Sierra Monitor Corporation 3100-01 manual SW1 SW2 SW3 SW4 SW5 SW9 SW8, Field-of-View See Figure

Page 6

Instruction Manual

SW1

SW2

SW3

SW4

SW5

SW9

SW8

SW7 SW1 Shown in off position SW6 SW2 Shown in on position

Figure 2-2: Configuration Switches

2.2Field-of-View (See Figure 2-1)

Optical Flame Detectors must be able to “see” the fire to declare an alarm. Any obstruction between the detector and the threat area will impair the de- tectors ability to cover the threat area. An obstruc- tion is anything that is not transparent to the sensor elements of the detector. UV sensors and some types of IR sensors cannot see through glass or plas- tics. The 3100 series of Flame Detectors has a 120° Field of View.

When covering a large area the detectors should be located to provide overlapping fields of view to in- sure complete coverage.

2.3Range

The size of fire and type of materials which consti- tute the threat will affect the detector’s range. Dif- ferent materials produce different amounts of the radiant energy used by the detector to “see” the fire. Also, the range of the detector is a function of the fire size. Using the square of the distance rule, if the device will detect a one sq. ft. fire at 60 feet, to detect a 1/4 size fire (aprox. 6 sq. in.) the devices must be within 30 feet. The Model 3100 Detector is optimized to a 1 sq. ft. Kerosene fire at 80 feet with the sensitivity settings set to maximum sensi- tivity.

2.4Environment

All optical flame detectors sense radiant energy at some frequency or frequencies within their Field- of-View. Any source which radiates energy at the same frequency or frequencies used by the detector

to sense a fire may impact the detector’s ability to “see” the fire. Care should be taken to minimize radiant energy sources within the detectors Field- of-View. Because of the variety of environments and conditions, a factory trained technician or quali- fied P.E. should be consulted before deciding on the location of devices. The Model 3100 Detector uses an Ultraviolet sensor (180 - 260 nanometers), an Infrared sensor (.715 - 3.5 microns), and a Vis- ible sensor (480 - 560 nanometers).

2.5Configuration (See Figure 2-2)

All of the 3100 Series models have field adjustable configuration switches located on the front face of the detector. The factory settings are shown in italic text. The enhanced models have additional con- figuration options for the Verified Fire.

2.5.1Sensitivity

All versions have several sensitivity settings available. The sensitivity settings are 20, 40, 60, and 80 feet. Each setting is optimized to alarm on a 1 sq. ft. Kerosene fire within 5 seconds. Switches 1 and 2 control the sensi- tivity. The factory default is 80 feet. (SW1 and SW2 are off.)

Note: Different fuels emit energy at different rates. For example; a fire involving fuel oil does not emit energy at the same rate as gaso- line. Consequently, the Model 3100 will be able to respond to a gasoline fire at a little greater distance than it will to a fuel oil fire. Similary, a fire involving acetone will be seen at a greater distance than one involving gaso- line.

Model 3100 Series Flame Detector (11/04)

Page: 3

Image 6
Contents Model Model Table of Contents Fault Diagnostics IntroductionModel 3100 Series Field of View GeneralSW7 SW1 Shown in off position SW6 SW2 Shown in on position Configuration See FigureSW1 SW2 SW3 SW4 SW5 SW9 SW8 Field-of-View See FigureLED Fire FaultNormal Relay operation See FigureVerify Relay Fault RelayAuxiliary Fault 5 4-20 mA OperationInstalling the Conduit and Wiring General PrecautionsHousing and Conduit Mounting the Housing PowerAuxiliary Relay 6 4-20 mA ConnectionsTroubleshooting Model 3100 Series Flame Detector 11/04 Field of View Responsivity Input voltage Dimensions WeightLimited Warranty LEDs RelaysFigure A-1 Model 3100 Series Exploded View Figure A-3 Model 3100 Series Common Wiring Connections Figure A-4 Model 3100 Series Enhanced Wiring Connections Fire OutputLatching Control Appendix B TablesVerify Control 3100-02, -03, -04 and -05 Models only Detector Non-Latching ControlFault Connector Connectors Fire Relay ConnectorVerify and Aux. Fault Connector Power/Communications ConnectorFalse Alarm Stimuli Table Fire and False Alarm Stimuli TableDetector Response to Fuels Table Appendix C -- Wiring Connections Index Model 3100 Series Flame Detector 11/04