Sierra Monitor Corporation 3100-01 manual Fire and False Alarm Stimuli Table

Page 20

Instruction Manual

B.3 Verify/Aux. Relay Configurations

Model #

Verify Relay

Aux. Relay

3100-02

Open Contacts

Closed Contacts

3100-03

Closed Contacts

Open Contacts

3100-04

Open Contacts

Open Contacts

3100-05

Closed Contact

Closed Contacts

B.4 Fault Table

Fault #

Fault Label

Description

1

Lens Test Fault

UV sensors didn’t detect enough UV from the internal UV source.

2

Configuration Fault

SW9 is “ON” or a failed program

3

Calibration Fault

Device is out of calibration

4

Volt. Low

Input Voltage is below 15 VDC

5

Photo. Sensor Fault

IR or Visible sensor failed to detect internal test source.

6

Relay Fault

Relay coil circuit is open.

7

Volt. High

Input Voltage was above 32 VDC

8

Temp. Out of Range

Internal device temperature went below -40° C or above 85° C.

 

 

 

B.5 False Alarm Stimuli Table

FALSE ALARM RESPONSE

This table shows the detectors ability to tolerate both modulated and unmodulated false alarm stimuli.

False Alarms Source

Distance

Unmodulated

Modulated

 

Resistive Electric Heater 1320 Watt

6 Feet

No Response

No Response

 

Fluorescent Lights (2) 40 Watt Bulbs

6 Feet

No Response

No Response

 

Halogen Light 500 Watt

10 Feet

No Response

No Response

 

Incandescent Light 100 Watt

6 Feet

No Response

No Response

 

Arc Welder 50 Watt

25 Feet

No Response

No Response

 

Direct Sunlight

93 million miles

No Response

No Response

 

 

 

 

 

 

B.6 Fire and False Alarm Stimuli Table

Model 3100 detector response to a fire while exposed to a variety of radiant energy sources.

False Alarms

Distance to False

Distance

Response Time to

 

Source

Alarm Source

to Fire

Fire

 

Resistive Electric Heater 1320 Watt

6 Feet

6 Feet

Less than 5 sec.

 

Florescent Lights (2) 40 Watt Bulbs

6 Feet

6 Feet

Less than 5 sec.

 

Halogen Light 500 Watt

10 Feet

6 Feet

Less than 5 sec.

 

Incandescent Light 100 Watt

6 Feet

6 Feet

Less than 5 sec.

 

Arc Welder 50 Watt

25 Feet

6 Feet

Less than 5 sec.

 

Direct Sunlight

93 million miles

6 Feet

Less than 5 sec.

 

 

 

 

 

 

Model 3100 Series Flame Detector (11/04)

Page: 17

Image 20
Contents Model Model Table of Contents Fault Diagnostics IntroductionModel 3100 Series Field of View GeneralConfiguration See Figure SW1 SW2 SW3 SW4 SW5 SW9 SW8SW7 SW1 Shown in off position SW6 SW2 Shown in on position Field-of-View See FigureLED Fault NormalFire Relay operation See FigureFault Relay Auxiliary FaultVerify Relay 5 4-20 mA OperationGeneral Precautions Housing and Conduit Mounting the HousingInstalling the Conduit and Wiring PowerAuxiliary Relay 6 4-20 mA ConnectionsTroubleshooting Model 3100 Series Flame Detector 11/04 Dimensions Weight Limited WarrantyField of View Responsivity Input voltage LEDs RelaysFigure A-1 Model 3100 Series Exploded View Figure A-3 Model 3100 Series Common Wiring Connections Figure A-4 Model 3100 Series Enhanced Wiring Connections Appendix B Tables Verify Control 3100-02, -03, -04 and -05 Models onlyFire OutputLatching Control Detector Non-Latching ControlConnectors Fire Relay Connector Verify and Aux. Fault ConnectorFault Connector Power/Communications ConnectorFalse Alarm Stimuli Table Fire and False Alarm Stimuli TableDetector Response to Fuels Table Appendix C -- Wiring Connections Index Model 3100 Series Flame Detector 11/04