Forward-curved centrifugal fans are dynamically balanced and mounted on tubular steel shafts. Fans are supported by roller-bearings mounted at both ends with heavy-guage steel supports. Spherical roller bearings are rated at an L10 life of 50,000 hours.

Fan guard / Air-inlet screens are 16 gauge galvanized steel.

TEFC Fan Motor—1.15 service factor, variable torque, and specially insulated for fluid cooler duty.

The MC Fluid Cooler air movement package including the structural support—guaranteed against failure for a period of five full years. The motor is warranted separately by the motor manufacturer.

Water Distribution System

Pressurized spray system distributes water evenly over the coil. Steel header box with PVC branch arms. Low-clog polypropylene nozzles—delivers precise distribution of water over the coil area.

Marley's hot-dipped galvanized coil is tested at 2757 kPa to ensure integrity and sloped to ensure total drainage at shutdown

Marley XCEL drift eliminators—limit drift losses to no more than .005% of the design m3/hr flow rate.

Structure

Forced-draft, counter-flow design requires considerably less plan area than crossflow fluid coolers typically use. Series 300 stainless steel or heavy mill galvanized steel construction.

Factory assembled—ensures final field installation will be hassle-free.

Centrifugal fans and a fully-enclosed falling water area create one of the quietest fluid cooler configurations on the market.

Image 3
Contents Marley MC Fluid Cooler Marley / MC Fluid Cooler / Table of Contents Marley / MC Fluid Cooler Marley / MC Fluid Cooler Side Elevation Marley / MC Fluid Cooler / Engineering Data Schematic7014H101 7014J101 3061 1041 3098 2587 1887 7014K101 Inlets 7055P081 15 x 7055Q081 4172 813 18.6 x Inlets Outlets Access Section Model Marley / MC Fluid Cooler / Engineering Data Support80MAX Marley / MC Fluid Cooler / Engineering Data HoistingAIR Inlet Elevation Indoor Storage Tank Fluid Cooler CoilFluid Cooling Recirculating Water Electric Basin HeatersMarley / MC Fluid Cooler / Engineering Data Water Quality BlowdownWater Treatment Thermal Performance Marley / MC Fluid Cooler / Specifications BasePerformance Warranty BaseCoil Design LoadingConstruction Mechanical Equipment Hot Water Distribution System AccessWarranty Drift EliminatorsMarley / MC Fluid Cooler / Specifications Options Stainless Steel Options Stainless Steel Collection BasinAll Stainless Fluid cooler Convenience and Safety Options Top Access Platform Ladder Safety CageLadder Extension Access Door Platform Distribution System Access Door PlatformControl Options Control System Basin Heater Vibration Limit SwitchMarley Premium VFD System Marley / MC Fluid Cooler / Specifications Options Miscellaneous Options Sound Control Discharge Hood Gregorys Bank Worcester WR3 8AB United Kingdom