProgrammed Daily on / OFF910 pm 710 am 1130 pm Present time Sweep Cool Drysweep Heat FAN Appendix E Installation Instructions STK-RCS-7TWSUA Installation location Parts supplied with the remote controllerRemote controller installation guidelines How to install the remote controllerInstalling directly onto the wall Installing with in-wall junction boxHow to wire the remote controller ON/OFF

XMS1272, XMS0972 specifications

The Sanyo XMS0972 and XMS1272 are remarkable air conditioning units that blend efficiency with cutting-edge technology. Designed for residential and commercial spaces, these models promise comfort while optimizing energy consumption.

One of the standout features of both the XMS0972 and XMS1272 is their advanced inverter technology. This feature allows the units to adjust their cooling capacity based on the room's ambient temperature. As a result, the air conditioners can maintain a consistent temperature without the frequent on/off cycles associated with traditional units. This not only ensures a more stable climate but also significantly reduces energy consumption, making them eco-friendly options.

Another significant characteristic is the Quiet Operation mode. Both models are engineered with noise reduction technology, providing a tranquil environment for users. This is particularly beneficial for bedrooms, offices, or libraries where noise levels can be a concern. The XMS models operate at a whisper-quiet level, allowing users to focus on their tasks or enjoy a peaceful night's sleep without disruption.

The Sanyo XMS0972 and XMS1272 also feature a user-friendly digital interface. With an intuitive remote control and an easy-to-read display, setting your desired temperature or switching modes has never been easier. Moreover, the smart diagnostic capability allows for quick troubleshooting, helping to identify any issues to ensure peak performance throughout their lifespan.

Both models are equipped with a 24-hour timer, adding convenience for users who wish to come home to a pre-cooled or heated environment. This feature enhances comfort and saves energy when the unit is not in use.

In terms of design, the Sanyo XMS units boast a sleek and modern aesthetic that seamlessly integrates into various interior styles. Their compact size allows for flexible installation options, making them suitable for various living and working spaces.

The XMS line also emphasizes air purification, incorporating advanced filters that capture dust, allergens, and other pollutants. This results in not just temperature control but also improved air quality, contributing to a healthier living environment.

In conclusion, the Sanyo XMS0972 and XMS1272 air conditioning units stand out for their energy efficiency, quiet operation, user-friendly features, and air purification capabilities. These characteristics make them an ideal choice for individuals and businesses looking for reliable and sophisticated climate control solutions.