Instruction Manual
APPENDIX B
TABLES
B.1 Dip Switch Settings
B.1.1 Sensitivity
Sensitivity | SW1 | SW2 | Level |
20 Foot | ON | ON | 4 |
40 Foot | OFF | ON | 3 |
60 Foot | ON | OFF | 2 |
80 Foot | OFF | OFF | 1 |
B.1.2 Verify Control (3100-02, -03, -04 and -05 Models only)
| Verify | Description | SW3 | SW4 | SW5 | |
| Level 0 | Verify = Fire | OFF | OFF | OFF | |
| Level 1 | Min. Verify (shorter) | ON | OFF | OFF |
|
| Level 2 | Min. Verify (shorter) | OFF | ON | OFF |
|
| Level 3 | Min. Verify (shorter) | ON | ON | OFF | |
| Level 4 | Min. Verify (shorter) | OFF | OFF | ON | |
| Level 5 | Min. Verify (shorter) | ON | OFF | ON | |
| Level 6 | Max. Verify (longer) | OFF | ON | ON | |
| Level 7 | Verify Disabled | ON | ON | ON | |
B.1.3 Fire Output“Latching” Control |
|
|
|
| ||
| Fire Output | Description |
|
| SW6 | |
| Latching | Alarm until Power down Reset |
| OFF | ||
| Following | Alarm until no fire (.5 to 10 sec.) |
| ON |
B.1.4 Verify Relay “Latching” Control
Verify Relay | Description | SW7 |
Latching | Alarm until Power down Reset | OFF |
Following | Alarm until no fire (.5 to 10 sec.) | ON |
|
|
|
B.1.5 Detector "Non-Latching" Control
SW6, SW7 and SW8 must be on for the detector to be
B.1.6 Factory Use Only
SW8 and SW9 must be in the OFF position for normal operation. They are used for factory calibration and testing.
Model 3100 Series Flame Detector (11/04) | Page: 15 |