D9412GV2/D7412GV2 Program Entry Guide 2.0 GV2MAIN

EN 15

Buzz on Fail

Default: No

Selection: Yes or No

 

Yes

 

Generate panel-wide trouble tones

 

 

 

 

and display PHONE FAIL # at

 

 

 

 

keypads when a Phone Fail Event

 

 

 

 

occurs.

 

 

 

 

 

 

No

 

Does not generate trouble tones at

 

 

 

 

keypads when a Phone Fail Event

 

 

 

 

occurs. PHONE FAIL # still displays.

 

 

 

 

 

 

 

 

 

 

 

 

To meet UL 864 requirements, set this

 

 

 

 

 

 

parameter to Yes.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Phone Supv Time must be programmed to use this feature.

When Buzz on Fail is Yes, users can disable the resulting trouble tone on individual keypads by setting CC# Trouble Tone to No.

Two Phone Lines

Default: No

Selection: Yes or No

 

Yes

 

The D928 Dual Phone Line Module

 

 

 

is installed. The LEDs on the D928

 

 

 

light to indicate primary or secondary

 

 

 

line trouble and COMM FAIL.

 

 

 

 

 

No

 

D928 Dual Phone Line Module is not

 

 

 

installed.

 

 

 

 

 

 

 

 

 

When using two telephone lines, set this

 

 

 

 

parameter to Yes to meet UL 864

 

 

requirements.

 

 

 

 

 

Program Phone Supv Time when using

 

 

 

 

 

 

two phone lines.

 

 

 

 

 

 

 

 

BFSK Duress Code

Default: 0

Selection: 0 to 9

Expand Test Rpt

Default: No

Selection: Yes or No

Yes

Off-normal events listed in Routing

 

Group Test Reports are reported to

 

the central station.

 

 

No

Off-normal conditions for the events

 

listed in the Routing Group Test

 

Reports at test time are not reported.

 

 

Use this program item to add system event information to scheduled Test Reports. Refer to Section 5.2 Skeds on page 115.

 

This parameter relates to Sked Function

 

Code 9 (Test Report) because it allows a

 

Sked to send Expanded Test Report

 

information. Expand Test Rpt does not

 

affect Sked Function Codes 28

 

(Expanded Off-Normal Test Report) and

 

29 (Non-Expanded Off-Normal Test

 

Report).

2.3

Routing

Use routing to select full or partial groups of events that report to up to four different destinations. Routing includes choosing the most important destination (route number), reporting the events to a single or multiple destination, and selecting a backup destination if the events fail.

2.3.1Called Party Disconnect

Telephone companies provide called party disconnect to allow the called party to terminate a call. The called party must go on hook (hang up) for a fixed interval before a dial tone is available for a new call. This interval varies with telephone company equipment. D9412GV2/D7412GV2 firmware allows for called party disconnect by adding a 35-sec on- hook interval to the dial-tone detect function. If the control panel does not detect a dial tone in 7 sec, it puts the phone line on hook for 35 sec to activate called party disconnect. The phone line goes off hook and begins a 7-sec dial tone detect. If no dial tone is detected, the control panel dials the number anyway. Each time the number is dialed, the control panel records this as an attempt. After ten attempts, the control panel enters communications failure and Comm Fail Route # appears on the keypads.

If Duress Enable in Area Parameters is Yes and Modem Format in Phone Parameters is No, you must program a number to identify Duress Reports at the central station.

Bosch Security Systems, Inc. 10/08 F01U003636-04

Image 15
Contents D9412GV2/D7412GV2 Prompt Sub-Prompt Type Styles Used in this ManualTable of Contents Tables SIA CP-01 Quick ReferenceProgramming Prompts Directory Document Name Part Number Using this Program Entry GuideDifferences between the D9412GV2 and D7412GV2 Features Literature ReferencedGV2MAIN Product HandlersProgramming Error Displays Guide to Programming OptionsProgramming the Control Panel with the D5200 Programmer Guide to UL 864 Programming Requirements Settings Permitted in UL Recommendation UL 864 Programming Recommendations Prompt Possible SettingsPhone Default Blank Selection Up to 24 characters do not enterFor SIA CP-01 Compliance Call Waiting Disable PhoneModem IIIa2 Communication Default Yes Selection Yes or NoPhone Parameters Modem FormatConettix D6600/D6100 Point/User FlagFail is Yes and CC Trouble Tone is Yes Alarm On FailPhone Supv Time Dtmf DialingBfsk Duress Code RoutingBuzz on Fail Two Phone LinesProgramming a Duplicate Report Programming Primary and Backup DestinationsRoute Number Groups Which Has the Highest Priority? Enhanced Routing# Backup Device # Primary DeviceView Events? Burglar Reports Fire ReportsBurglar Reports Fire Reports Selection Report DescriptionSending Test Reports User ReportsTest Reports User Reports Selection Report DescriptionTest Reports Selection Description Diagnostic Reports Selection DescriptionRelay Reports AutoFunc ReportsRPS Reports Point Reports RPS Reports Selections Report DescriptionPoint Reports Selections Description User Change Reports Selections Description Access ReportsAccess Reports Selections Report Description User Chng ReportsProgramming a Primary and Backup Destination Enhanced RoutingEnhanced Routing .4 Enhanced Routing on RG# Primary Pager RG# Backup SDIRG# Backup SDI, and Enhanced RG# Primary SDIProgramming the Pager Phone Number Pager Display FieldsEvent Priorit Event Description Number Event Descriptions, Priorities, and NumbersPower Supervision Default Selection 1 to 90 Blank and 0 are invalidAC Fail Time Default 60 sec Selection 10 to 300 sec in 5-sec Increments AC Fail DisplayAC Fail/Res Rpt Printer Parameters ## Supervised ## Scope## A1 through A8 in Scope RPS Parameters Log % Full RPS PasscodeAnswer Disarmed RPS Call BackRPS Line Monitor Answer ArmedMiscellaneous RPS PhDuress Type # Area On Cancel ReportArea Parameters AreaProgramming Ten-Digit Account Numbers Programming Account Numbers in 9000 Series Control PanelsProgramming Four-Digit Account Numbers Programming Four-Digit Account Numbers D5200 Programmer# Exit Tone # Delay Res# FA Bypass Max # Auto Watch# Duress Enable # Duress Enable must be set to YesVerify Time to 60 sec # Area Type Shared Area Arming Sequence Shared-Area Characteristics Arming a Shared AreaAccess Control Readers Assigned to the Shared Area Disarming a Shared Area# Burg Pat # Fire Time# Fire Pat # Burg Time# Single Ring # Bell TestRing # Acct O/C # Fail to Open # Disable O/C in Window# Area O/C # Auto CloseExit Dly Time If Disable O/C in Window is# Fail to Close # Restrictd O/C# Latest Close Time Default Selection 0000 toArming Features # Perimeter O/CD1255 Keypad Parameter Setup RequirementTo Early Ambush Timer on # Early Ambush# Exit Warning must be set to Yes # Exit Restart# Arm No Exit # Exit Warning# Entry Warning must be set to Yes # Entry WarningKeypad Command Center Cmd CenterCC# Supervised CC# A1through A8 in Scope Default Blank Selection To 128, A, B, C, and BlankCC# Area Assign CC# ScopeDefault Blank Selection 1 to 8, Blank CC# Entr Cycl DrCC# Assign Door CC# Arm Now Warn CC# Trouble ToneCC# Entry Tone CC# Exit Tone## Passcode Arm CC# Close DoorCC# EnhancCmdCtr CC# Passcode Follows ScopeCC# Abort Display CC# Cancel DisplayCC# Scroll Lock CC# Menu Key LockArea# Acct Is On Area# Is OnArea# Not Ready Area# Is OffSee .10.2 Area Text on Custom FunctionCF### Text CF### Key StrokesProgramming Custom Function Keystrokes CF### Custom Function KeystrokesExample Keypad Programming Choices CommandsUser Interface Keypad SelectionsMstr Arm Inst Master Arm DelayPerim Delay Watch ModeView Pt Status Perim PartialView Area Stat View MemoryChg Passcode Access Ctl LevelDoor Control Chg Time/DateUser Cmd Del UserExtend Close Print LogRemote Program Bypass a PtUnbypass a Pt Change RelayInvisible Walk Test Service WalkDisplay Rev Change SkedsCustom Functions Function 128 throughAuthority Level ## Disarm## Mstr Arm Inst ## Master Arm Delay## Perim Delay ## Watch Mode## Fire Test ## View Memory## View Pt Status ## Walk Test## Unlock Door ## Send Report## Door Control ## Cycle Door## Chg Passcode ## Access Ctl Lvl## Chg Display ## Chg Time/Date## View Log ## Del User## Extend Close ## User Cmd## Display Rev ## Reset Sensors## Change Relay ## Remote Program## Invisible Walk Test ## Service Walk## Default Text ## Change Skeds## Area O/C ## Perimeter O/C## C Function 128 through ## Force ArmLevel or L## Disarm Level authority to ## Security Level## Disarm Level ## Function LevelMenu Item #6 Watch ModeDefault Refer to the program record sheet Selection Function List## CC Address 1 through Relay Parameters# Alarm Bell # Reset SensorsArea Relays # Area Armed # Watch Mode# Area Fault # Force Armed# Duress Relay # Perim Fault# Silent Alarm Ground Fault DetectSummary Fire Tbl Summary AlarmPhone Fail Comm FailSummary SupBurg Summary TroublePass Code or Token Worksheet Bsfk User Code Report User ###Reporting and Logging User pass code User token or card### Passcode ### User Group### Area 1 through Area 8 Auth ### SU1 through SU3 Site ### Name### Mstr Site ### Mstr Crd DataPoint Index Point Index## Type Description Selection ## Type Description Disarmed is Yes NormalOpen ShortPoint Responses Applications for Point Responses 9, D, and E## Response of 8-9-A-B-C Example of 24-hour point ## Pt ResponseHour Points Example of Controlled point## Silent Bell ## Entry Delay## Ring Til Rst ## Audible After 2 Failures## Invisible Pt Point Response ## Buzz On FaultKeypad for any fault condition while the point ## Watch PointRelay Follows Point The relay ## RlyResp Type## Disp as Dvc ## Local While Disarmed## Disable Rst ## Local While Armed## FA Retrnable 5 Open/Close Options ## BP Retrnable## Bypassable A# Auto Close prompt## Cross Point ## Report Bypass at Occurrence## Fire Point ## ResettableParameter Abort Window ## Alarm AbortPoint Number ### Point Index### BFSK/Relay Codes/Relays ### Area Assign### Debounce ### BFSK/RelayCMD7 Point Text ### Point TextCMD7 Point Index CMD7 BFSK/RelayCMD9 Point Index CMD9 BFSK/RelayCMD9 Point Text Windows Window# Sunday # Thursday # Monday# Tuesday # Wednesday# Open Window Stop Default Selection Hhmm hours and minutesDisable O/C in Window is programmed Yes # Open Window StartProgramming to Link Two Days over Midnight # Close Early Begin# Close Window Stop # Close Window StartHoliday Indexes for O/C Windows # Xept Holiday# Holiday # Area 1 throughNormal Store Hours Opening and Closing Windows WorksheetUW# User Group User Windows #UW# Monday UW# Group EnableUW# Group Disable UW# SundaySked Number SkedsUW# Xept Holiday UW# Holiday 1 through## Function Code ## Area 1through## Point Number To 128 for D9412GV2 ## Relay NumberSelections Blank To 128 for D9412GV2 To 64 for D7412GV2## Defer Status ## Defer Test## Hourly Report If Expand Test Rpt in Phone## Cmd Center Cmd Center and Custom Func## Custom Func ## Door 1 through ## Access Ctl Level ### Access Ctl Level# ## Cmd Center 1throughAccess Authority Events No Entry Events Off ## Monday ## Time## Date ## SundayDate Holiday Indexes## Xept Holiday ## HolidayIndex 4 Days Index 1 DaysIndex 2 Days Index 3 DaysSDI Automation Enable SDI AutoIntroduction RPS and D5200 Handler RequirementsRTS Control Parity/StopDTR Control SupervisionEnable SDI RPS User Interface Modifications for CommandSDI RPS Parameters Call Back Enabled Refer to RPS IP Address Set RPS IP Address to 0 if Enable ExtRPS IP Address RPS Port NumberPrograms→Accessories→Communications For Best Data Smart OneFor US Robotics PC running Remote Programming Software RPS Modem Pstn External Modem ConnectionD9412GV2/D7412GV2 Program Entry Guide 6.0 GV2AUX Modem Init String Enable Ext ModemDefault Atdt Selection Not available Seize RelayPath # IP Add3 Enhanced CommPath # IP Add1 Path # IP Add2Path # Retry Count is set to Path # PortNumPath # Poll Rate Path # Poll Rate is set to 120 secDefault Selection Sec to 65535 sec Path # Ack WaitExample of Retry Count Path # Anti-Replay SDI RPS/Enhanced Communications ConfigurationDefault Selection 300, 1200, 2400, 4800, 9600, 14.4 K Path # Retry CountRoute Group Attempts RG# 1 AttemptFire Summary Sustain Secondary Ambush Code Enable Protocol TypeFire Supv Res Type Fire Trouble ResoundSwinger Count Default Selection 0, 3, 4, 5, orDefault Selection 3, or Passcode LengthEarly Armed Relay Cross Point ParametersCrystalTime Adj Perimeter RelayDefault 20 sec Selection Sec to 255 sec Cross Point TimeCross Point Ranges Within Groups #CC#Scope Door ProfileDoor # # Entry Area #Effects of Programming on Custom Function Activation Default Blank Selection Blank, 1 to 127, 129 to# Door Point # Interlock Point# Card Type # Auto Door?# Fire Unlock? # Disarm on Open?# Buzz Time Strike Profile# Strike Time # Shunt Time# REXShunt Only? Event Profile# Deact On Open? # RTE Shunt Only?# Exit Request? # Access Granted?# No Entry? # Enter Request?Programming the Control Panels for SIA CP--01 Compliance SIA CP-01 Quick ReferencePhone Parameters Power SupervisionPhone Printer ParametersBell Parameters Arming FeaturesKeypad Command Center Assignment51 Access Control FunctionsArea Relays Custom FunctionsPoint Index Command 7 and Command 104Point Assignments 102 Pass Code or Token Worksheet115 Holiday Indexes 124144 Bosch Security Systems, Inc /08 F01U003636-04 Bosch Security Systems, Inc. F01U003636-04
Related manuals
Manual 74 pages 9.34 Kb

D9412GV2 specifications

The Bosch D9412GV2 is an exceptional dishwasher that stands out in the competitive world of home appliances. Known for its reliability and advanced features, this model offers a blend of cutting-edge technology and user-friendly design that appeals to modern households.

One of the most noteworthy features of the D9412GV2 is its impressive cleaning performance. Boasting a unique combination of powerful jets and specialized wash cycles, it ensures that even the toughest stains are removed effectively. The dishwasher features Bosch’s patented PrecisionWash system, which utilizes intelligent sensors to monitor the wash cycle’s progress and adjust the water spray for optimal cleaning results. This not only guarantees sparkling dishes but also conserves water and energy.

In terms of capacity, the D9412GV2 does not disappoint. It has a spacious interior that is designed to accommodate up to 16 place settings, making it an ideal choice for families or those who frequently entertain guests. The adjustable racks and flexible loading options allow users to maximize space and customize the dishwasher to suit their unique needs. The third rack is particularly useful for utensils and smaller items, providing additional space that enhances efficiency.

The dishwasher is also engineered with noise reduction features for a quieter operation. With a sound rating of 44 decibels, it operates silently in the background, allowing for uninterrupted conversations and a peaceful home environment. This is especially beneficial for open-concept living spaces.

Energy efficiency is another hallmark of the Bosch D9412GV2. It is Energy Star certified, reflecting its commitment to sustainable practices. It uses less water and electricity without compromising performance, making it a responsible choice for eco-conscious consumers.

Moreover, the presence of the Home Connect feature allows users to control and monitor their dishwasher remotely via a smartphone app. This innovative technology enables users to start or stop cycles, receive notifications, and even download new wash programs, adding convenience and flexibility to busy lifestyles.

In conclusion, the Bosch D9412GV2 is a state-of-the-art dishwasher that excels in cleaning performance, capacity, and energy efficiency. With its innovative technologies and thoughtful design, it represents Bosch's commitment to quality and customer satisfaction, making it a valuable addition to any kitchen.