Thermo Products chx-3 75n, 100n, 125n Is Inducer Running On Low Speed? Yes Does The Hot

Page 57
IS INDUCER RUNNING

All installations and services must be performed by qualified service personnel.

IS INDUCER RUNNING

ON LOW SPEED?

YES

DOES THE HOT

SURFACE IGNITOR

ENERGIZE AND GLOW?

YES

NO

NO

CHECK CONTACTS ON LOW FIRE PRESSURE SWITCH AND FOR BLOCKAGE IN FLUE. IF OK, REPLACE DUAL PRESSURE SWITCH.

IS THERE VOLTAGE ACROSS

HOT SURFACE IGNITOR

TERMINALS "IGN" & "IGN N" AT THE 50V51-843 CONTROL AFTER 17 SECOND PREPURGE?

YES

CHECK WIRING TO HOT

SURFACE IGNITOR AND

IF OK, REPLACE HOT

SURFACE IGNITOR

ASSEMBLY

REPLACE THE

50V51-843 CONTROL.

 

 

YES

 

 

 

 

IS THE HIGH LIMIT,

NO

ROLL-OUT LIMIT, AND

AUX LIMIT ON

 

 

(CDX MODELS)

 

SWITCHES CLOSED?

NO

IF HIGH LIMIT OR

AUX LIMIT OPEN CHECK

FOR RESTRICTED

FILTERS OR DUCT WORK IF ROLL-OUT SWITCH OPEN INSPECT FLUE FOR RESTRICTIONS.

AFTER HOT SURFACE

IGNITOR WARM-UP,

DOES GAS VALVE OPEN?

YES

AFTER GAS VALVE

OPENS, DO THE

BURNERS IGNITE?

NO

NO

 

CHECK ACROSS "MVL" AND

 

 

"MV COM" TERMINALS ON

 

 

50V51-843 CONTROL FOR 24

NO

 

VOLTS DURING THE 4 SECOND

 

 

 

FLAME PROVING PERIOD

 

 

AFTER IGNITOR WARM-UP.

 

 

IS THERE 24 VOLTS?

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

IS COLLECTOR BOX

NO

PRESSURE SWITCH CLOSED?

YES

CHECK WIRING TO GAS

VALVE AND IF OK,

REPLACE GAS VALVE.

CHECK FOR PROPER LINE

AND MANIFOLD PRESSURE.

REFERENCE GAS PRESSURE

CHART PAGE 31.

REPLACE THE

50V51-843 CONTROL.

CHECK DRAIN FOR BLOCKAGE WATER TRAPPED IN HOSE, REPLACE SWITCH.

YES

OK

51

Image 57
Contents CHX3-75N CDX3-75N CHX3-100N CDX3-100N MODELS FOR USE WITH NATURAL GAS OR LP GAS PROPANECHX3-125N CDX3-125N INSTALLATION AND OPERATION MANUALI. SAFETY INFORMATION This and the previous page contain reproductions of the various warning and instruction labels placed on the Thermo Pride Two Stage Condensing Gas Furnaces. Please read and comply with the contents of these labels 1.A windows be opened The CHX3/CDX3 furnace models are sealed combustion design, which does not require an air shutter adjustment air shutters are not used for proper flame characteristics. Burner box access cover must always be secured with all screws in place and tightened before operating furnace INDEX SECTIONBEGINNING PAGE II. FURNACE SPECIFICATIONS CDX3 SERIES INSTALLATION PARTS PACKAGES – CHX3-75 INSTALLATION PARTS PACKAGES – CDX3-75 Grounding instructions III. GENERAL INSTALLATION B1. CDX3 HORIZONTAL APPLICATION B. FURNACE LOCATIONFigure PVC Pipe Designation Maximum Quantity of Elbows Outside Combustion Air Intake RH view E.Direct Venting Through a Sidewallc.The vent terminal shall not be located •near soffit vents, crawl space vents, or other areas where condensate or water vapor could create a nuisance, hazard, or cause property damage, and Page E1. Single-PipeSidewall Venting Option 5.Optional Direct Vent Terminations Install these optional kits according to the instructions provided with each kit. The location and clearance requirements are identical to those of the standard vent terminations described in this manual 1.Figures 6B, 7, and 8 follow depicting typical exhaust vent and air intake connections for the furnace model series CHX3 and the CDX3, respectively, as well as a list of required parts to correctly install each system Applications Applications leading away from the furnace must be composed of 3-inchdiameter PVC pipe and pipe fittings only. Refer to item E in Figure 3. Connecting The Combustion Air Intake Piping Figure 14. TRAP ASSEMBLY MOUNTED ON CHX3 I.CONDENSATE DRAIN LINE AND TRAP ASSEMBLYFigure 15. TRAP ASSEMBLY MOUNTED ON CDX3 2.Determine on which side of furnace the condensate disposal line is to be run NOTICE: On CHX3/CDX3’s this must be the same side as the flue outlet or bottom of unit. Attach the condensate trap to the furnace casing using the #8x3/4” sheet metal screws provided in the parts package. Pilot holes are provided on both sides of the casing for mounting J. GENERAL GAS PIPING J1. REQUIREMENTS AND SIZING OF DUCT WORK Figure 18A TABLE 2A K. FILTERS 1. CHX3 MODELS: HIGHBOYS Figure2. CDX3 MODELS: COUNTERFLOWS Figure L. WIRING Table 4A Switch Settings S7 DIP SwitchOptions Time2-StageBlower Settings from factory Table 4C IV. STARTING THE UNIT A. SEQUENCE OF OPERATIONS FLAME MUST BE DETECTED IF THERMOSTAT W2 CONTACTS ARE CLOSED OTHERWISE OPERATING INSTRUCTIONS B. INITIAL START UPObserve the following precautions when measuring C. Measuring And Adjusting Heat Input RateA.Burner manifold pressure with a pressure gauge B.Gas flowrate by clocking gas meterNOTICE: A U-tubemanometer, measuring pressure in inches of water column, is recommended for all gas pressure measurements. However, an aneroid pressure gauge, in good working condition, capable of reading pressure changes of 0.05 in. W.G., or less, that was recently calibrated within the last year, is a satisfactory alternate. These two 2 devices will be considered as equivalent and interchangeable. Either device is referred to below as a “pressure gauge” Heat input rate in BTUH = Figure Checking The Burner Flame 21.Go to Checkout Procedure belowCheckout Procedure TABLE 6 - CONVERTING GAS FLOW RATE V. INSTALLERS INSTRUCTIONS TO USER D. FURNACE CHECKOUT PROCEDUREFigure VI. TROUBLESHOOTING Power must be disconnected before servicing DIAGNOSTIC FEATURESTROUBLESHOOTING GUIDE IS INDUCER RUNNING ON LOW SPEED? YES DOES THE HOT DO BURNERS STAY LIT PAST PROOF OF FLAME CHECK? REPLACE THE 50V51-843CONTROL CHECK FOR 24 VOLTS Appendix –AReplacement Parts List Page Page Page Appendix – B Wiring Diagrams