Bosch Appliances D9412GV2 manual # Duress Relay, # Perim Fault, # Silent Alarm, AC Failure

Page 81

D9412GV2/D7412GV2 Program Entry Guide 2.0 GV2MAIN

EN 81

A# Duress Relay

Default: Blank

Selection: Blank, 1 to 128 (1 to 64 for D7412GV2), A, B, or C

Activates when a Duress alarm is generated from a keypad assigned to the specified area.

Burg Time needs a bell period programmed and A# Duress Enable must be Yes. This relay activates when the Burg Bell starts and deactivates when the Burg Bell time ends. The Burg Bell pattern has no effect on this relay function.

A# Perim Fault

Default: Blank

Selection: Blank, 1 to 128 (1 to 64 for D7412GV2), A, B, or C

Activates when a Controlled Perimeter point (P## Type 1) assigned to the specified area is faulted, regardless of the armed state of the area. This relay provides a steady output until all Perimeter points in the area return to normal.

This relay does not activate on interior faults. To detect all area point faults, program all points as Perimeter points in the area where this relay is assigned.

A# Silent Alarm

Default: Blank

Selection: Blank, 1 to 128 (1 to 64 for D7412GV2), A, B, or C

This relay activates when a point assigned to the specified area and programmed for P## Silent Bell goes into alarm.

Alternate Functions for A# Silent Alarm

Area 4: For time control, programming any value other than 60 in the Silent Alarm Relay for Area 4 enables AC (traditional) time control. Entering a value of 60 for Area 4 disables AC time control and switches the time control to the on-board crystal. This alternate function is replaced by the CrystalTime Adj prompt (refer to page 142) in the GV2AUX handler for the D9412GV2 and D7412GV2 in firmware v7.07 and later.

Area 5: Programming a non-zero value in the Silent Alarm Relay for Area 5 enables Ground Fault Detect on the D9412GV2 or D7412GV2 Control Panel using firmware versions 7.01 and 7.02 only. In version 7.03 and above, this setting is not used.

To meet UL 864 requirements, enable

Ground Fault Detect.

Refer to Ground Fault Detect in the D9412GV2/D7412GV2 Operation and Installation Guide (P/N: F01U003641).

Area 7: Perimeter Armed Relay, when enabled, turns the Fail to Close Relay function into a Perimeter Armed Relay function.

To change the Fail to Close Relay into a Perimeter Armed Relay function, program 63 in the Silent Alarm Relay for Area 7. Set A# Fail to Close Relay to the area to be Perimeter Armed. Refer to Area 8 for additional information. This alternate function is replaced by the Perimeter Relay prompt (refer to page 142) in the GV2AUX handler for the D9412GV2 and D7412GV2 in firmware v7.07 and later.

Area 8: Programming a value of 64 in the Silent Alarm Relay for Area 8 causes the Area Armed or Perimeter Armed Relay (refer to Area 7) to activate at the beginning of the exit delay time. This alternate function is replaced by the EarlyArmed Relay prompt (refer to page 142) in the GV2AUX handler for the D9412GV2 and D7412GV2 in firmware v7.07 and later.

2.13.2 Panel-Wide Relays

The following eleven relay options activate when they occur anywhere in the control panel. They are not restricted by area boundaries.

AC Failure

Default: Blank

Selection: Blank, 1 to 128 (1 to 64 for D7412GV2), A, B, or C

Activates when the control panel responds to an AC power failure as programmed in AC Fail Time in Section 2.5 Power Supervision on page 28. This relay automatically resets when AC power restores.

Use this relay to create audible annunciation. Enable the keypad’s trouble sounders for all applications except commercial fire systems.

Bosch Security Systems, Inc. 10/08 F01U003636-04

Image 81
Contents D9412GV2/D7412GV2 Prompt Sub-Prompt Type Styles Used in this ManualTable of Contents Tables SIA CP-01 Quick ReferenceProgramming Prompts Directory Differences between the D9412GV2 and D7412GV2 Features Using this Program Entry GuideLiterature Referenced Document Name Part NumberGV2MAIN Product HandlersProgramming Error Displays Guide to Programming OptionsProgramming the Control Panel with the D5200 Programmer Guide to UL 864 Programming Requirements Settings Permitted in UL Recommendation UL 864 Programming Recommendations Prompt Possible SettingsFor SIA CP-01 Compliance Call Waiting Disable Default Blank Selection Up to 24 characters do not enterPhone PhonePhone Parameters Default Yes Selection Yes or NoModem Format Modem IIIa2 CommunicationConettix D6600/D6100 Point/User FlagPhone Supv Time Alarm On FailDtmf Dialing Fail is Yes and CC Trouble Tone is YesBuzz on Fail RoutingTwo Phone Lines Bfsk Duress CodeRoute Number Groups Which Has the Highest Priority? Programming Primary and Backup DestinationsEnhanced Routing Programming a Duplicate Report# Backup Device # Primary DeviceView Events? Burglar Reports Fire ReportsFire Reports Selection Report Description Burglar ReportsTest Reports User ReportsUser Reports Selection Report Description Sending Test ReportsTest Reports Selection Description Diagnostic Reports Selection DescriptionRelay Reports AutoFunc ReportsRPS Reports Point Reports RPS Reports Selections Report DescriptionPoint Reports Selections Description Access Reports Selections Report Description Access ReportsUser Chng Reports User Change Reports Selections DescriptionProgramming a Primary and Backup Destination Enhanced RoutingEnhanced Routing .4 Enhanced Routing on RG# Backup SDI, and Enhanced RG# Backup SDIRG# Primary SDI RG# Primary PagerProgramming the Pager Phone Number Pager Display FieldsEvent Priorit Event Description Number Event Descriptions, Priorities, and NumbersPower Supervision Default Selection 1 to 90 Blank and 0 are invalidAC Fail Time Default 60 sec Selection 10 to 300 sec in 5-sec Increments AC Fail DisplayAC Fail/Res Rpt Printer Parameters ## Supervised ## Scope## A1 through A8 in Scope RPS Parameters Log % Full RPS PasscodeRPS Line Monitor RPS Call BackAnswer Armed Answer DisarmedMiscellaneous RPS PhDuress Type Area Parameters Cancel ReportArea # Area OnProgramming Four-Digit Account Numbers Programming Account Numbers in 9000 Series Control PanelsProgramming Four-Digit Account Numbers D5200 Programmer Programming Ten-Digit Account Numbers# FA Bypass Max # Delay Res# Auto Watch # Exit Tone# Duress Enable # Duress Enable must be set to YesVerify Time to 60 sec # Area Type Access Control Readers Assigned to the Shared Area Shared-Area Characteristics Arming a Shared AreaDisarming a Shared Area Shared Area Arming Sequence# Fire Pat # Fire Time# Burg Time # Burg Pat# Single Ring # Bell TestRing # Acct O/C # Area O/C # Disable O/C in Window# Auto Close # Fail to Open# Fail to Close If Disable O/C in Window is# Restrictd O/C Exit Dly TimeArming Features Default Selection 0000 to# Perimeter O/C # Latest Close TimeTo Early Ambush Timer on Parameter Setup Requirement# Early Ambush D1255 Keypad# Arm No Exit # Exit Restart# Exit Warning # Exit Warning must be set to Yes# Entry Warning must be set to Yes # Entry WarningKeypad Command Center Cmd CenterCC# Supervised CC# Area Assign Default Blank Selection To 128, A, B, C, and BlankCC# Scope CC# A1through A8 in ScopeDefault Blank Selection 1 to 8, Blank CC# Entr Cycl DrCC# Assign Door CC# Entry Tone CC# Trouble ToneCC# Exit Tone CC# Arm Now WarnCC# EnhancCmdCtr CC# Close DoorCC# Passcode Follows Scope ## Passcode ArmCC# Scroll Lock CC# Cancel DisplayCC# Menu Key Lock CC# Abort DisplayArea# Not Ready Area# Is OnArea# Is Off Area# Acct Is OnCF### Text Custom FunctionCF### Key Strokes See .10.2 Area Text onProgramming Custom Function Keystrokes CF### Custom Function KeystrokesExample User Interface CommandsKeypad Selections Keypad Programming ChoicesPerim Delay Master Arm DelayWatch Mode Mstr Arm InstView Area Stat Perim PartialView Memory View Pt StatusDoor Control Access Ctl LevelChg Time/Date Chg PasscodeExtend Close Del UserPrint Log User CmdUnbypass a Pt Bypass a PtChange Relay Remote ProgramDisplay Rev Service WalkChange Skeds Invisible Walk TestAuthority Level Function 128 through## Disarm Custom Functions## Perim Delay ## Master Arm Delay## Watch Mode ## Mstr Arm Inst## View Pt Status ## View Memory## Walk Test ## Fire Test## Door Control ## Send Report## Cycle Door ## Unlock Door## Chg Display ## Access Ctl Lvl## Chg Time/Date ## Chg Passcode## Extend Close ## Del User## User Cmd ## View Log## Change Relay ## Reset Sensors## Remote Program ## Display Rev## Default Text ## Service Walk## Change Skeds ## Invisible Walk Test## C Function 128 through ## Perimeter O/C## Force Arm ## Area O/C## Disarm Level ## Security Level## Function Level Level or L## Disarm Level authority toDefault Refer to the program record sheet Selection #6 Watch ModeFunction List Menu Item## CC Address 1 through Relay Parameters# Alarm Bell # Reset SensorsArea Relays # Area Fault # Watch Mode# Force Armed # Area Armed# Silent Alarm # Perim FaultGround Fault Detect # Duress RelayPhone Fail Summary AlarmComm Fail Summary Fire TblSummary SupBurg Summary TroublePass Code or Token Worksheet Reporting and Logging User ###User pass code User token or card Bsfk User Code Report### Passcode ### User Group### Area 1 through Area 8 Auth ### Mstr Site ### Name### Mstr Crd Data ### SU1 through SU3 SitePoint Index Point Index## Type Description Selection ## Type Description Open NormalShort Disarmed is YesPoint Responses Applications for Point Responses 9, D, and E## Response of 8-9-A-B-C Hour Points ## Pt ResponseExample of Controlled point Example of 24-hour point## Silent Bell ## Entry Delay## Ring Til Rst ## Audible After 2 Failures## Invisible Pt Keypad for any fault condition while the point ## Buzz On Fault## Watch Point Point Response## Disp as Dvc ## RlyResp Type## Local While Disarmed Relay Follows Point The relay## Disable Rst ## Local While Armed## FA Retrnable ## Bypassable ## BP RetrnableA# Auto Close prompt 5 Open/Close Options## Cross Point ## Report Bypass at Occurrence## Fire Point ## ResettablePoint Number ## Alarm Abort### Point Index Parameter Abort Window### Debounce ### Area Assign### BFSK/Relay ### BFSK/Relay Codes/RelaysCMD7 Point Index ### Point TextCMD7 BFSK/Relay CMD7 Point TextCMD9 Point Index CMD9 BFSK/RelayCMD9 Point Text Windows Window# Sunday # Tuesday # Monday# Wednesday # ThursdayDisable O/C in Window is programmed Yes Default Selection Hhmm hours and minutes# Open Window Start # Open Window StopProgramming to Link Two Days over Midnight # Close Early Begin# Close Window Stop # Close Window Start# Holiday # Xept Holiday# Area 1 through Holiday Indexes for O/C WindowsNormal Store Hours Opening and Closing Windows WorksheetUW# User Group User Windows #UW# Group Disable UW# Group EnableUW# Sunday UW# MondayUW# Xept Holiday SkedsUW# Holiday 1 through Sked Number## Function Code ## Area 1through## Point Number Selections Blank ## Relay NumberTo 128 for D9412GV2 To 64 for D7412GV2 To 128 for D9412GV2## Hourly Report ## Defer TestIf Expand Test Rpt in Phone ## Defer Status## Cmd Center Cmd Center and Custom Func## Custom Func ## Access Ctl Level# ## Access Ctl Level ### Cmd Center 1through ## Door 1 throughAccess Authority Events No Entry Events Off ## Date ## Time## Sunday ## Monday## Xept Holiday Holiday Indexes## Holiday DateIndex 2 Days Index 1 DaysIndex 3 Days Index 4 DaysIntroduction Enable SDI AutoRPS and D5200 Handler Requirements SDI AutomationDTR Control Parity/StopSupervision RTS ControlEnable SDI RPS User Interface Modifications for CommandSDI RPS Parameters Call Back Enabled RPS IP Address Set RPS IP Address to 0 if Enable ExtRPS Port Number Refer to RPS IP AddressPrograms→Accessories→Communications For Best Data Smart OneFor US Robotics PC running Remote Programming Software RPS Modem Pstn External Modem ConnectionD9412GV2/D7412GV2 Program Entry Guide 6.0 GV2AUX Default Atdt Selection Not available Enable Ext ModemSeize Relay Modem Init StringPath # IP Add1 Enhanced CommPath # IP Add2 Path # IP Add3Path # Poll Rate Path # PortNumPath # Poll Rate is set to 120 sec Path # Retry Count is set toDefault Selection Sec to 65535 sec Path # Ack WaitExample of Retry Count Default Selection 300, 1200, 2400, 4800, 9600, 14.4 K SDI RPS/Enhanced Communications ConfigurationPath # Retry Count Path # Anti-ReplayRoute Group Attempts RG# 1 AttemptFire Summary Sustain Fire Supv Res Type Enable Protocol TypeFire Trouble Resound Secondary Ambush CodeDefault Selection 3, or Default Selection 0, 3, 4, 5, orPasscode Length Swinger CountCrystalTime Adj Cross Point ParametersPerimeter Relay Early Armed RelayDefault 20 sec Selection Sec to 255 sec Cross Point TimeCross Point Ranges Within Groups Door # Door Profile# Entry Area # #CC#Scope# Door Point Default Blank Selection Blank, 1 to 127, 129 to# Interlock Point Effects of Programming on Custom Function Activation# Fire Unlock? # Auto Door?# Disarm on Open? # Card Type# Strike Time Strike Profile# Shunt Time # Buzz Time# Deact On Open? Event Profile# RTE Shunt Only? # REXShunt Only?# No Entry? # Access Granted?# Enter Request? # Exit Request?Programming the Control Panels for SIA CP--01 Compliance SIA CP-01 Quick ReferencePhone Power SupervisionPrinter Parameters Phone ParametersKeypad Command Center Assignment51 Arming FeaturesAccess Control Functions Bell ParametersArea Relays Custom FunctionsPoint Assignments 102 Command 7 and Command 104Pass Code or Token Worksheet Point Index115 Holiday Indexes 124144 Bosch Security Systems, Inc /08 F01U003636-04 Bosch Security Systems, Inc. F01U003636-04
Related manuals
Manual 74 pages 9.34 Kb

D9412GV2 specifications

The Bosch D9412GV2 is an exceptional dishwasher that stands out in the competitive world of home appliances. Known for its reliability and advanced features, this model offers a blend of cutting-edge technology and user-friendly design that appeals to modern households.

One of the most noteworthy features of the D9412GV2 is its impressive cleaning performance. Boasting a unique combination of powerful jets and specialized wash cycles, it ensures that even the toughest stains are removed effectively. The dishwasher features Bosch’s patented PrecisionWash system, which utilizes intelligent sensors to monitor the wash cycle’s progress and adjust the water spray for optimal cleaning results. This not only guarantees sparkling dishes but also conserves water and energy.

In terms of capacity, the D9412GV2 does not disappoint. It has a spacious interior that is designed to accommodate up to 16 place settings, making it an ideal choice for families or those who frequently entertain guests. The adjustable racks and flexible loading options allow users to maximize space and customize the dishwasher to suit their unique needs. The third rack is particularly useful for utensils and smaller items, providing additional space that enhances efficiency.

The dishwasher is also engineered with noise reduction features for a quieter operation. With a sound rating of 44 decibels, it operates silently in the background, allowing for uninterrupted conversations and a peaceful home environment. This is especially beneficial for open-concept living spaces.

Energy efficiency is another hallmark of the Bosch D9412GV2. It is Energy Star certified, reflecting its commitment to sustainable practices. It uses less water and electricity without compromising performance, making it a responsible choice for eco-conscious consumers.

Moreover, the presence of the Home Connect feature allows users to control and monitor their dishwasher remotely via a smartphone app. This innovative technology enables users to start or stop cycles, receive notifications, and even download new wash programs, adding convenience and flexibility to busy lifestyles.

In conclusion, the Bosch D9412GV2 is a state-of-the-art dishwasher that excels in cleaning performance, capacity, and energy efficiency. With its innovative technologies and thoughtful design, it represents Bosch's commitment to quality and customer satisfaction, making it a valuable addition to any kitchen.