Sanyo KMS2472, KMS1872 Self-diagnostics Lamps, Indication on indoor unit, Blinking On Illuminated

Page 36

(1)Self-diagnostics Lamps

INDOOR UNIT

(1) OPERATION lamp

(2) TIMER lamp

(3) QUIET lamp ION lamp

OPERATION button

REMOTE CONTROL receiver

Since the indications cover various units, the corresponding parts listed below may not be present in some models.

Indication on indoor unit

.... OFF

 

 

.... Blinking

.... ON (Illuminated)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Quiet

Timer

Operation

Code

Diagnostics item

 

 

 

 

 

Diagnostics contents

(3)

(2)

(1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S01

Room temperature sensor failure

(1)Sensor open circuit or short circuit

 

 

 

 

 

 

 

 

 

(2)Contact failure at connector or open circuit at terminal crimping location

 

 

 

S02

Indoor heat exchanger sensor failure

 

 

 

 

(short-circuit detection only for the humidity sensor)

 

 

 

 

 

 

 

(3)Indoor/outdoor circuit board failure

 

 

 

 

 

 

 

S03

Humidity sensor failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S04

Compressor temperature sensor failure

(1)Sensor open circuit or short circuit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(2)Contact failure at connector or open circuit at terminal crimping location

 

 

 

S05

Outdoor heat exchanger sensor failure

 

 

 

(3)Outdoor circuit board failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S06

Outdoor air temperature sensor failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S07

failureOutdoor electrical current detection

Outdoor circuit board failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E01

Indoor/outdoor communications failure

(1)

Mis-wiring

(2) AC power failure

(3) Blown fuse

(4) Power relay failure

 

 

 

(5)

Indoor or outdoor circuit board failure

 

 

 

 

 

 

 

(serial communications)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E02

• HIC circuit failure

(1)

HIC or power Tr failure (2) Outdoor fan does not turn.

(3) Instantaneous power outage

 

 

 

(4)

Service valve not opened.

(5) Outdoor fan blocked.

(6) Continuous overload operation

 

 

 

• Power Tr (transistor) circuit failure

 

 

 

 

 

(7)

Compressor failure

(8) Outdoor circuit board failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E03

Outdoor unit external ROM (OTP data)

(1)

External ROM data failure

 

(2) Outdoor circuit board failure

 

 

 

failure

 

 

 

 

E04

Peak current cut-off

(1)

Instantaneous power outage

(2) HIC or power transistor failure

 

 

 

(3)

Outdoor circuit board failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E05

PAM circuit failure

(1)

Outdoor circuit board failure

(2) Outdoor power supply voltage failure

 

 

 

Active circuit failure

 

 

 

 

 

 

 

 

 

 

 

 

 

E06

Compressor discharge overheat

(1) Electric expansion valve failure

(2) Capillaries choked

(3) Shortage of refrigerant

 

 

 

prevention activated.

(4) Continuous overload operation

(5) Outdoor fan does not rotate (6) Outdoor circuit board failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E07

Indoor fan operating failure

(1)

Fan motor failure

(2) Contact failure at connector

 

(3) Indoor circuit board failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E08

4-way valve switching failure

(1)

4-way valve failure (heat pump model only)

 

 

 

 

 

 

Indoor zero-cross failure

(2)

Outdoor circuit board failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E09

No-refrigerant protection

(1)

Service valve not opened.

 

(2) Shortage of refrigerant

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E10

DC compressor drive circuit failure

(1)

Open phase

(2) Outdoor circuit board failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E11

Outdoor fan operating failure

(1)

Fan motor failure

(2) Contact failure at connector

 

(3) Outdoor circuit board failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor system communications failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E12

Outdoor high-pressure SW

(1)

Mis-wiring

(2) Blown fuse

 

(3) Power relay failure

(4) Open phase

 

 

 

OLR operation

(5)

Outdoor circuit board failure

(6) Compressor failure

 

 

 

 

 

 

Outdoor power supply open phase

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor coil freezing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E13

Freeze-prevention operation activated.

(1)

Indoor fan system failure

(2) Shortage of refrigerant

(3) Low-temperature operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

36

Image 36
Contents Capacity Indoor Model No Product Code No 500BTU / h KMS0772 000BTU / h KMS097211,900BTU / h KMS1272 17,500BTU / h KMS1872Please Read Before Starting Table of Contents Applicable MULTI-OUTDOOR Units Temperature Indoor Air Intake Temp Outdoor Air Intake Temp Indoor Air Intake Temp Outdoor Air Intake TempUnit Specifications KMS0772208V KMS0972 KMS0972 KMS1272 KMS1272 KMS1872 KMS1872 KMS2472 KMS2472 Major Component Specifications Indoor UnitCB-KMS0972 CB-KMS1272 CB-KMS1872 CB-KMS2472 Other Component Specifications Temperature F CResistance k ohm Dimensional Data KMS0972 KMS1272Indoor Unit KMS1872 KMS2472 Refrigerant Flow Diagram Indoor Unit KMS0772 KMS0972 KMS1272 Indoor unitAir Throw Distance Charts Performance DataIndoor Unit Indoor Unit Indoor Unit Indoor Unit Electric Wiring Diagrams Indoor Unit KMS0772 KMS0972 KMS12728FA2-5257-70500-0 Operation Functions Emergency operationPAM- control Timer backup Lamp colorsProtective Functions Freeze preventionPrecautions before Performing Inspection or Repair Method of Self-DiagnosticsSelf-diagnostics Lamps Code Diagnostics itemIndication on indoor unit Blinking On IlluminatedReplace the controller Replace the circuit board or the fuseUsing the TEST/T-RUN terminals Checking the Indoor and Outdoor UnitsChecking the indoor unit Control Check items unit operation Checking the serial communicationsTrouble Diagnosis of Fan Motor Indoor Fan MotorNoise Malfunction and Electromagnetic Interference Noise malfunctionElectromagnetic interference Locations most susceptible to noise Trouble CorrectionKMS0772 KMS0972 KMS1272 KMS1872 KMS2472 Features Contents Alert SymbolsProduct Information Installation Location Safety InstructionsElectrical Requirements Names of Parts Unit Display and Operation Button Quiet lampRemote Control Unit Display Remote Control Unit HR. Timer buttonAdvance button TransmitterDRY Using the Remote Control Unit How to Install BatteriesTemperature Display Selector button ACL button ALL ClearUsing the Remote Control Unit Operation with the Remote Control Unit OperationOperation with the Remote Control Unit Press the ON/OFF operation buttonCooling and DRY Mode Night Setback Mode is used for saving energyQuiet Mode Power failure during operation Special RemarksClicking sound is heard from the air conditioner Setting the Timer Operation IndicationSetting the Timer To cancel a timer program Press the Cancel button1030 pm 710 am 1100 am Present time Using the 1-Hour OFF Timer Setting procedureCancellation procedure Operation together with the Daily ON/OFF Repeat TimerAdjusting the Airflow Direction Setting the airflow manuallyHorizontal Sweep functionCare and Cleaning When the air conditioner is not runningOperation without the Remote Control UnitCare and Cleaning How to remove the anti-mold filterHow to replace the anti-mold filter Air intake grilleHow to clean the air clean filter How to install the air clean filterCleaning the negative ion generator Washing the grille with waterTroubleshooting Operating RangeTrouble Possible Cause Remedy Appendix B Installation Instructions Contents For Indoor UnitFor safe installation and trouble-free operation, you must Please Read Before Starting…In a Ceiling or Wall …In a RoomGeneral Installation Site Selection Additional Materials Required for InstallationEmbedding the Tubing and Wiring 150 L1+L2+L3+L4 230How to Install the Indoor Unit Remove the Rear Panel from the UnitMake a Hole Install the Rear Panel on the Wall If Wooden WallIf Block, Brick, Concrete or Similar Type Wall How to remove the grille How to replace the grilleBe sure to wear work gloves Cut by the sharp aluminum finsIndoor unit types KMS1872, KMS2472 Wiring Instructions General precautions on wiring Shape the Indoor Side TubingWiring Instructions for Inter-unit Connections Loose wiring may cause Fore, be sure all wiring isHow to connect wiring to the terminal For Indoor Unit For Outdoor Unit For solid core wiring or F-cableMounting Right-side tubingSwitching drain hose and drain cap Left-side tubingDrain cap To unmount indoor unit Risk of Electric ShockHow to Test Run the Air Conditioner Operation lamp Timer lamp Quiet lamp ION lampRemote Control Unit Installation Position Mounting on a WallAddress Switch Address Setting of the Remote Control UnitConnecting a Home Automation device Installation Check Sheet