B.3 Verify/Aux. Relay Configurations
Model # | Verify Relay | Aux. Relay |
Open Contacts | Closed Contacts | |
Closed Contacts | Open Contacts | |
Open Contacts | Open Contacts | |
Closed Contact | Closed Contacts |
B.4 Fault Table
Fault # | Fault Label | Description |
1 | Lens Test Fault | UV sensors didn’t detect enough UV from the internal UV source. |
2 | Configuration Fault | SW9 is “ON” or a failed program |
3 | Calibration Fault | Device is out of calibration |
4 | Volt. Low | Input Voltage is below 15 VDC |
5 | Photo. Sensor Fault | IR or Visible sensor failed to detect internal test source. |
6 | Relay Fault | Relay coil circuit is open. |
7 | Volt. High | Input Voltage was above 32 VDC |
8 | Temp. Out of Range | Internal device temperature went below |
|
|
|
B.5 False Alarm Stimuli Table
FALSE ALARM RESPONSE
This table shows the detectors ability to tolerate both modulated and unmodulated false alarm stimuli.
False Alarms Source | Distance | Unmodulated | Modulated |
|
Resistive Electric Heater 1320 Watt | 6 Feet | No Response | No Response |
|
Fluorescent Lights (2) 40 Watt Bulbs | 6 Feet | No Response | No Response |
|
Halogen Light 500 Watt | 10 Feet | No Response | No Response |
|
Incandescent Light 100 Watt | 6 Feet | No Response | No Response |
|
Arc Welder 50 Watt | 25 Feet | No Response | No Response |
|
Direct Sunlight | 93 million miles | No Response | No Response |
|
|
|
|
|
|
B.6 Fire and False Alarm Stimuli Table
Model 3100 detector response to a fire while exposed to a variety of radiant energy sources.
False Alarms | Distance to False | Distance | Response Time to |
|
Source | Alarm Source | to Fire | Fire |
|
Resistive Electric Heater 1320 Watt | 6 Feet | 6 Feet | Less than 5 sec. |
|
Florescent Lights (2) 40 Watt Bulbs | 6 Feet | 6 Feet | Less than 5 sec. |
|
Halogen Light 500 Watt | 10 Feet | 6 Feet | Less than 5 sec. |
|
Incandescent Light 100 Watt | 6 Feet | 6 Feet | Less than 5 sec. |
|
Arc Welder 50 Watt | 25 Feet | 6 Feet | Less than 5 sec. |
|
Direct Sunlight | 93 million miles | 6 Feet | Less than 5 sec. |
|
|
|
|
|
|
Model 3100 Series Flame Detector (11/04) | Page: 17 |