All installations and services must be performed by qualified service personnel.

After pre-purge, does the oil primary produce a spark at the

ignition electrodes?

Yes

No

Is there 120 VAC across the ignition transformer?

Yes

No

Try resetting the oil primary control by depressing the RESET button. Check cad cell function. If all else fails, replace the oil primary.

Check wiring to the ignition transformer and the

electrodes. Also, check ignition electrode gap. Reset if necessary. Replace electrodes or ignition transformer.

While ignition electrodes are sparking does fuel valve open?

Yes

No

Does the oil solenoid

valve have 120 VAC across it during the ignition attempt?

Yes

Check wiring to fuel valve. If valve does not open, replace fuel valve.

No

Try resetting the oil primary control by depressing the RESET button. If this does not work, replace the oil primary.

36

Image 38
Contents OIL-FIRED Furnace Safety Section Do not RUN the OIL Pump DRY for More than Five MinutesPage Page Page Page Table of Contents Section Beginning Page Models OME III. Furnace Specifications Model Burner DataBlower Data Furnace Location IV. Installation Roof JackStandard Chimney Base Installation Page Page Page Alcove Installation Closet InstallationCombustion AIR Page Page Fuel Piping Page Electrical Wiring AWG Terminal Definitions & Field Wiring Blower Controller Information for PSC MotorInputs Operating Modes Page PSC Trouble Shooting Diagnostic FeaturesWiring Diagram Burner Installation Burner Operation and AdjustmentPage Page Flue GAS Combustion Analysis Burner Combustion ParametersPage Troubleshooting Flowchart Correct wire connections Page Does the burner stay Yes CAD Cell Checkout Procedure Heat Exchanger Cleaning InstructionsPage Cleaning or Replacing Flue Pipes Extended ShutdownVI. User Information Section Component Locations Inspection AreasFilter Location and Cleaning Contact Information Installation / ServiceAppendix A. Replacement Parts List