All installations and services must be performed by qualified service personnel.

After fuel valve opens, does the burner ignite?

No

Is oil present in the fuel line at the valve?

Yes

No

Check the fuel supply. Open all manual shutoff valves serving the unit.

Purge any air in the fuel line.

Yes

Are the ignition electrodes

 

No

 

Reposition to

 

 

 

positioned correctly?

 

 

correct location.

Yes

Check for blocked or severely worn burner nozzle. Clean or replace as required.

 

 

Does the burner stay

No

lit past proof of flame

 

check?

 

 

 

Yes

 

Yes

Is the oil tank full of fuel? Is the fuel clean without contaminates?

Is the fuel filter dirty?

 

Add or replace fuel and fuel

 

No

filter. Also, check cad cell

 

for proper operation.

 

 

 

 

 

 

Does the fan timer

No

energize the circulating

 

air blower after the 56

 

second time delay?

 

 

 

 

 

Yes

Check settings on fan timer against those on connection diagram. Is blower still inoperable

after time delay with fan timer set correctly?

 

Measure voltage

Yes

on the circulating

air blower terminals.

 

 

Is it 120 VAC?

 

 

Yes

Does blower wheel spin freely?

Yes

Is blower motor

capacitor functioning

properly?

Yes

37Replace motor

 

 

 

Check wiring to

 

 

 

 

blower. If okay,

 

No

 

 

set fan selector

 

 

 

 

switch to manual.

 

 

 

 

If fan operates,

 

 

 

 

replace fan timer.

 

 

 

 

 

 

 

 

 

 

Check for blower wheel

No

 

rubing against housing

 

 

or motor shaft spinning

 

freely. Adjust or replace

 

 

 

as necessary.

No

 

 

 

 

 

 

 

 

 

 

 

 

Replace blower

 

 

 

 

 

 

 

 

 

motor capacitor.

 

 

 

 

 

 

 

Image 39
Contents OIL-FIRED Furnace Do not RUN the OIL Pump DRY for More than Five Minutes Safety SectionPage Page Page Page Table of Contents Section Beginning Page Models OME Burner Data III. Furnace Specifications ModelBlower Data IV. Installation Roof Jack Standard ChimneyFurnace Location Base Installation Page Page Page Closet Installation Alcove InstallationCombustion AIR Page Page Fuel Piping Page Electrical Wiring AWG Blower Controller Information for PSC Motor Terminal Definitions & Field WiringInputs Operating Modes Page Diagnostic Features PSC Trouble ShootingWiring Diagram Burner Operation and Adjustment Burner InstallationPage Page Burner Combustion Parameters Flue GAS Combustion AnalysisPage Troubleshooting Flowchart Correct wire connections Page Does the burner stay Yes Heat Exchanger Cleaning Instructions CAD Cell Checkout ProcedurePage Extended Shutdown Cleaning or Replacing Flue PipesVI. User Information Section Inspection Areas Component LocationsContact Information Installation / Service Filter Location and CleaningAppendix A. Replacement Parts List