VENTING - GENERAL GUIDELINES
The following guidelines apply to all categories to follow.
Table 4
Vent Systems
Termination Clearance Requirements
Structure | Minimum Clearances for |
| Termination Locations |
|
|
| 4 feet below |
Door, window or any gravity vent inlet |
|
4 feet horizontally | |
|
|
| 1 foot above |
|
|
Forced air inlet within 10 ft. | 3 feet above |
|
|
Adjoining building or parapet | 6 feet |
|
|
Adjacent public walkways | 7 feet above grade |
|
|
Electric, gas meters & regulators | 4 feet horizontal |
|
|
Do not damper or add heat recovery devices to the flue piping. Failure to open such a damper prior to operating the gas unit heater will result in the spillage of fl ue gas into the occupied space.
Avoid installing units in areas under negative pressure. When required, a flue vent fan should be installed in accordance with the instructions included with the fan.
Vent connectors serving Category I and Category
IIheaters shall not be connected into any portion of mechanical draft systems operating under positive vent pressure.
Maintain
ADDITIONAL REQUIREMENT
FOR CANADIAN INSTALLATIONS
REFER TO SPECIFICATION TABLE AND INSTALLA- TION MANUAL FOR PROPER USAGE.
*The following instructions apply to Canadian installations in addition to installation and operating instructions.
1.Installation must conform with local building codes, or in the absence of local codes, with current CGA B149.1, Installation Codes for Natural Gas Burning Appliances and Equipment, or CGA B149.2, Installation Codes for Propane Gas Burning Appliances and Equipment.
2.Any reference to U. S. standards or codes in these instructions are to be ignored, and the applicable Canadian standards or codes applied
ANSI now organizes vented appliances into four categories.
Venting Categories
| Non |
|
| Condensing | Condensing |
Negative |
|
|
Vent | I | II |
Pressure |
|
|
Positive |
|
|
Vent | III | IV |
Pressure |
|
|
Category I
Includes
Category II
Groups condensing appliances with negative vent pressure.
Category III
Appliances are
Category IV
Covers condensing appliances with positive vent pressure.
NOTICE: Category II and IV do not apply to equip- ment specified within this manual.
17