Instruction Manual
B.2 Connectors |
|
|
| |
B.2.1 Fire Relay Connector |
|
|
| |
|
|
|
|
|
| (J2) Fire Relay | Description |
|
|
| Pin 1 (Left Most) & Pin 2 | Normally Open Side of Relay |
|
|
| Pin 3 & Pin 4 (Middle) | Common or Center Side of Relay |
|
|
| Pin 5 & Pin 6 (Right Most) | Normally Closed Side of Relay |
|
|
B.2.2 Verify and Aux. Fault Connector |
|
|
| |
|
|
|
| |
| (J3) Verify/Aux. | Description | ||
| Pin 1 (Left Most) & Pin 2 | Verify Relay Common Side of Relay |
| |
| Pin 3 & Pin 4 | Verify Relay NO or NC Side of Relay | ||
| Pin 5 | Aux. Fault Relay Common Side of Relay | ||
| Pin 6 (Right Most) | Aux. Fault Relay NO or NC Side of Relay | ||
|
|
|
|
|
B.2.3 Fault Connector |
|
|
| |
| (J4) Fault Relay | Description (Normally Energized State) | ||
| Pin 1 (Left Most) | Normally Closed Side of Relay |
|
|
| Pin 2 (Middle) | Common Side of Relay |
| |
| Pin 3 (Right Most) | Normally Open Side of Relay |
|
B.2.4 Power/Communications Connector | ||
|
|
|
| (J5) Power/Comm. | Description |
| Pin 1 (Left Most) & Pin 5 | Power (DC |
| Pin 2 & Pin 6 | Communication RS 485 |
| Pin 3 & Pin 7 | Communication RS 485 (+) |
| Pin 4 & Pin 8 (Right Most) | Power (DC +) |
B.2.5 3100-06 Connectors
(J2) Connector | Description |
Pin 1 (Left Most) | Power (DC |
Pin 2 | Communication RS 485 |
Pin 3 | Communication RS 485 (+) |
Pin 4 | Power (DC +) |
Pin 5 | |
Pin 6 | |
Pin 7 to Pin 8 Jumper (Right Most) | Enables |
|
|
Page: 16 | Model 3100 Series Flame Detector (11/04) |