D9412GV2/D7412GV2 Program Entry Guide 2.0 GV2MAIN

EN 19

Restoral Reports are not sent if the control panel resets after a point is bypassed and then unbypassed. This is true for both Fire and Non-fire points.

User Reports

Selecting Yes enables a report to be sent when the event occurs.

Table 12: User Reports

Report

Selection

Report Description

 

s

 

R# Point

Yes, No

Point Bypass Event

Bypass

 

 

R# Forced

Yes, No

Forced Point Event

Point

 

 

R# Point

Yes, No

Point Opening Event

Open

 

 

R# Point

Yes, No

Point Closing Event

Close

 

 

R# Forced

Yes, No

Point Force Armed

Arm

 

 

R# Fail To

Yes, No

Fail to Open Event

Open

 

 

R# Fail To

Yes, No

Fail to Close Event

Close

 

 

R# Ext Clos

Yes, No

Extend Close Time

Tm

 

Event

R# Opening

Yes, No

Opening Events

Rpt

 

 

R# Forced

Yes, No

Point Forced Close

Close

 

Event

R# Closing

Yes, No

Closing Events

Rpt

 

 

R# FC Perim

Yes, No

Forced Close

Inst

 

Perimeter Instant

 

 

Armed Event

R# FC Perim

Yes, No

Forced Close

Delay

 

Perimeter Delay

 

 

Armed Event

R# Perim Inst

Yes, No

Perimeter Instant

Arm

 

Armed Event

R# Perim

Yes, No

Perimeter Delay

Delay Arm

 

Armed Event

R# Send User

Yes, No

User text

Text

 

 

 

 

 

Test Reports

To meet UL 864 requirements for Central Station and Remote Station applications, enable Test Reports.

Sending Test Reports

Automatic: To send a single Test Report (R# Test Report) automatically, enable Sked Function Code #9 (Test Report) in the Skeds section of the program. Refer to Table 13.

Manual: To send a single Test Report manually, enter [COMMAND][4][3] at the keypad. Refer to the Send Report prompt on page 63.

To expand this Test Report to include any off-normal point condition or other off-normal system conditions, Expand Test Rpt (refer to page 12) must be programmed Yes. Refer to the footnotes with Table 14 on page 20 for a list of event types that are included in an expanded test report. Additionally, the expanded test report includes Summary Fire Supervisory, Summary Fire Fault, Summary Controlled Point Fault, and Summary Point Device Fault conditions.

The control panel can generate an Expanded Off- Normal Test Report by using Sked Function Code 28 or a Non-Expanded Off-Normal Test Report using Sked Function Code 29. To generate this event, one or more points must be in an off-normal state at the time the Sked executes. Expanded Off-Normal Test Reports include the Off Normal Test Report Event as well as a panel-wide summary of off-normal point and system conditions. Non-Expanded Off-Normal Test Report Events are sent only when a point is in the off- normal state but sends only the Off-Normal Test Report Event.

Sending Status Reports

Automatic: To send a Status Report automatically that includes the events shown in the footnotes in Table 13, enable Sked Function Code #10 in the Skeds section of the program.

Manual: To send a Status Report manually that includes the events shown in the footnotes in Table 13, enter [COMMAND][4][2] at the keypad. Refer to the Send Report prompt on page 63.

Sending off-normal conditions as a Status Report following a Test Report is required by some automation systems. Sending off-normal conditions as a Non-status Report that follows a Test Report is required for other automation systems.

An off-normal condition is any point that is missing, trouble, supervisory, or in alarm. Also, points not cleared at the keypad report as off-normal.

Bosch Security Systems, Inc. 10/08 F01U003636-04

Image 19
Contents D9412GV2/D7412GV2 Prompt Sub-Prompt Type Styles Used in this ManualTable of Contents SIA CP-01 Quick Reference TablesProgramming Prompts Directory Document Name Part Number Using this Program Entry GuideDifferences between the D9412GV2 and D7412GV2 Features Literature ReferencedGV2MAIN Product HandlersGuide to Programming Options Programming Error DisplaysProgramming the Control Panel with the D5200 Programmer Guide to UL 864 Programming Requirements Settings Permitted in UL Recommendation UL 864 Programming Recommendations Prompt Possible SettingsPhone Default Blank Selection Up to 24 characters do not enterFor SIA CP-01 Compliance Call Waiting Disable PhoneModem IIIa2 Communication Default Yes Selection Yes or NoPhone Parameters Modem FormatConettix D6600/D6100 Point/User FlagFail is Yes and CC Trouble Tone is Yes Alarm On FailPhone Supv Time Dtmf DialingBfsk Duress Code RoutingBuzz on Fail Two Phone LinesProgramming a Duplicate Report Programming Primary and Backup DestinationsRoute Number Groups Which Has the Highest Priority? Enhanced Routing# Primary Device # Backup DeviceView Events? Burglar Reports Fire ReportsBurglar Reports Fire Reports Selection Report DescriptionSending Test Reports User ReportsTest Reports User Reports Selection Report DescriptionTest Reports Selection Description Diagnostic Reports Selection DescriptionAutoFunc Reports Relay ReportsRPS Reports RPS Reports Selections Report Description Point ReportsPoint Reports Selections Description User Change Reports Selections Description Access ReportsAccess Reports Selections Report Description User Chng ReportsEnhanced Routing Programming a Primary and Backup DestinationEnhanced Routing .4 Enhanced Routing on RG# Primary Pager RG# Backup SDIRG# Backup SDI, and Enhanced RG# Primary SDIProgramming the Pager Phone Number Pager Display FieldsEvent Priorit Event Description Number Event Descriptions, Priorities, and NumbersDefault Selection 1 to 90 Blank and 0 are invalid Power SupervisionAC Fail Time AC Fail Display Default 60 sec Selection 10 to 300 sec in 5-sec IncrementsAC Fail/Res Rpt Printer Parameters ## Scope ## Supervised## A1 through A8 in Scope RPS Parameters Log % Full RPS PasscodeAnswer Disarmed RPS Call BackRPS Line Monitor Answer ArmedRPS Ph MiscellaneousDuress Type # Area On Cancel ReportArea Parameters AreaProgramming Ten-Digit Account Numbers Programming Account Numbers in 9000 Series Control PanelsProgramming Four-Digit Account Numbers Programming Four-Digit Account Numbers D5200 Programmer# Exit Tone # Delay Res# FA Bypass Max # Auto Watch# Duress Enable must be set to Yes # Duress EnableVerify Time to 60 sec # Area Type Shared Area Arming Sequence Shared-Area Characteristics Arming a Shared AreaAccess Control Readers Assigned to the Shared Area Disarming a Shared Area# Burg Pat # Fire Time# Fire Pat # Burg Time# Bell Test # Single RingRing # Acct O/C # Fail to Open # Disable O/C in Window# Area O/C # Auto CloseExit Dly Time If Disable O/C in Window is# Fail to Close # Restrictd O/C# Latest Close Time Default Selection 0000 toArming Features # Perimeter O/CD1255 Keypad Parameter Setup RequirementTo Early Ambush Timer on # Early Ambush# Exit Warning must be set to Yes # Exit Restart# Arm No Exit # Exit Warning# Entry Warning must be set to Yes # Entry WarningCmd Center Keypad Command CenterCC# Supervised CC# A1through A8 in Scope Default Blank Selection To 128, A, B, C, and BlankCC# Area Assign CC# ScopeCC# Entr Cycl Dr Default Blank Selection 1 to 8, BlankCC# Assign Door CC# Arm Now Warn CC# Trouble ToneCC# Entry Tone CC# Exit Tone## Passcode Arm CC# Close DoorCC# EnhancCmdCtr CC# Passcode Follows ScopeCC# Abort Display CC# Cancel DisplayCC# Scroll Lock CC# Menu Key LockArea# Acct Is On Area# Is OnArea# Not Ready Area# Is OffSee .10.2 Area Text on Custom FunctionCF### Text CF### Key StrokesCF### Custom Function Keystrokes Programming Custom Function KeystrokesExample Keypad Programming Choices CommandsUser Interface Keypad SelectionsMstr Arm Inst Master Arm DelayPerim Delay Watch ModeView Pt Status Perim PartialView Area Stat View MemoryChg Passcode Access Ctl LevelDoor Control Chg Time/DateUser Cmd Del UserExtend Close Print LogRemote Program Bypass a PtUnbypass a Pt Change RelayInvisible Walk Test Service WalkDisplay Rev Change SkedsCustom Functions Function 128 throughAuthority Level ## Disarm## Mstr Arm Inst ## Master Arm Delay## Perim Delay ## Watch Mode## Fire Test ## View Memory## View Pt Status ## Walk Test## Unlock Door ## Send Report## Door Control ## Cycle Door## Chg Passcode ## Access Ctl Lvl## Chg Display ## Chg Time/Date## View Log ## Del User## Extend Close ## User Cmd## Display Rev ## Reset Sensors## Change Relay ## Remote Program## Invisible Walk Test ## Service Walk## Default Text ## Change Skeds## Area O/C ## Perimeter O/C## C Function 128 through ## Force ArmLevel or L## Disarm Level authority to ## Security Level## Disarm Level ## Function LevelMenu Item #6 Watch ModeDefault Refer to the program record sheet Selection Function List## CC Address 1 through Relay Parameters# Reset Sensors # Alarm BellArea Relays # Area Armed # Watch Mode# Area Fault # Force Armed# Duress Relay # Perim Fault# Silent Alarm Ground Fault DetectSummary Fire Tbl Summary AlarmPhone Fail Comm FailSummary SupBurg Summary TroublePass Code or Token Worksheet Bsfk User Code Report User ###Reporting and Logging User pass code User token or card### User Group ### Passcode### Area 1 through Area 8 Auth ### SU1 through SU3 Site ### Name### Mstr Site ### Mstr Crd DataPoint Index Point Index## Type Description Selection ## Type Description Disarmed is Yes NormalOpen ShortApplications for Point Responses 9, D, and E Point Responses## Response of 8-9-A-B-C Example of 24-hour point ## Pt ResponseHour Points Example of Controlled point## Silent Bell ## Entry Delay## Audible After 2 Failures ## Ring Til Rst## Invisible Pt Point Response ## Buzz On FaultKeypad for any fault condition while the point ## Watch PointRelay Follows Point The relay ## RlyResp Type## Disp as Dvc ## Local While Disarmed## Local While Armed ## Disable Rst## FA Retrnable 5 Open/Close Options ## BP Retrnable## Bypassable A# Auto Close prompt## Cross Point ## Report Bypass at Occurrence## Fire Point ## ResettableParameter Abort Window ## Alarm AbortPoint Number ### Point Index### BFSK/Relay Codes/Relays ### Area Assign### Debounce ### BFSK/RelayCMD7 Point Text ### Point TextCMD7 Point Index CMD7 BFSK/RelayCMD9 BFSK/Relay CMD9 Point IndexCMD9 Point Text Window Windows# Sunday # Thursday # Monday# Tuesday # Wednesday# Open Window Stop Default Selection Hhmm hours and minutesDisable O/C in Window is programmed Yes # Open Window StartProgramming to Link Two Days over Midnight # Close Early Begin# Close Window Stop # Close Window StartHoliday Indexes for O/C Windows # Xept Holiday# Holiday # Area 1 throughNormal Store Hours Opening and Closing Windows WorksheetUW# User Group User Windows #UW# Monday UW# Group EnableUW# Group Disable UW# SundaySked Number SkedsUW# Xept Holiday UW# Holiday 1 through## Area 1through ## Function Code## Point Number To 128 for D9412GV2 ## Relay NumberSelections Blank To 128 for D9412GV2 To 64 for D7412GV2## Defer Status ## Defer Test## Hourly Report If Expand Test Rpt in PhoneCmd Center and Custom Func ## Cmd Center## Custom Func ## Door 1 through ## Access Ctl Level ### Access Ctl Level# ## Cmd Center 1throughAccess Authority Events No Entry Events Off ## Monday ## Time## Date ## SundayDate Holiday Indexes## Xept Holiday ## HolidayIndex 4 Days Index 1 DaysIndex 2 Days Index 3 DaysSDI Automation Enable SDI AutoIntroduction RPS and D5200 Handler RequirementsRTS Control Parity/StopDTR Control SupervisionUser Interface Modifications for Command Enable SDI RPSSDI RPS Parameters Call Back Enabled Refer to RPS IP Address Set RPS IP Address to 0 if Enable ExtRPS IP Address RPS Port NumberFor Best Data Smart One Programs→Accessories→CommunicationsFor US Robotics PC running Remote Programming Software RPS Modem Pstn External Modem ConnectionD9412GV2/D7412GV2 Program Entry Guide 6.0 GV2AUX Modem Init String Enable Ext ModemDefault Atdt Selection Not available Seize RelayPath # IP Add3 Enhanced CommPath # IP Add1 Path # IP Add2Path # Retry Count is set to Path # PortNumPath # Poll Rate Path # Poll Rate is set to 120 secPath # Ack Wait Default Selection Sec to 65535 secExample of Retry Count Path # Anti-Replay SDI RPS/Enhanced Communications ConfigurationDefault Selection 300, 1200, 2400, 4800, 9600, 14.4 K Path # Retry CountRG# 1 Attempt Route Group AttemptsFire Summary Sustain Secondary Ambush Code Enable Protocol TypeFire Supv Res Type Fire Trouble ResoundSwinger Count Default Selection 0, 3, 4, 5, orDefault Selection 3, or Passcode LengthEarly Armed Relay Cross Point ParametersCrystalTime Adj Perimeter RelayCross Point Time Default 20 sec Selection Sec to 255 secCross Point Ranges Within Groups #CC#Scope Door ProfileDoor # # Entry Area #Effects of Programming on Custom Function Activation Default Blank Selection Blank, 1 to 127, 129 to# Door Point # Interlock Point# Card Type # Auto Door?# Fire Unlock? # Disarm on Open?# Buzz Time Strike Profile# Strike Time # Shunt Time# REXShunt Only? Event Profile# Deact On Open? # RTE Shunt Only?# Exit Request? # Access Granted?# No Entry? # Enter Request?Programming the Control Panels for SIA CP--01 Compliance SIA CP-01 Quick ReferencePhone Parameters Power SupervisionPhone Printer ParametersBell Parameters Arming FeaturesKeypad Command Center Assignment51 Access Control FunctionsArea Relays Custom FunctionsPoint Index Command 7 and Command 104Point Assignments 102 Pass Code or Token Worksheet115 Holiday Indexes 124144 Bosch Security Systems, Inc /08 F01U003636-04 Bosch Security Systems, Inc. F01U003636-04
Related manuals
Manual 74 pages 9.34 Kb

D9412GV2 specifications

The Bosch D9412GV2 is an exceptional dishwasher that stands out in the competitive world of home appliances. Known for its reliability and advanced features, this model offers a blend of cutting-edge technology and user-friendly design that appeals to modern households.

One of the most noteworthy features of the D9412GV2 is its impressive cleaning performance. Boasting a unique combination of powerful jets and specialized wash cycles, it ensures that even the toughest stains are removed effectively. The dishwasher features Bosch’s patented PrecisionWash system, which utilizes intelligent sensors to monitor the wash cycle’s progress and adjust the water spray for optimal cleaning results. This not only guarantees sparkling dishes but also conserves water and energy.

In terms of capacity, the D9412GV2 does not disappoint. It has a spacious interior that is designed to accommodate up to 16 place settings, making it an ideal choice for families or those who frequently entertain guests. The adjustable racks and flexible loading options allow users to maximize space and customize the dishwasher to suit their unique needs. The third rack is particularly useful for utensils and smaller items, providing additional space that enhances efficiency.

The dishwasher is also engineered with noise reduction features for a quieter operation. With a sound rating of 44 decibels, it operates silently in the background, allowing for uninterrupted conversations and a peaceful home environment. This is especially beneficial for open-concept living spaces.

Energy efficiency is another hallmark of the Bosch D9412GV2. It is Energy Star certified, reflecting its commitment to sustainable practices. It uses less water and electricity without compromising performance, making it a responsible choice for eco-conscious consumers.

Moreover, the presence of the Home Connect feature allows users to control and monitor their dishwasher remotely via a smartphone app. This innovative technology enables users to start or stop cycles, receive notifications, and even download new wash programs, adding convenience and flexibility to busy lifestyles.

In conclusion, the Bosch D9412GV2 is a state-of-the-art dishwasher that excels in cleaning performance, capacity, and energy efficiency. With its innovative technologies and thoughtful design, it represents Bosch's commitment to quality and customer satisfaction, making it a valuable addition to any kitchen.