Sierra Monitor Corporation 3100-01 manual Field of View Responsivity Input voltage, LEDs Relays

Page 14

Instruction Manual

6.0SPECIFICATIONS Sensitivity:

Field of View:

Responsivity: Input voltage:

Current Draw: Temperature Range:

Operating:

Storage:

LEDs:

Relays:

Model 3100-01:

3100-02, -03, -04, -05 Enhanced Relay Models:

4-20 mA Outputs

3100-06:

Connections:

Enclosure:

Hazardous area classification:

Dimensions:

Weight:

1 ft. sq. Pan fire on axis @ 80 feet within 5 seconds (using standard fuel) Switch selectable form 20 to 80 feet to a 1 sq. ft. kerosene fire

120 degree cone

UV - 185 to 260 nm, IR - 0.715 to 3.5 microns, Visible - 480 to 560 nm 15 to 32 volts, typically 24 volts

@24 Volts DC: 72 mA normal mode, 82 mA alarm mode

-40oF to 185oF (-40oC to 85oC) -67oF to 230oF(-55oC to 110oC)

Display switch settings, fault type, fire and verified fire information

Fire and Fault Relays

120 VAC, 1.0 amp @ 24 VDC resistive, normally open and normally closed contacts, latching or fire-following modes

Fire, Fault, Verify and Aux Relays

0.5amp @ 120 VAC, 1.0 amp @ 24 VDC resistive, normally open and normally closed contacts are available.

0 mA - Fault, 4 - mA - Normal Mode, 12 mA - Alarm, 20 mA - Verified Fire Screw terminals, 14 - 22 AGW wire size

Copper-free Cast Aluminum with epoxy finish, Conduits: Two 3/4 inch NPT feed- through hubs

NEMA 4X, Explosion Proof

Class I, Div. 1 and 2, Groups B, C, D, Class II and III, Div. 1 and 2, Groups E, F, G

5.4x 4.8 x 3.7 inches (13.7 x 12.2 x 9.4 cm) 3 lbs (1.3 Kg)

7.0 LIMITED WARRANTY

SIERRA MONITOR CORPORATION warrants its products to be free from defects in workmanship or material under normal use and service for two years after date of shipment. SMC will repair or replace with- out charge any equipment found to be defective during the warranty period. Final determination of the nature and responsibility for defective or damaged equipment will be made by SMC personnel.

All warranties hereunder are contingent upon proper use in the application for which the product was intended and do not cover products which have been modified or repaired without SMC approval or which have been sub- jected to accident, improper maintenance, installation or application, or on which original identification marks have been removed or altered. This Limited Warranty also will not apply to interconnecting cables or wires, consumables (ie. calibration gases, batteries, sensors),

nor to any damage resulting from battery leakage.

In all cases SMC’s responsibility and liability under this warranty shall be limited to the cost of the equipment. The purchaser must obtain shipping instructions for the prepaid return of any item under this warranty provi- sion and compliance with such instruction shall be a condition of this warranty.

Except for the express warranty stated above, SMC dis- claims all warranties with regard to the products sold hereunder including all implied warranties of merchant- ability and fitness and the express warranties stated herein are in lieu of all obligations or liabilities on the part of SMC for damages including, but not limited to, conse- quential damages arising out of/or in connection with the use or performance of the product.

Model 3100 Series Flame Detector (11/04)

Page: 11

Image 14
Contents Model Model Table of Contents Fault Diagnostics IntroductionModel 3100 Series Field of View GeneralSW7 SW1 Shown in off position SW6 SW2 Shown in on position Configuration See FigureSW1 SW2 SW3 SW4 SW5 SW9 SW8 Field-of-View See FigureLED Fire FaultNormal Relay operation See FigureVerify Relay Fault RelayAuxiliary Fault 5 4-20 mA OperationInstalling the Conduit and Wiring General PrecautionsHousing and Conduit Mounting the Housing PowerAuxiliary Relay 6 4-20 mA ConnectionsTroubleshooting Model 3100 Series Flame Detector 11/04 Field of View Responsivity Input voltage Dimensions WeightLimited Warranty LEDs RelaysFigure A-1 Model 3100 Series Exploded View Figure A-3 Model 3100 Series Common Wiring Connections Figure A-4 Model 3100 Series Enhanced Wiring Connections Fire OutputLatching Control Appendix B TablesVerify Control 3100-02, -03, -04 and -05 Models only Detector Non-Latching ControlFault Connector Connectors Fire Relay ConnectorVerify and Aux. Fault Connector Power/Communications ConnectorFalse Alarm Stimuli Table Fire and False Alarm Stimuli TableDetector Response to Fuels Table Appendix C -- Wiring Connections Index Model 3100 Series Flame Detector 11/04