All installations and services must be performed by qualified service personnel.

M. FLUE GAS COMBUSTION ANALYSIS

: Burner adjustments must be confirmed by instrumentation. Failure to use accurate or calibrated instrumentation to correctly setup the burner may result in reduced efficiency, sooting, and/or the production of hazardous carbon monoxide gas.

For typical burner combustion analysis results, refer to the table below.

BURNER COMBUSTION PARAMETERS

FURNACE MODEL OME-72

LOW-FIRE

HIGH-FIRE

 

FUEL TYPE

#1 OR #2 FUEL OIL

#1 OR #2 FUEL OIL

CO (CARBON MONOXIDE)

50PPM OR LESS

50PPM OR LESS

CO2 (CARBON DIOXIDE)

10.5-11%

11-12%

 

O2 (OXYGEN)

4.5-6%

4.5-6%

 

SMOKE SPOT RATING

0

0

 

AIR SHUTTER ADJUSTMENT

OPEN TO POSITION 3.5

OPEN TO POSITION 3.5

32

Image 34
Contents OIL-FIRED Furnace Safety Section Do not RUN the OIL Pump DRY for More than Five MinutesPage Page Page Page Table of Contents Section Beginning Page Models OME III. Furnace Specifications Model Burner DataBlower Data Standard Chimney IV. Installation Roof JackFurnace Location Base Installation Page Page Page Alcove Installation Closet InstallationCombustion AIR Page Page Fuel Piping Page Electrical Wiring AWG Terminal Definitions & Field Wiring Blower Controller Information for PSC MotorInputs Operating Modes Page PSC Trouble Shooting Diagnostic FeaturesWiring Diagram Burner Installation Burner Operation and AdjustmentPage Page Flue GAS Combustion Analysis Burner Combustion ParametersPage Troubleshooting Flowchart Correct wire connections Page Does the burner stay Yes CAD Cell Checkout Procedure Heat Exchanger Cleaning InstructionsPage Cleaning or Replacing Flue Pipes Extended ShutdownVI. User Information Section Component Locations Inspection AreasFilter Location and Cleaning Contact Information Installation / ServiceAppendix A. Replacement Parts List