Sanyo KMS2472, KMS1872 Checking the Indoor and Outdoor Units, Using the TEST/T-RUN terminals

Page 38

8-3. Checking the Indoor and Outdoor Units

(1) Checking the indoor unit

No.

 

 

 

Control

 

 

 

 

 

 

 

 

 

 

 

 

Check items (unit operation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Use the remote controller to operate the

 

• The rated voltage must be present between inter-unit wirings 1 and 2.

 

 

unit in "TEST run" mode. To determine

 

• Connect a 5 k ohm resistor between inter-unit wirings 2 and 3. When the

 

 

whether the mode is currently in

 

 

 

 

 

 

voltage at both ends is measured, approximately 12 to 15V DC must

 

 

"TEST run" mode, check the 4 indicator

 

 

be output and the multimeter pointer must bounce once every 8

 

 

lamps on the unit. If all 4 are blinking,

 

 

seconds.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the current mode is "TEST run."

 

 

 

 

 

 

Or instead of measuring the voltage, you can insert an LED jig and

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

check that the LED flickers once every 8 seconds.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If there are no problems with the above, then check the outdoor unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

For the "Test run" procedure, refer to "4. How to Test Run the Air Conditioner" on Appendix B.

 

 

 

 

 

 

 

 

 

 

 

 

 

(2) Checking the outdoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No.

 

 

 

Control

 

 

 

 

 

 

 

 

 

 

 

 

Check items (unit operation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

Apply the rated voltage between outdoor

 

• The control panel LED (red) must illuminate.

 

 

 

 

 

 

 

 

 

unit terminals L1 and L2.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

Short-circuit the outdoor unit COM terminal

 

• The compressor and fan motor must all turn on.

 

 

 

 

 

 

 

 

 

to the T-RUN terminal.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If there are no problems with the above, then check the indoor unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Using the TEST/T-RUN terminals

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TEST/T-RUN terminals

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T-RUN

: Test run (compressor and fan motor turn ON).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TEST/MV : Compresses time to 1/60th (accelerates

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation by 60 times faster than normal).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(TEST)/MV

 

T-RUN

 

COM

 

 

(3) Checking the serial communications

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.... OFF

.... Blinking

 

.... Illuminated

 

 

 

 

Control 1

 

 

 

 

 

 

Control 2

 

 

 

 

Initial self-diagnostics

 

Short-circuit terminals 2 and 3 on

Short-circuit terminals 2 and 3 on

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the indoor unit terminal plate.

the outdoor unit terminal plate.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Probable location of malfunction

 

Quiet

 

Timer

Operation

 

Quiet

 

Timer

Operation

Quiet

 

Timer

 

Operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

( 3 )

 

( 2 )

( 1 )

 

( 3 )

 

 

( 2 )

 

 

( 1 )

 

( 3 )

 

 

( 2 )

 

 

( 1 )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit circuit board failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit circuit board failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Failure (open circuit, contact failure, etc.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

in the inter-unit wirings

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit circuit board failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Turn the power OFF before performing short circuiting procedures.

Refer to the previous pages when performing system self-diagnostics.

So that the check can be made quickly, indicators blink at first communication after power ON.

Before performing the above checks, perform “TEST run” operation, and check that the rated voltage is output to terminals L1 and L2 on the outdoor unit. If it is not output, there is a failure related to the indoor unit power.

38

Image 38
Contents 11,900BTU / h KMS1272 Capacity Indoor Model No Product Code No 500BTU / h KMS0772000BTU / h KMS0972 17,500BTU / h KMS1872Please Read Before Starting Table of Contents Applicable MULTI-OUTDOOR Units Temperature Indoor Air Intake Temp Outdoor Air Intake Temp Indoor Air Intake Temp Outdoor Air Intake TempUnit Specifications KMS0772208V KMS0972 KMS0972 KMS1272 KMS1272 KMS1872 KMS1872 KMS2472 KMS2472 Major Component Specifications Indoor UnitCB-KMS0972 CB-KMS1272 CB-KMS1872 CB-KMS2472 Resistance k ohm Other Component SpecificationsTemperature F C Dimensional Data KMS0972 KMS1272Indoor Unit KMS1872 KMS2472 Refrigerant Flow Diagram Indoor Unit KMS0772 KMS0972 KMS1272 Indoor unitAir Throw Distance Charts Performance DataIndoor Unit Indoor Unit Indoor Unit Indoor Unit Electric Wiring Diagrams Indoor Unit KMS0772 KMS0972 KMS12728FA2-5257-70500-0 PAM- control Operation FunctionsEmergency operation Timer backup Lamp colorsProtective Functions Freeze preventionPrecautions before Performing Inspection or Repair Method of Self-DiagnosticsIndication on indoor unit Self-diagnostics LampsCode Diagnostics item Blinking On IlluminatedReplace the controller Replace the circuit board or the fuseChecking the indoor unit Control Check items unit operation Using the TEST/T-RUN terminalsChecking the Indoor and Outdoor Units Checking the serial communicationsTrouble Diagnosis of Fan Motor Indoor Fan MotorElectromagnetic interference Noise Malfunction and Electromagnetic InterferenceNoise malfunction Locations most susceptible to noise Trouble CorrectionKMS0772 KMS0972 KMS1272 KMS1872 KMS2472 Features Product Information ContentsAlert Symbols Electrical Requirements Installation LocationSafety Instructions Names of Parts Unit Display and Operation Button Quiet lampRemote Control Unit Display Advance button Remote Control UnitHR. Timer button TransmitterDRY Temperature Display Selector button Using the Remote Control UnitHow to Install Batteries ACL button ALL ClearUsing the Remote Control Unit Operation with the Remote Control Unit OperationOperation with the Remote Control Unit Press the ON/OFF operation buttonCooling and DRY Mode Night Setback Mode is used for saving energyQuiet Mode Clicking sound is heard from the air conditioner Power failure during operationSpecial Remarks Setting the Timer Operation Indication1030 pm 710 am 1100 am Present time Setting the TimerTo cancel a timer program Press the Cancel button Cancellation procedure Using the 1-Hour OFF TimerSetting procedure Operation together with the Daily ON/OFF Repeat TimerHorizontal Adjusting the Airflow DirectionSetting the airflow manually Sweep functionOperation without the Remote Care and CleaningWhen the air conditioner is not running Control UnitHow to replace the anti-mold filter Care and CleaningHow to remove the anti-mold filter Air intake grilleCleaning the negative ion generator How to clean the air clean filterHow to install the air clean filter Washing the grille with waterTrouble Possible Cause Remedy TroubleshootingOperating Range Appendix B Installation Instructions Contents For Indoor Unit…In a Ceiling or Wall For safe installation and trouble-free operation, you mustPlease Read Before Starting …In a RoomGeneral Installation Site Selection Additional Materials Required for InstallationEmbedding the Tubing and Wiring 150 L1+L2+L3+L4 230Make a Hole How to Install the Indoor UnitRemove the Rear Panel from the Unit If Block, Brick, Concrete or Similar Type Wall Install the Rear Panel on the WallIf Wooden Wall Be sure to wear work gloves How to remove the grilleHow to replace the grille Cut by the sharp aluminum finsIndoor unit types KMS1872, KMS2472 Wiring Instructions General precautions on wiring Shape the Indoor Side TubingWiring Instructions for Inter-unit Connections How to connect wiring to the terminal For Indoor Unit Loose wiring may causeFore, be sure all wiring is For Outdoor Unit For solid core wiring or F-cableMounting Right-side tubingDrain cap Switching drain hose and drain capLeft-side tubing To unmount indoor unit Risk of Electric ShockHow to Test Run the Air Conditioner Operation lamp Timer lamp Quiet lamp ION lampRemote Control Unit Installation Position Mounting on a WallAddress Switch Address Setting of the Remote Control UnitConnecting a Home Automation device Installation Check Sheet