Bosch Appliances D9412GV2 manual Printer Parameters

Page 30

D9412GV2/D7412GV2 Program Entry Guide 2.0 GV2MAIN

EN 30

AC Tag Along

Default:

Yes

Selection:

Yes or No

Yes

Send AC messages as tag along

 

events.

 

 

No

Do not send AC messages as tag

 

along events.

 

 

Send AC Reports only if any other event occurs while AC is off-normal.

If AC Tag Along is set to Yes and a subsequent event is generated, the AC Fail Event is sent first, before sending any subsequent events.

AC Tag Along is required for NFPA and UL 864 Commercial Fire systems. Be sure to program AC Fail/Res Rpt as No if AC Tag Along is programmed Yes.

AC/Battery Buzz

Default:

No

Selection:

Yes or No

Yes

Initiates panel-wide trouble tone at

 

all keypads.

 

 

No

Does not initiate panel-wide trouble

 

tone at keypads

 

 

Initiates a panel-wide trouble tone at keypads when AC fails or battery is low or missing. This program item does not prevent the SERVC AC FAIL or SERVC BATT LOW displays.

To comply with NFPA standards and

UL 864 requirements for Commercial Fire systems, program this item as Yes.

If annunciating panel-wide troubles at a keypad with CC# Scope set to Panel Wide is undesirable, set CC# Trouble Tone to No. Refer to Section 2.10 Keypad (Command Center) on page 51 for keypad configurations.

Bat Fail/Res Rpt

Default: Yes

Selection: Yes or No

Yes Battery Failure and Restoral Reports are

sent to the central station. They are routed

to the telephone number programmed for

Power/Phone Events.

 

Modem

Missing or

BATTERY

Report

shorted

MISSING

s

Discharged

BATTERY

 

 

below 12.1

LOW

 

VDC

 

BFSK

Missing,

TROUBLE

Report

shorted low

ZONE 9

s

battery

 

No Battery Failure and Restoral Reports are not sent to the central station.

To comply with NFPA standards and

UL 864 requirements for Commercial Fire systems, program this item as Yes.

2.6Printer Parameters

Up to three D9131A Parallel Printer Interface Modules can be connected to the D9412GV2’s (one printer for the D7412GV2’s) SDI bus. Each printer is identified by an address of 17, 18, or 19. Options are available for Routing Reports and area assignments.

Printer Address

Default: 17

Selection: 17, 18, or 19 (only 17 is available for the D7412GV2)

Enter the printer address you are programming.

P## Area Assign

Default: 1

Selection: 1 to 8

Assign an area to the printer programmed in Printer Address.

Bosch Security Systems, Inc. 10/08 F01U003636-04

Image 30
Contents D9412GV2/D7412GV2 Type Styles Used in this Manual Prompt Sub-PromptTable of Contents Tables SIA CP-01 Quick ReferenceProgramming Prompts Directory Literature Referenced Using this Program Entry GuideDifferences between the D9412GV2 and D7412GV2 Features Document Name Part NumberProduct Handlers GV2MAINProgramming Error Displays Guide to Programming OptionsProgramming the Control Panel with the D5200 Programmer Guide to UL 864 Programming Requirements Settings Permitted in UL UL 864 Programming Recommendations Prompt Possible Settings RecommendationPhone Default Blank Selection Up to 24 characters do not enterFor SIA CP-01 Compliance Call Waiting Disable PhoneModem Format Default Yes Selection Yes or NoPhone Parameters Modem IIIa2 CommunicationPoint/User Flag Conettix D6600/D6100Dtmf Dialing Alarm On FailPhone Supv Time Fail is Yes and CC Trouble Tone is YesTwo Phone Lines RoutingBuzz on Fail Bfsk Duress CodeEnhanced Routing Programming Primary and Backup DestinationsRoute Number Groups Which Has the Highest Priority? Programming a Duplicate Report# Backup Device # Primary DeviceView Events? Fire Reports Selection Report Description Fire ReportsBurglar Reports Burglar ReportsUser Reports Selection Report Description User ReportsTest Reports Sending Test ReportsDiagnostic Reports Selection Description Test Reports Selection DescriptionRelay Reports AutoFunc ReportsRPS Reports Point Reports RPS Reports Selections Report DescriptionPoint Reports Selections Description User Chng Reports Access ReportsAccess Reports Selections Report Description User Change Reports Selections DescriptionProgramming a Primary and Backup Destination Enhanced RoutingEnhanced Routing .4 Enhanced Routing on RG# Primary SDI RG# Backup SDIRG# Backup SDI, and Enhanced RG# Primary PagerPager Display Fields Programming the Pager Phone NumberEvent Descriptions, Priorities, and Numbers Event Priorit Event Description NumberPower Supervision Default Selection 1 to 90 Blank and 0 are invalidAC Fail Time Default 60 sec Selection 10 to 300 sec in 5-sec Increments AC Fail DisplayAC Fail/Res Rpt Printer Parameters ## Supervised ## Scope## A1 through A8 in Scope RPS Parameters RPS Passcode Log % FullAnswer Armed RPS Call BackRPS Line Monitor Answer DisarmedMiscellaneous RPS PhDuress Type Area Cancel ReportArea Parameters # Area OnProgramming Four-Digit Account Numbers D5200 Programmer Programming Account Numbers in 9000 Series Control PanelsProgramming Four-Digit Account Numbers Programming Ten-Digit Account Numbers# Auto Watch # Delay Res# FA Bypass Max # Exit Tone# Duress Enable # Duress Enable must be set to YesVerify Time to 60 sec # Area Type Disarming a Shared Area Shared-Area Characteristics Arming a Shared AreaAccess Control Readers Assigned to the Shared Area Shared Area Arming Sequence# Burg Time # Fire Time# Fire Pat # Burg Pat# Single Ring # Bell TestRing # Acct O/C # Auto Close # Disable O/C in Window# Area O/C # Fail to Open# Restrictd O/C If Disable O/C in Window is# Fail to Close Exit Dly Time# Perimeter O/C Default Selection 0000 toArming Features # Latest Close Time# Early Ambush Parameter Setup RequirementTo Early Ambush Timer on D1255 Keypad# Exit Warning # Exit Restart# Arm No Exit # Exit Warning must be set to Yes# Entry Warning # Entry Warning must be set to YesKeypad Command Center Cmd CenterCC# Supervised CC# Scope Default Blank Selection To 128, A, B, C, and BlankCC# Area Assign CC# A1through A8 in ScopeDefault Blank Selection 1 to 8, Blank CC# Entr Cycl DrCC# Assign Door CC# Exit Tone CC# Trouble ToneCC# Entry Tone CC# Arm Now WarnCC# Passcode Follows Scope CC# Close DoorCC# EnhancCmdCtr ## Passcode ArmCC# Menu Key Lock CC# Cancel DisplayCC# Scroll Lock CC# Abort DisplayArea# Is Off Area# Is OnArea# Not Ready Area# Acct Is OnCF### Key Strokes Custom FunctionCF### Text See .10.2 Area Text onProgramming Custom Function Keystrokes CF### Custom Function KeystrokesExample Keypad Selections CommandsUser Interface Keypad Programming ChoicesWatch Mode Master Arm DelayPerim Delay Mstr Arm InstView Memory Perim PartialView Area Stat View Pt StatusChg Time/Date Access Ctl LevelDoor Control Chg PasscodePrint Log Del UserExtend Close User CmdChange Relay Bypass a PtUnbypass a Pt Remote ProgramChange Skeds Service WalkDisplay Rev Invisible Walk Test## Disarm Function 128 throughAuthority Level Custom Functions## Watch Mode ## Master Arm Delay## Perim Delay ## Mstr Arm Inst## Walk Test ## View Memory## View Pt Status ## Fire Test## Cycle Door ## Send Report## Door Control ## Unlock Door## Chg Time/Date ## Access Ctl Lvl## Chg Display ## Chg Passcode## User Cmd ## Del User## Extend Close ## View Log## Remote Program ## Reset Sensors## Change Relay ## Display Rev## Change Skeds ## Service Walk## Default Text ## Invisible Walk Test## Force Arm ## Perimeter O/C## C Function 128 through ## Area O/C## Function Level ## Security Level## Disarm Level Level or L## Disarm Level authority toFunction List #6 Watch ModeDefault Refer to the program record sheet Selection Menu ItemRelay Parameters ## CC Address 1 through# Alarm Bell # Reset SensorsArea Relays # Force Armed # Watch Mode# Area Fault # Area ArmedGround Fault Detect # Perim Fault# Silent Alarm # Duress RelayComm Fail Summary AlarmPhone Fail Summary Fire TblSummary Trouble Summary SupBurgPass Code or Token Worksheet User pass code User token or card User ###Reporting and Logging Bsfk User Code Report### Passcode ### User Group### Area 1 through Area 8 Auth ### Mstr Crd Data ### Name### Mstr Site ### SU1 through SU3 SitePoint Index Point Index## Type Description Selection ## Type Description Short NormalOpen Disarmed is YesPoint Responses Applications for Point Responses 9, D, and E## Response of 8-9-A-B-C Example of Controlled point ## Pt ResponseHour Points Example of 24-hour point## Entry Delay ## Silent Bell## Ring Til Rst ## Audible After 2 Failures## Invisible Pt ## Watch Point ## Buzz On FaultKeypad for any fault condition while the point Point Response## Local While Disarmed ## RlyResp Type## Disp as Dvc Relay Follows Point The relay## Disable Rst ## Local While Armed## FA Retrnable A# Auto Close prompt ## BP Retrnable## Bypassable 5 Open/Close Options## Report Bypass at Occurrence ## Cross Point## Resettable ## Fire Point### Point Index ## Alarm AbortPoint Number Parameter Abort Window### BFSK/Relay ### Area Assign### Debounce ### BFSK/Relay Codes/RelaysCMD7 BFSK/Relay ### Point TextCMD7 Point Index CMD7 Point TextCMD9 Point Index CMD9 BFSK/RelayCMD9 Point Text Windows Window# Sunday # Wednesday # Monday# Tuesday # Thursday# Open Window Start Default Selection Hhmm hours and minutesDisable O/C in Window is programmed Yes # Open Window Stop# Close Early Begin Programming to Link Two Days over Midnight# Close Window Start # Close Window Stop# Area 1 through # Xept Holiday# Holiday Holiday Indexes for O/C WindowsOpening and Closing Windows Worksheet Normal Store HoursUser Windows # UW# User GroupUW# Sunday UW# Group EnableUW# Group Disable UW# MondayUW# Holiday 1 through SkedsUW# Xept Holiday Sked Number## Function Code ## Area 1through## Point Number To 128 for D9412GV2 To 64 for D7412GV2 ## Relay NumberSelections Blank To 128 for D9412GV2If Expand Test Rpt in Phone ## Defer Test## Hourly Report ## Defer Status## Cmd Center Cmd Center and Custom Func## Custom Func ## Cmd Center 1through ## Access Ctl Level ### Access Ctl Level# ## Door 1 throughAccess Authority Events No Entry Events Off ## Sunday ## Time## Date ## Monday## Holiday Holiday Indexes## Xept Holiday DateIndex 3 Days Index 1 DaysIndex 2 Days Index 4 DaysRPS and D5200 Handler Requirements Enable SDI AutoIntroduction SDI AutomationSupervision Parity/StopDTR Control RTS ControlEnable SDI RPS User Interface Modifications for CommandSDI RPS Parameters Call Back Enabled RPS Port Number Set RPS IP Address to 0 if Enable ExtRPS IP Address Refer to RPS IP AddressPrograms→Accessories→Communications For Best Data Smart OneFor US Robotics External Modem Connection PC running Remote Programming Software RPS Modem PstnD9412GV2/D7412GV2 Program Entry Guide 6.0 GV2AUX Seize Relay Enable Ext ModemDefault Atdt Selection Not available Modem Init StringPath # IP Add2 Enhanced CommPath # IP Add1 Path # IP Add3Path # Poll Rate is set to 120 sec Path # PortNumPath # Poll Rate Path # Retry Count is set toDefault Selection Sec to 65535 sec Path # Ack WaitExample of Retry Count Path # Retry Count SDI RPS/Enhanced Communications ConfigurationDefault Selection 300, 1200, 2400, 4800, 9600, 14.4 K Path # Anti-ReplayRoute Group Attempts RG# 1 AttemptFire Summary Sustain Fire Trouble Resound Enable Protocol TypeFire Supv Res Type Secondary Ambush CodePasscode Length Default Selection 0, 3, 4, 5, orDefault Selection 3, or Swinger CountPerimeter Relay Cross Point ParametersCrystalTime Adj Early Armed RelayDefault 20 sec Selection Sec to 255 sec Cross Point TimeCross Point Ranges Within Groups # Entry Area # Door ProfileDoor # #CC#Scope# Interlock Point Default Blank Selection Blank, 1 to 127, 129 to# Door Point Effects of Programming on Custom Function Activation# Disarm on Open? # Auto Door?# Fire Unlock? # Card Type# Shunt Time Strike Profile# Strike Time # Buzz Time# RTE Shunt Only? Event Profile# Deact On Open? # REXShunt Only?# Enter Request? # Access Granted?# No Entry? # Exit Request?SIA CP-01 Quick Reference Programming the Control Panels for SIA CP--01 CompliancePrinter Parameters Power SupervisionPhone Phone ParametersAccess Control Functions Arming FeaturesKeypad Command Center Assignment51 Bell ParametersCustom Functions Area RelaysPass Code or Token Worksheet Command 7 and Command 104Point Assignments 102 Point IndexHoliday Indexes 124 115144 Bosch Security Systems, Inc /08 F01U003636-04 Bosch Security Systems, Inc. F01U003636-04
Related manuals
Manual 74 pages 9.34 Kb

D9412GV2 specifications

The Bosch D9412GV2 is an exceptional dishwasher that stands out in the competitive world of home appliances. Known for its reliability and advanced features, this model offers a blend of cutting-edge technology and user-friendly design that appeals to modern households.

One of the most noteworthy features of the D9412GV2 is its impressive cleaning performance. Boasting a unique combination of powerful jets and specialized wash cycles, it ensures that even the toughest stains are removed effectively. The dishwasher features Bosch’s patented PrecisionWash system, which utilizes intelligent sensors to monitor the wash cycle’s progress and adjust the water spray for optimal cleaning results. This not only guarantees sparkling dishes but also conserves water and energy.

In terms of capacity, the D9412GV2 does not disappoint. It has a spacious interior that is designed to accommodate up to 16 place settings, making it an ideal choice for families or those who frequently entertain guests. The adjustable racks and flexible loading options allow users to maximize space and customize the dishwasher to suit their unique needs. The third rack is particularly useful for utensils and smaller items, providing additional space that enhances efficiency.

The dishwasher is also engineered with noise reduction features for a quieter operation. With a sound rating of 44 decibels, it operates silently in the background, allowing for uninterrupted conversations and a peaceful home environment. This is especially beneficial for open-concept living spaces.

Energy efficiency is another hallmark of the Bosch D9412GV2. It is Energy Star certified, reflecting its commitment to sustainable practices. It uses less water and electricity without compromising performance, making it a responsible choice for eco-conscious consumers.

Moreover, the presence of the Home Connect feature allows users to control and monitor their dishwasher remotely via a smartphone app. This innovative technology enables users to start or stop cycles, receive notifications, and even download new wash programs, adding convenience and flexibility to busy lifestyles.

In conclusion, the Bosch D9412GV2 is a state-of-the-art dishwasher that excels in cleaning performance, capacity, and energy efficiency. With its innovative technologies and thoughtful design, it represents Bosch's commitment to quality and customer satisfaction, making it a valuable addition to any kitchen.