Marley / MC Fluid Cooler / Specifications: Base
Specifications | Specification Value |
1.0Base:
16
1.1 | Furnish and install a | ■ Your specification base establishes the type, configuration, base | |||||||||||||||||||||||||||||||
| material and physical limitations of the fluid cooler to be quoted. | ||||||||||||||||||||||||||||||||
| fill, industrial duty, galvanized steel, | During the planning and layout stages of your project, you will have | |||||||||||||||||||||||||||||||
| closed circuit fluid cooler. Unit shall | focused your attention on a fluid cooler selection that fits your space | |||||||||||||||||||||||||||||||
| consist of _____ cell(s), as shown on | allotment, and whose power usage is acceptable. Limitations on | |||||||||||||||||||||||||||||||
| plans. The limiting overall dimensions | physical size and total operating kW avoid the introduction of unfore- | |||||||||||||||||||||||||||||||
| of the fluid cooler shall be _____ wide, | seen operational and | |||||||||||||||||||||||||||||||
| _____ long, and _____ high. Total oper- | cells, and the maximum fan kW/cell will work to your advantage. | |||||||||||||||||||||||||||||||
| ating kW of all fans shall not exceed | The benefit of a | |||||||||||||||||||||||||||||||
| _____ kW, consisting of_____ @ _____ | ||||||||||||||||||||||||||||||||
| kW motor(s). Fluid cooler shall be simi- | are inherently easy to operate, access and maintain. | |||||||||||||||||||||||||||||||
| lar and equal in all respects to Marley | counterflow fluid coolers have all mechanical equipment located at a | |||||||||||||||||||||||||||||||
| Model _____________________. | low level for easy access, and the water distribution system is acces- | |||||||||||||||||||||||||||||||
|
| sible by simply removing the lightweight drift eliminator panels | |||||||||||||||||||||||||||||||
2.0 | Thermal Performance: | ■ CTI Certification means that the fluid cooler has been tested under | |||||||||||||||||||||||||||||||
|
| operating conditions and found to perform as rated by the manufac- | |||||||||||||||||||||||||||||||
2.1 | Water as the heat transfer fluid. | turer under those circumstances. It | |||||||||||||||||||||||||||||||
| The fluid cooler shall be capable of | assures the buyer that the fluid cooler | |||||||||||||||||||||||||||||||
| cooling _____ m3/hr of water from | is not intentionally or inadvertently |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||
| _____ °C to _____ °C at a design enter- | undersized by the manufacturer. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||||||||
| ing air |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| °C. Coil pressure drop shall not exceed |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
| _____ kPa. The thermal performance |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| rating shall be Certified by the Cooling |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Technology Institute. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
2.1Aqueous glycol solution as the heat transfer fluid.
The fluid cooler shall be capable of cooling _____ m3/hr of water from
_____ °C to _____ °C at a design enter- ing air
°C. Coil pressure drop shall not exceed
_____ kPa. The thermal performance rating shall be based on the Cooling Technology Institute certified perfor- mance rating adjusted for the thermal properties of the aqueous glycol solu- tion used.
3.0Performance Warranty:
3.1 | CTI Certification notwithstanding, the | ■ However, CTI certification alone is not sufficient to assure you that the |
| fluid cooler manufacturer shall guaran- | fluid cooler will perform satisfactorily in your situation. Certification |
| tee that the fluid cooler supplied will | is established under relatively controlled conditions, and fluid coolers |
| meet the specified performance condi- | seldom operate under such ideal circumstances. They are affected by |
| tions when the fluid cooler is installed | nearby structures, machinery, enclosures, effluent from other sources, |
| according to plan. If, because of a | etc. Responsible and knowledgeable bidders will take such |
| suspected thermal performance defi- | cific effects into consideration in selecting the fluid |
| ciency, the owner chooses to conduct | specifier must insist by the written specification that the designer/ |
| an | manufacturer guarantee this “real world” performance. Any reluc- |
| under the supervision of a qualified, | tance on the part of the bidder should cause you some concern. |
| disinterested third party in accordance |
|
| with CTI or ASME standards during the |
|
| first year of operation; and if the fluid |
|
| cooler fails to perform within the limits |
|
| of test tolerance; then the fluid cooler |
|
| manufacturer will pay for the cost of |
|