Sierra Monitor Corporation 3100-01 manual Led

Page 7

Instruction Manual

LED 1

LED 2

Mounting Screw

(2 locations)

Configuration Switches

Figure 2-3: Model 3100 Series Detector Module (Front)

2.5.2Verify Control

The Enhanced Model 3100-02, -03, -04, - 05 and -06 have the Verified Fire function. The Verify Control switches allow the user to select the verify level, disable the verify function, or make the Verify Relay operate in parallel with the Fire Relay. The verify function in enabled when the detector de- clares an alarm. The verify level sets the degree of certainty required to declare a veri- fied fire. The lowest level (1) is the lowest certainty (fastest) and the highest level (6) is the greatest certainty (slowest) of a fire. The verify function enables an algorithm which evaluates the fire signature over time to de- termine the degree of certainty. When the degree of certainty exceeds the level set by the configuration switches a Verified Fire is declared and the Verify Relay is energized. Switches 3, 4, and 5 control the verify func- tion. The factory default is verify disabled and set to level 0. (SW3, SW4 and SW5 are off.)

2.5.3Latching Control

The latching controls allow the detector or individual relay outputs to be set to “Latch- ing” or “Fire Following”. “Latching” causes the relay to stay energized until power is re- moved from the detector. “Non-latching” al- lows the relay to reset (de-energize) when a flame is not present for a short period of time.

For the detector to be set to "Non-latching" both Fire Output and Verify Output must be set to "Non-latching". If either the fire out-

put or the verify output is set to "Latching" then the detector will be set to "Latching".

When the detector is set to "Latching" the LED's will indicate an alarm until the device is reset regardless of the fire or verify relay output settings.

The Verify Relay is automatically configured as “Latching” if the Fire Relay is set to “Latch- ing”. SW6 sets the Fire Relay Output, SW7 sets the Verify Relay Output and SW8 sets the Detector Mode. To set the detector to "Non-latching", SW6, SW7 and SW8 must be set to "Non-latching. The factory defaults are “Latching” (SW6 and SW7 are off.)

2.5.4Other Configuration Switches

The last configuration switch (SW9) must be in the off position. The factory default set- ting is off.

2.6LED operation (See Figure 2-3)

The status of all versions of the flame detectors can be determined from the LEDs located behind the lens on the front of the detector. The LEDs will flash at intervals or remain on to indicate the detec- tors status. (Fault Mode, Normal Mode, Alarm Mode, Verified Fire Mode, and on power up the Configuration Settings).

2.6.1Power Up

At power up all versions of the flame detec- tor will begin flashing the LEDs. The LEDs will flash 8 consecutive patterns which indi- cates the positions of the configuration switches. Each pattern indicates the position

Page: 4

Model 3100 Series Flame Detector (11/04)

Image 7
Contents Model Model Table of Contents Introduction Fault DiagnosticsGeneral Model 3100 Series Field of ViewField-of-View See Figure Configuration See FigureSW1 SW2 SW3 SW4 SW5 SW9 SW8 SW7 SW1 Shown in off position SW6 SW2 Shown in on positionLED Relay operation See Figure FaultNormal Fire5 4-20 mA Operation Fault RelayAuxiliary Fault Verify RelayPower General PrecautionsHousing and Conduit Mounting the Housing Installing the Conduit and Wiring6 4-20 mA Connections Auxiliary RelayTroubleshooting Model 3100 Series Flame Detector 11/04 LEDs Relays Dimensions WeightLimited Warranty Field of View Responsivity Input voltageFigure A-1 Model 3100 Series Exploded View Figure A-3 Model 3100 Series Common Wiring Connections Figure A-4 Model 3100 Series Enhanced Wiring Connections Detector Non-Latching Control Appendix B TablesVerify Control 3100-02, -03, -04 and -05 Models only Fire OutputLatching ControlPower/Communications Connector Connectors Fire Relay ConnectorVerify and Aux. Fault Connector Fault ConnectorFire and False Alarm Stimuli Table False Alarm Stimuli TableDetector Response to Fuels Table Appendix C -- Wiring Connections Index Model 3100 Series Flame Detector 11/04