Bosch Appliances D9412GV2 manual RPS Call Back, RPS Line Monitor, Answer Armed, Answer Disarmed

Page 34

D9412GV2/D7412GV2 Program Entry Guide 2.0 GV2MAIN

EN 34

RPS Call Back

Default:

No

Selection:

Yes or No

Yes

When the control panel hears the

 

correct RPS passcode, it hangs up

 

the phone, seizes the phone line,

 

then dials the programmed RPS

 

phone number (refer to the RPS Ph

 

prompt on page 35). This ensures

 

that the control panel only

 

communicates with RPS units

 

connected to the programmed phone

 

number.

 

If the call is answered manually, the

 

call back must be initiated manually.

 

 

No

The RPS session starts immediately.

 

No call back is required. The control

 

panel can engage in RPS sessions

 

when called from any phone number

 

and a proper RPS passcode is

 

identified.

 

 

This function allows the control panel, after it verifies the RPS passcode, to provide an additional level of security by hanging up and dialing the RPS phone number at the central station before allowing any upload or download.

When using the RPS Call Back feature, be sure to program the character “C” as the last digit in the RPS phone number when using DTMF Dialing.

RPS Line Monitor

Default:

Yes

Selection:

Yes or No

Yes

Allows the control panel to

 

communicate with RPS after the

 

answering machine answers the

 

phone.

 

 

No

Use No if the control panel does not

 

share the phone line with an

 

answering machine.

 

 

This program item enables a control panel that shares a phone line with an answering machine to communicate with RPS at the central station, even though the answering machine answers the phone. You must program Answer Armed or Answer Disarmed. The control panel must be in the correct armed state.

Program this item No if it causes false seizures of the phone line or if you do not use RPS. This indicates that a device using the same frequency tone is also using the phone line to which the control panel is connected.

If RPS Call Back is programmed Yes, the control panel hangs up the phone after the RPS tone and a proper RPS passcode is identified. It then calls the RPS phone number.

Answer Armed

Default:

Refer to the program record sheet

Selection:

1 to 15, or Blank

Blank

No answer.

 

 

1 to 15

The control panel answers the phone

 

after the specified number of rings

 

when all areas are master armed.

 

 

Set the telephone ring counter to answer when all areas are master armed. If any area in the control panel is perimeter armed or disarmed, the Answer Disarmed ring counter is used.

The remote programming software (RPS) considers perimeter armed as a disarmed state.

Answer Disarmed

Default:

Refer to the program record sheet

Selection:

1 to 15, or Blank

Blank

No answer.

 

 

1 to 15

The control panel answers the

 

phone after the specified number of

 

rings when any area in the system is

 

in a perimeter armed or disarmed

 

state.

 

 

Set telephone ring counter to answer when any area is in a perimeter armed or disarmed state.

The RPS considers perimeter armed as a disarmed state.

Bosch Security Systems, Inc. 10/08 F01U003636-04

Image 34
Contents D9412GV2/D7412GV2 Type Styles Used in this Manual Prompt Sub-PromptTable of Contents SIA CP-01 Quick Reference TablesProgramming Prompts Directory Literature Referenced Using this Program Entry GuideDifferences between the D9412GV2 and D7412GV2 Features Document Name Part NumberProduct Handlers GV2MAINGuide to Programming Options Programming Error DisplaysProgramming the Control Panel with the D5200 Programmer Guide to UL 864 Programming Requirements Settings Permitted in UL UL 864 Programming Recommendations Prompt Possible Settings RecommendationPhone Default Blank Selection Up to 24 characters do not enterFor SIA CP-01 Compliance Call Waiting Disable PhoneModem Format Default Yes Selection Yes or NoPhone Parameters Modem IIIa2 CommunicationPoint/User Flag Conettix D6600/D6100Dtmf Dialing Alarm On FailPhone Supv Time Fail is Yes and CC Trouble Tone is YesTwo Phone Lines RoutingBuzz on Fail Bfsk Duress CodeEnhanced Routing Programming Primary and Backup DestinationsRoute Number Groups Which Has the Highest Priority? Programming a Duplicate Report# Primary Device # Backup DeviceView Events? Fire Reports Selection Report Description Fire ReportsBurglar Reports Burglar ReportsUser Reports Selection Report Description User ReportsTest Reports Sending Test ReportsDiagnostic Reports Selection Description Test Reports Selection DescriptionAutoFunc Reports Relay ReportsRPS Reports RPS Reports Selections Report Description Point ReportsPoint Reports Selections Description User Chng Reports Access ReportsAccess Reports Selections Report Description User Change Reports Selections DescriptionEnhanced Routing Programming a Primary and Backup DestinationEnhanced Routing .4 Enhanced Routing on RG# Primary SDI RG# Backup SDIRG# Backup SDI, and Enhanced RG# Primary PagerPager Display Fields Programming the Pager Phone NumberEvent Descriptions, Priorities, and Numbers Event Priorit Event Description NumberDefault Selection 1 to 90 Blank and 0 are invalid Power SupervisionAC Fail Time AC Fail Display Default 60 sec Selection 10 to 300 sec in 5-sec IncrementsAC Fail/Res Rpt Printer Parameters ## Scope ## Supervised## A1 through A8 in Scope RPS Parameters RPS Passcode Log % FullAnswer Armed RPS Call BackRPS Line Monitor Answer DisarmedRPS Ph MiscellaneousDuress Type Area Cancel ReportArea Parameters # Area OnProgramming Four-Digit Account Numbers D5200 Programmer Programming Account Numbers in 9000 Series Control PanelsProgramming Four-Digit Account Numbers Programming Ten-Digit Account Numbers# Auto Watch # Delay Res# FA Bypass Max # Exit Tone# Duress Enable must be set to Yes # Duress EnableVerify Time to 60 sec # Area Type Disarming a Shared Area Shared-Area Characteristics Arming a Shared AreaAccess Control Readers Assigned to the Shared Area Shared Area Arming Sequence# Burg Time # Fire Time# Fire Pat # Burg Pat# Bell Test # Single RingRing # Acct O/C # Auto Close # Disable O/C in Window# Area O/C # Fail to Open# Restrictd O/C If Disable O/C in Window is# Fail to Close Exit Dly Time# Perimeter O/C Default Selection 0000 toArming Features # Latest Close Time# Early Ambush Parameter Setup RequirementTo Early Ambush Timer on D1255 Keypad# Exit Warning # Exit Restart# Arm No Exit # Exit Warning must be set to Yes# Entry Warning # Entry Warning must be set to YesCmd Center Keypad Command CenterCC# Supervised CC# Scope Default Blank Selection To 128, A, B, C, and BlankCC# Area Assign CC# A1through A8 in ScopeCC# Entr Cycl Dr Default Blank Selection 1 to 8, BlankCC# Assign Door CC# Exit Tone CC# Trouble ToneCC# Entry Tone CC# Arm Now WarnCC# Passcode Follows Scope CC# Close DoorCC# EnhancCmdCtr ## Passcode ArmCC# Menu Key Lock CC# Cancel DisplayCC# Scroll Lock CC# Abort DisplayArea# Is Off Area# Is OnArea# Not Ready Area# Acct Is OnCF### Key Strokes Custom FunctionCF### Text See .10.2 Area Text onCF### Custom Function Keystrokes Programming Custom Function KeystrokesExample Keypad Selections CommandsUser Interface Keypad Programming ChoicesWatch Mode Master Arm DelayPerim Delay Mstr Arm InstView Memory Perim PartialView Area Stat View Pt StatusChg Time/Date Access Ctl LevelDoor Control Chg PasscodePrint Log Del UserExtend Close User CmdChange Relay Bypass a PtUnbypass a Pt Remote ProgramChange Skeds Service WalkDisplay Rev Invisible Walk Test## Disarm Function 128 throughAuthority Level Custom Functions## Watch Mode ## Master Arm Delay## Perim Delay ## Mstr Arm Inst## Walk Test ## View Memory## View Pt Status ## Fire Test## Cycle Door ## Send Report## Door Control ## Unlock Door## Chg Time/Date ## Access Ctl Lvl## Chg Display ## Chg Passcode## User Cmd ## Del User## Extend Close ## View Log## Remote Program ## Reset Sensors## Change Relay ## Display Rev## Change Skeds ## Service Walk## Default Text ## Invisible Walk Test## Force Arm ## Perimeter O/C## C Function 128 through ## Area O/C## Function Level ## Security Level## Disarm Level Level or L## Disarm Level authority toFunction List #6 Watch ModeDefault Refer to the program record sheet Selection Menu ItemRelay Parameters ## CC Address 1 through# Reset Sensors # Alarm BellArea Relays # Force Armed # Watch Mode# Area Fault # Area ArmedGround Fault Detect # Perim Fault# Silent Alarm # Duress RelayComm Fail Summary AlarmPhone Fail Summary Fire TblSummary Trouble Summary SupBurgPass Code or Token Worksheet User pass code User token or card User ###Reporting and Logging Bsfk User Code Report### User Group ### Passcode### Area 1 through Area 8 Auth ### Mstr Crd Data ### Name### Mstr Site ### SU1 through SU3 SitePoint Index Point Index## Type Description Selection ## Type Description Short NormalOpen Disarmed is YesApplications for Point Responses 9, D, and E Point Responses## Response of 8-9-A-B-C Example of Controlled point ## Pt ResponseHour Points Example of 24-hour point## Entry Delay ## Silent Bell## Audible After 2 Failures ## Ring Til Rst## Invisible Pt ## Watch Point ## Buzz On FaultKeypad for any fault condition while the point Point Response## Local While Disarmed ## RlyResp Type## Disp as Dvc Relay Follows Point The relay## Local While Armed ## Disable Rst## FA Retrnable A# Auto Close prompt ## BP Retrnable## Bypassable 5 Open/Close Options## Report Bypass at Occurrence ## Cross Point## Resettable ## Fire Point### Point Index ## Alarm AbortPoint Number Parameter Abort Window### BFSK/Relay ### Area Assign### Debounce ### BFSK/Relay Codes/RelaysCMD7 BFSK/Relay ### Point TextCMD7 Point Index CMD7 Point TextCMD9 BFSK/Relay CMD9 Point IndexCMD9 Point Text Window Windows# Sunday # Wednesday # Monday# Tuesday # Thursday# Open Window Start Default Selection Hhmm hours and minutesDisable O/C in Window is programmed Yes # Open Window Stop# Close Early Begin Programming to Link Two Days over Midnight# Close Window Start # Close Window Stop# Area 1 through # Xept Holiday# Holiday Holiday Indexes for O/C WindowsOpening and Closing Windows Worksheet Normal Store HoursUser Windows # UW# User GroupUW# Sunday UW# Group EnableUW# Group Disable UW# MondayUW# Holiday 1 through SkedsUW# Xept Holiday Sked Number## Area 1through ## Function Code## Point Number To 128 for D9412GV2 To 64 for D7412GV2 ## Relay NumberSelections Blank To 128 for D9412GV2If Expand Test Rpt in Phone ## Defer Test## Hourly Report ## Defer StatusCmd Center and Custom Func ## Cmd Center## Custom Func ## Cmd Center 1through ## Access Ctl Level ### Access Ctl Level# ## Door 1 throughAccess Authority Events No Entry Events Off ## Sunday ## Time## Date ## Monday## Holiday Holiday Indexes## Xept Holiday DateIndex 3 Days Index 1 DaysIndex 2 Days Index 4 DaysRPS and D5200 Handler Requirements Enable SDI AutoIntroduction SDI AutomationSupervision Parity/StopDTR Control RTS ControlUser Interface Modifications for Command Enable SDI RPSSDI RPS Parameters Call Back Enabled RPS Port Number Set RPS IP Address to 0 if Enable ExtRPS IP Address Refer to RPS IP AddressFor Best Data Smart One Programs→Accessories→CommunicationsFor US Robotics External Modem Connection PC running Remote Programming Software RPS Modem PstnD9412GV2/D7412GV2 Program Entry Guide 6.0 GV2AUX Seize Relay Enable Ext ModemDefault Atdt Selection Not available Modem Init StringPath # IP Add2 Enhanced CommPath # IP Add1 Path # IP Add3Path # Poll Rate is set to 120 sec Path # PortNumPath # Poll Rate Path # Retry Count is set toPath # Ack Wait Default Selection Sec to 65535 secExample of Retry Count Path # Retry Count SDI RPS/Enhanced Communications ConfigurationDefault Selection 300, 1200, 2400, 4800, 9600, 14.4 K Path # Anti-ReplayRG# 1 Attempt Route Group AttemptsFire Summary Sustain Fire Trouble Resound Enable Protocol TypeFire Supv Res Type Secondary Ambush CodePasscode Length Default Selection 0, 3, 4, 5, orDefault Selection 3, or Swinger CountPerimeter Relay Cross Point ParametersCrystalTime Adj Early Armed RelayCross Point Time Default 20 sec Selection Sec to 255 secCross Point Ranges Within Groups # Entry Area # Door ProfileDoor # #CC#Scope# Interlock Point Default Blank Selection Blank, 1 to 127, 129 to# Door Point Effects of Programming on Custom Function Activation# Disarm on Open? # Auto Door?# Fire Unlock? # Card Type# Shunt Time Strike Profile# Strike Time # Buzz Time# RTE Shunt Only? Event Profile# Deact On Open? # REXShunt Only?# Enter Request? # Access Granted?# No Entry? # Exit Request?SIA CP-01 Quick Reference Programming the Control Panels for SIA CP--01 CompliancePrinter Parameters Power SupervisionPhone Phone ParametersAccess Control Functions Arming FeaturesKeypad Command Center Assignment51 Bell ParametersCustom Functions Area RelaysPass Code or Token Worksheet Command 7 and Command 104Point Assignments 102 Point IndexHoliday Indexes 124 115144 Bosch Security Systems, Inc /08 F01U003636-04 Bosch Security Systems, Inc. F01U003636-04
Related manuals
Manual 74 pages 9.34 Kb

D9412GV2 specifications

The Bosch D9412GV2 is an exceptional dishwasher that stands out in the competitive world of home appliances. Known for its reliability and advanced features, this model offers a blend of cutting-edge technology and user-friendly design that appeals to modern households.

One of the most noteworthy features of the D9412GV2 is its impressive cleaning performance. Boasting a unique combination of powerful jets and specialized wash cycles, it ensures that even the toughest stains are removed effectively. The dishwasher features Bosch’s patented PrecisionWash system, which utilizes intelligent sensors to monitor the wash cycle’s progress and adjust the water spray for optimal cleaning results. This not only guarantees sparkling dishes but also conserves water and energy.

In terms of capacity, the D9412GV2 does not disappoint. It has a spacious interior that is designed to accommodate up to 16 place settings, making it an ideal choice for families or those who frequently entertain guests. The adjustable racks and flexible loading options allow users to maximize space and customize the dishwasher to suit their unique needs. The third rack is particularly useful for utensils and smaller items, providing additional space that enhances efficiency.

The dishwasher is also engineered with noise reduction features for a quieter operation. With a sound rating of 44 decibels, it operates silently in the background, allowing for uninterrupted conversations and a peaceful home environment. This is especially beneficial for open-concept living spaces.

Energy efficiency is another hallmark of the Bosch D9412GV2. It is Energy Star certified, reflecting its commitment to sustainable practices. It uses less water and electricity without compromising performance, making it a responsible choice for eco-conscious consumers.

Moreover, the presence of the Home Connect feature allows users to control and monitor their dishwasher remotely via a smartphone app. This innovative technology enables users to start or stop cycles, receive notifications, and even download new wash programs, adding convenience and flexibility to busy lifestyles.

In conclusion, the Bosch D9412GV2 is a state-of-the-art dishwasher that excels in cleaning performance, capacity, and energy efficiency. With its innovative technologies and thoughtful design, it represents Bosch's commitment to quality and customer satisfaction, making it a valuable addition to any kitchen.