Thermo Products ome-72d36 service manual III. Furnace Specifications Model, Burner Data

Page 10

All installations and services must be performed by qualified service personnel.

III. FURNACE SPECIFICATIONS

MODEL

 

OME-72

 

Low Fire

High Fire1

HEAT INPUT RATE (BTUH)

70,000

 

85,000

HEATING CAPACITY (BTUH)

60,000

 

72,000

BURNER NOZZLE (GPH X

 

 

 

ANGLE, HOLLOW CONE)

0.50X80°A

0.60X80°A

OIL PUMP PRESSURE (PSIG)

 

120

 

VENT PIPE SIZE (INCHES)

 

4

 

DESIGN TEMPERATURE RISE (°F)

65

 

MINIMUM RETURN AIR TEMP. (°F)

50

 

SEASONAL EFFICIENCY

 

 

 

(AFUE2 *, %)

 

86

 

1Burner shipped with 0.60x80°A nozzle

2*AFUE - INCLUDES STEADY STATE THERMAL EFFICIENCY AND OFF CYCLE LOSSES.

ELECTRICAL RATINGS AND SETTINGS: ELECTRICAL SUPPLY: 120 VAC / 60HZ / 1 PHASE

MAXIMUM TIME DELAY TYPE FUSE OR HACR BREAKER RATING: 15 AMPS

TOTAL RATED CURRENT (AMPS): 10.3

NOMINAL HEAT ANTICIPATOR SETTING -- 0.2 mA

DIMENSIONS & WEIGHTS:

CABINET: WIDTH - 18 IN., DEPTH – 24-3/4 IN., HEIGHT - 57 IN.

NO.70 MOBILE HOME BASE: WIDTH - 18 5/16 IN., DEPTH - 24¼ IN., HEIGHT - 4 IN.

WARM AIR DUCT: WIDTH – 12 IN., DEPTH – 12 IN., HEIGHT - 14 ¼ IN.

COTTAGE BASE: WIDTH – 18 3/16 IN., DEPTH - 24¼ IN., HEIGHT – 14¾ IN.

FILTER QUANTITY & SIZE: (1) @ 18 IN. x 24 IN. x 1 IN. EA.

APPROXIMATE SHIPPING WEIGHT: 240 LBS.

 

BURNER DATA

 

OME-72

MANUFACTURER:

R.W. BECKETT CORP.

MODEL:

AFG

AIR TUBE LENGTH (IN.): 3

HEAD DESIGN:

F-3

REFRACTORY TYPE:

ISOFORM (SOFT FIBER)

OIL PUMP

 

PRESSURE (P.S.I.G.)

120

8

Image 10
Contents OIL-FIRED Furnace Safety Section Do not RUN the OIL Pump DRY for More than Five MinutesPage Page Page Page Table of Contents Section Beginning Page Models OME III. Furnace Specifications Model Burner DataBlower Data Standard Chimney IV. Installation Roof JackFurnace Location Base Installation Page Page Page Alcove Installation Closet InstallationCombustion AIR Page Page Fuel Piping Page Electrical Wiring AWG Terminal Definitions & Field Wiring Blower Controller Information for PSC MotorInputs Operating Modes Page PSC Trouble Shooting Diagnostic FeaturesWiring Diagram Burner Installation Burner Operation and AdjustmentPage Page Flue GAS Combustion Analysis Burner Combustion ParametersPage Troubleshooting Flowchart Correct wire connections Page Does the burner stay Yes CAD Cell Checkout Procedure Heat Exchanger Cleaning InstructionsPage Cleaning or Replacing Flue Pipes Extended ShutdownVI. User Information Section Component Locations Inspection AreasFilter Location and Cleaning Contact Information Installation / ServiceAppendix A. Replacement Parts List