Sterling GG-45, GG-90, GG-75, GG-60, GG-120, GG-30 Venting General Guidelines, Venting Categories

Page 17

VENTING - GENERAL GUIDELINES

The following guidelines apply to all categories to follow.

Table 4

Vent Systems

Termination Clearance Requirements

Structure

Minimum Clearances for

 

Termination Locations

 

 

 

4 feet below

Door, window or any gravity vent inlet

 

4 feet horizontally

 

 

 

1 foot above

 

 

Forced air inlet within 10 ft.

3 feet above

 

 

Adjoining building or parapet

6 feet

 

 

Adjacent public walkways

7 feet above grade

 

 

Electric, gas meters & regulators

4 feet horizontal

 

 

Do not damper or add heat recovery devices to the flue piping. Failure to open such a damper prior to operating the gas unit heater will result in the spillage of fl ue gas into the occupied space.

Avoid installing units in areas under negative pressure. When required, a flue vent fan should be installed in accordance with the instructions included with the fan.

Vent connectors serving Category I and Category

IIheaters shall not be connected into any portion of mechanical draft systems operating under positive vent pressure.

Maintain 1-inch (25.4mm) clearance between the vent pipe and combustible materials.

ADDITIONAL REQUIREMENT

FOR CANADIAN INSTALLATIONS

REFER TO SPECIFICATION TABLE AND INSTALLA- TION MANUAL FOR PROPER USAGE.

*The following instructions apply to Canadian installations in addition to installation and operating instructions.

1.Installation must conform with local building codes, or in the absence of local codes, with current CGA B149.1, Installation Codes for Natural Gas Burning Appliances and Equipment, or CGA B149.2, Installation Codes for Propane Gas Burning Appliances and Equipment.

2.Any reference to U. S. standards or codes in these instructions are to be ignored, and the applicable Canadian standards or codes applied

ANSI now organizes vented appliances into four categories.

Venting Categories

 

Non

 

 

Condensing

Condensing

Negative

 

 

Vent

I

II

Pressure

 

 

Positive

 

 

Vent

III

IV

Pressure

 

 

Category I

Includes non-condensing appliances with negative vent pressure, like the traditional atmospheric unit heater.

Category II

Groups condensing appliances with negative vent pressure.

Category III

Appliances are non-condensing and operate with a positive vent pressure.

Category IV

Covers condensing appliances with positive vent pressure.

NOTICE: Category II and IV do not apply to equip- ment specified within this manual.

17

Image 17
Contents Receiving Instructions Tubular GAS Fired Direct Spark Propeller Unit HeatersDescription Table of ContentsGeneral Safety Information Performance DATA† Page Installation Installation Gas Pipe Size GAS PipingPipe Sizing Gas Piping Requirements Pipe InstallationElectrical Connections Thermostat Wiring and LocationElectrical Connections Electrical Connections Electrical Connections Electrical Connections Electrical Connections Venting into an unlined masonry chimney is prohibited Additional Requirements for Canadian InstallationsVenting Venting Categories Venting General GuidelinesVertically VENTED, Category I Figure Standard CombustionCategory I Horizontal Venting Requirements Vent Support Horizontally VENTED, Category III Figure Vertically VENTED, Category III Type B Draft Hood Connector Venting Venting Combustion AIR Venting and Piping Separarted Combustion Installation Venting CategoryCarbon Monoxide Exhaust VentingSeparated Combustion Concentric Vent Box DimensionsConcentric Vent Installation Horizontal Intake/Vent Installation Exhaust AIR Collar AIR Inlet CollarVertical Termination Horizontal TerminationShut Down OperationExplanation of Controls See Figure GAS Input Rate Primary AIR Shutter AdjustmentMain Burner Orifice Schedule Tubular Unit Heater High Altitude DerationNever over oil the motor or premature failure may occur Periodic ServiceSymptoms Possible Causes Corrective Action Tubular Propeller Troubleshooting GuideRealign power venter wheel Check operation of switch, did the switch LED Status Indicates CHECK/REPAIR Pattern Status CHECK/REPAIR ItemDescription Propeller Parts HOW to Order Replacement Parts Unit Type UT 14, 15 + Accessories AS5 Capacity CA Supply Voltage SVWith power and gas on With power and gas offPRE-INSPECTION Information GeneralHvac Products