Marley / MC Fluid Cooler / Engineering Data: Water Quality | 15 |
|
The MC Fluid Cooler can be a very effective air washer. Atmospheric dust able to pass through the relatively small louver openings will enter the recirculating water system. Increased concentrations can intensify systems maintenance by clogging screens and
In areas prone to dust and sedimentation, you should consider installing some means for keeping the collection basin clean. Typical devices include side stream filters and a variety of filtration media.
Blowdown
Blowdown or Bleedoff is the continuous removal of a small portion of the water from the open recirculating system. Blowdown is used to prevent the dissolved solids from concentrating to the point where they will form scale. The amount of blowdown required depends on the cooling
User Manual .
CAUTION
The fluid cooler must be located at such distance and direction to avoid the possibility of contaminated discharge air being drawn into building fresh air intake ducts.The purchaser should certify that the location of the fluid cooler is in compliance with applicable air pollution, fire and clean air codes.
Water Treatment
To control the buildup of dissolved solids resulting from water evaporation, as well as airborne impurities and biological contaminants including Legionella, an effective consistent water treatment program is required. Simple blowdown may be adequate to control corrosion and scale, but biological contamination can only be controlled with biocides.
An acceptable water treatment program must be compatible with the variety of materials incorporated in a fluid
MC Fluid Cooler User Manual which accompanies the fluid cooler and also is available from your local Marley sales representative.