Sanyo XMS1272, XMS0972 service manual How to Install the Indoor Unit, Preparation for Suspending

Page 77

3. How to Install the Indoor Unit

3-1. Preparation for Suspending

This unit uses a drain pump. Use a carpenter’s level to check that the unit is level.

3-2. Suspending the Indoor Unit

(1)Fix the suspension bolts securely in the ceiling using the method shown in the diagrams, by attaching them to the ceiling support structure, or by any other method that ensures that the unit will be securely and safely suspended. (Fig. 6-1)

(2)Follow the diagram to make the holes in the ceiling.

(3)Determine the pitch of the suspension bolts using the supplied full-scale installation diagram. The dia- gram shows the relationship between the positions of the suspension fitting, unit, and panel. (Fig. 6-2)

3-3. Placing the Unit Inside the Ceiling

(1)Be sure to remove the fan protection (4pcs) for transportation before hanging up the indoor unit.

(2)When placing the unit inside the ceiling, determine the pitch of the suspension bolts using the supplied full-scale installation diagram. (Fig. 6-3)

Tubing and wiring must be laid inside the ceiling when suspending the unit. If the ceiling is already constructed, lay the tubing and wiring into position for connection to the unit before placing the unit inside the ceiling.

(3)The length of suspension bolts must be appropriate for a distance between the bottom of the bolt and the bottom of the unit of more than 19/32" (15 mm) as shown in the diagram. (Fig. 6-3)

(4)Thread the 3 hexagonal nuts (locally purchased) and 2 supplied washers onto each of the 4 suspension bolts as shown in the diagram. Use 1 nut and 1 washer for the upper side, and 2 nuts and 1 washer for the lower side, so that the unit will not fall off the suspension lugs. (Fig. 6-4)

(5)Adjust so that the distance between the unit and the ceiling bottom is 1/2" (13 mm) to 23/32" (18 mm). Tighten the nuts on the upper side and lower side of the suspension lug. (Fig. 6-4)

Hole-in-anchor

Concrete

Insert

Hole-in-plug

Suspension bolt (M10 or 3/8") (locally purchased)

Fig. 6-1

23-5/8"(600mm)

Ceiling opening dimensions

21-1/32"(534mm)

Suspension bolt pitch

 

 

 

 

 

 

 

 

 

 

 

 

 

Ceiling opening dimensions

 

 

21-1/32"(534mm)

Suspension bolt pitch

23-5/8"(600mm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22-5/8"(575mm)

Drain tube

 

 

 

 

 

 

 

 

 

 

 

2-3/32"

6-5/16"

6-11/16"

connection port

 

 

 

(outer dia

1-1/32"(

26mm))

 

 

(53mm)

(160mm)

(170mm)

1-25/32"

 

 

 

 

 

 

(45mm)

 

 

 

8-15/32"

(215mm)

11-5/32"(283mm)

 

 

4-19/32"

(117mm)

1-25/32" (45mm)

 

 

 

 

1-3/16"

(30mm)

 

 

Power supply port

Refrigerant tubing joint

 

 

 

 

 

 

 

(narrow tube side)

 

 

 

 

 

 

 

 

1/4( 6.35mm) (flared)

 

 

 

 

 

Fig. 6-2

)

Over 19/32" (15mm)

 

1/2" — 23/32" (13~18mm

Supplied screw

Full-scale installation diagram

(printed on top of container box)

 

 

 

Fig. 6-3

 

 

 

 

 

 

 

 

 

 

 

Suspension bolt

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nuts and washers

 

 

 

 

 

 

 

 

 

 

 

Suspension lug

(used for upper and lower)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Double nut

Notch

1/2" — 23/32" (13~18mm)

Fig. 6-4

6

Image 77
Contents 17,500BTU / h 11,900BTU / hSafety Precautions Prohibit Table of Contents STK-RCS-7TWSUA Applicable MULTI-OUTDOOR Units Indoor Air Intake Temp Outdoor Air Intake Temp Operating RangeIndoor Unit XMS0972 & PNR-XS1872 SpecificationsUnit Specifications 208V Indoor UnitXMS0972 & PNR-XS1872 XMS1272 & PNR-XS1872 XMS1272 & PNR-XS1872 XS1872 & PNR-XS1872 XS1872 & PNR-XS1872 Indoor Unit Major Component SpecificationsIndoor Unit Body XMS0972 Indoor Unit PanelIndoor Unit Body XMS1272 Indoor Unit Body XS1872 ModelKTEC-35-S98 Other Component SpecificationsIndoor heat exchanger sensor ModelPT2M-51H-S3534 Dimensional DataIndoor Unit XS1872 & PNR-XS1872 Indoor unit Refrigerant Flow DiagramRefrigerant Flow Diagram 8FA2 Electrical Data5250-46900 Disassembly Procedure MaintenanceDisconnect the connectors in the control box Remove the air intake grillRemove the ceiling panel Remove the power box and control box Remove the indoor air temperature sensorScrew Ground cable CN07 ScrewCN03 CN09 CN06 Remove the main body lower section Remove the heat exchanger sensor Remove the drain pump and float switchRemove the heat exchanger Remove the turbo fan and fan motorOperation Functions FunctionsEmergency operation PAM- controlLamp colors Timer backupFreeze prevention Protective FunctionsMethod of Self-Diagnostics TroubleshootingPrecautions before Performing Inspection or Repair Self-diagnostics Lamps Checking the Indoor and Outdoor Units Using the TEST/T-RUN terminalsReplace the controller Replace the circuit board or the fuseBefore the Operation Serial Communication Error Identification ProcedureOff Blinking Illuminated Condition E01Terminal board Outdoor Unit Condition E12 Indoor Fan Motor Trouble Diagnosis of Fan MotorNoise malfunction Noise Malfunction and Electromagnetic InterferenceElectromagnetic interference Locations most susceptible to noise Trouble CorrectionXMS0972 & PNR-XS1872 XMS1272 & PNR-XS1872 Pub. OI-85264181141000 Sanyo Mode D’EMPLOIContents FeaturesInstallation Location Alert SymbolsSafety Instructions Product InformationUnit Display and Operation Button Names of PartsSymbols Remote Control Unit DisplayRemote Control Unit Temperature setting buttons Temp HR. Timer button 1-HOUR OFF TimerMode selector button SensorUsing the Remote Control Unit Manual fan speed Operation with the Remote Control UnitAutomatic fan speed Cooling and DRY Mode Setting the TimerSpecial Remarks How it works?1030 pm 710 am 1100 am Present time Operation IndicationAdjusting the Airflow Direction Using the 1-HOUR OFF TimerTips for Energy Saving Do notWhen the air conditioner is not running Care and CleaningCleaning the flaps Cleaning the main unit and remote control unitHow to remove the air intake grille How to remove the filterAir filter Care After a prolonged idle periodOperating Range TroubleshootingWired Remote Controller XS1872 & PNR-XS1872 Pub. OI-85264181108001 Sanyo XS1271 XS1872OI-108-2-EG Important Multiple use is applied for the model XS1872 only OI-108-4-EG OI-108-5-EG OI-108-6-EG OI-108-7-EG OI-108-8-EG OI-108-9-EG OI-108-10-EG OI-108-11-EG OI-108-12-EG OI-108-13-EG OI-108-14-EG OI-108-15-EG Appendix C Installation Instructions For Indoor Unit ContentsPlease Read Before Starting For safe installation and trouble-free operation, you must…In a Ceiling or Wall …In a Room Accessories Supplied with Unit Table Tools Required for Installation not supplied General Optional Copper Tubing KitAdditional Materials Required for Installation Installation Site SelectionH1, H2, H3, H4 Embedding the Tubing and WiringPreparation for Suspending How to Install the Indoor UnitSuspending the Indoor Unit Placing the Unit Inside the CeilingDo not install an air bleeder as Installing the Drain PipingAttach so that the hose band Fastener is on the side10a Checking the DrainageIndoor unit Gaps Ceiling surface Ceiling panel Installing the Ceiling PanelAttaching the air-intake grille Wiring the Ceiling Panel and the IndicatorWhen Removing the Ceiling Panel for Servicing Checking After InstallationAdjusting the Auto Flap Wiring Instructions General precautions on wiringFor stranded wiring How to connect wiring to the terminal For Indoor UnitFor Outdoor Unit For solid core wiring or F-cable How to Test Run the Air Conditioner Rear side Remote control unit mount Remote Control Unit Installation PositionTo take out the remote control unit, pull it forward Mounting on a WallAddress Setting of the Remote Control Unit Address SwitchInstallation Check Sheet Connecting a Home Automation DeviceSTK-RCS-7TWSUA Pub. OI-85264181139000 Sanyo STK-RCS-7TWSUADo not cool or heat the room too much Hot Start Heating System SET button Timer and Present Time setting buttonsAuto Timer Select buttonAutomatic Operation Only for COOL/DRY/HEAT Model Heating Mode Only for COOL/DRY/HEAT Model Remote Control Unit Display910 pm 710 am 1130 pm Present time ProgrammedDaily on / OFF Sweep Cool Drysweep Heat FAN Appendix E Installation Instructions STK-RCS-7TWSUA Remote controller installation guidelines Parts supplied with the remote controllerHow to install the remote controller Installation locationInstalling directly onto the wall Installing with in-wall junction boxHow to wire the remote controller ON/OFF