All installations and services must be performed by qualified service personnel.

: If you do not follow these instructions exactly, a fire or explosion may result causing personal injury, loss of life or property damage.

: NEVER use gasoline or a mixture of oil and gasoline to start the burner or furnace.

1.Qualified service personnel must perform the first lighting of the burner.

2.The burner instructions must be read and understood before any attempt is made to light this burner.

NOTE: For the sequence of burner operations, see individual burner manual. To successfully service and initially set up this furnace you must use the following instruments:

[Items (a)-(d) ... apply to both oil and gas furnaces), item (e) ... applies to gas units only, and items (f)-(h) ... applies to oil units only]

a.Carbon dioxide (CO2) or oxygen (O2) analyzer.

b.Flue gas thermometer (range 100°F to 1000°F) and temperature-measuring device (range -40°F to 240°F, for return and supply air temperatures).

c.Carbon monoxide (CO) detector

d.Electrical multimeter

e.Liquid, U-tube type manometer or equivalent pressure measuring instrument (range: 0 – 28 in.W.G.)

f.Smoke spot tester or equivalent smoke density measuring device

g.Oil pressure gauge (range: 0-150 PSIG)

h.Vacuum gauge (range: 0-30 in. W.G. vacuum)

Turn the main service switch that provides power to the furnace to the “off” position. Set thermostat above room temperature. Open all fuel supply valves. Bleed air out of fuel supply line, if not already completed (for oil, power must be “on” to the burner and the pump must be operating to expel air in the supply line).

When ignition is established, if necessary, make a preliminary burner air adjustment to attain a clean combustion flame (one which does not create smoke by eye). The flame may be viewed through the overfire inspection cover (see exploded diagram of replacement parts for location identification). After the furnace is warmed up to a steady- state condition (about 15 minutes), the final burner adjustment should be made using combustion instrumentation for measuring carbon dioxide (CO2) or oxygen (O2), carbon monoxide (CO), smoke, and stack temperature. In order to achieve the most efficient combustion possible, the following steps must be taken.

IMPORTANT: To achieve proper combustion and efficiency instruments must be used to secure CO2, O2 and CO readings.

30

Image 32
Contents OIL-FIRED Furnace Safety Section Do not RUN the OIL Pump DRY for More than Five MinutesPage Page Page Page Table of Contents Section Beginning Page Models OME III. Furnace Specifications Model Burner DataBlower Data Furnace Location IV. Installation Roof JackStandard Chimney Base Installation Page Page Page Alcove Installation Closet InstallationCombustion AIR Page Page Fuel Piping Page Electrical Wiring AWG Terminal Definitions & Field Wiring Blower Controller Information for PSC MotorInputs Operating Modes Page PSC Trouble Shooting Diagnostic FeaturesWiring Diagram Burner Installation Burner Operation and AdjustmentPage Page Flue GAS Combustion Analysis Burner Combustion ParametersPage Troubleshooting Flowchart Correct wire connections Page Does the burner stay Yes CAD Cell Checkout Procedure Heat Exchanger Cleaning InstructionsPage Cleaning or Replacing Flue Pipes Extended ShutdownVI. User Information Section Component Locations Inspection AreasFilter Location and Cleaning Contact Information Installation / ServiceAppendix A. Replacement Parts List