All installations and services must be performed by qualified service personnel.

condensate, which causes the tank to rust. It is also recommended to use a water trap or additives to prevent condensate accumulation.

If the tank is above the burner, and gravity oil feed to the burner is permitted, a single line system may be used. The line should have a gradual slope downward of approximately 1/2 inch per foot, or more, to a point directly below where it is connected to the pump. Installing the line with a downward slope will help prevent the formation of air pockets in the line.

IMPORTANT: An oil safety valve or a delayed-action solenoid valve is required with all gravity feed oil supply systems.

IMPORTANT: The oil storage tank must be free of water, sludge and scale to prevent excessive wear and possible damage to furnace oil pump and burner nozzle. A fuel oil filter installed in the oil supply line to the burner is required.

OIL FILTER: For all installations, use a low micron, oil filter with the capacity to trap particles 10 microns in diameter, or greater. Filtering the oil supply helps to prevent nozzle clogging. Install the oil filter inside the building between the tank shutoff valve and the burner. The filter cartridge should be replaced at least once a year. The filter body should be thoroughly cleaned before installing a new cartridge.

20

Image 22
Contents OIL-FIRED Furnace Safety Section Do not RUN the OIL Pump DRY for More than Five MinutesPage Page Page Page Table of Contents Section Beginning Page Models OME III. Furnace Specifications Model Burner DataBlower Data Standard Chimney IV. Installation Roof JackFurnace Location Base Installation Page Page Page Alcove Installation Closet InstallationCombustion AIR Page Page Fuel Piping Page Electrical Wiring AWG Terminal Definitions & Field Wiring Blower Controller Information for PSC MotorInputs Operating Modes Page PSC Trouble Shooting Diagnostic FeaturesWiring Diagram Burner Installation Burner Operation and AdjustmentPage Page Flue GAS Combustion Analysis Burner Combustion ParametersPage Troubleshooting Flowchart Correct wire connections Page Does the burner stay Yes CAD Cell Checkout Procedure Heat Exchanger Cleaning InstructionsPage Cleaning or Replacing Flue Pipes Extended ShutdownVI. User Information Section Component Locations Inspection AreasFilter Location and Cleaning Contact Information Installation / ServiceAppendix A. Replacement Parts List