Marley / MC Fluid Cooler / Specifications: Base
Specifications | Specification Value |
8.0Drift Eliminators:
19
8.1 | Drift eliminators shall be PVC, triple | ■ Drift rate varies with design water loading and air rate, as well as drift |
| pass and shall limit drift losses to no | eliminator depth and number of directional changes. The indicated |
| more than 0.005% of the design water | rate of 0.005% is easily achievable without premium cost. If a lower |
| flow rate. | rate is required, please discuss with your Marley sales representative. |
9.0 | Hot Water Distribution System: |
|
9.1 | A pressured spray system shall distrib- | ■ The combination of PVC piping and polypropylene nozzles is very |
| ute water evenly over the fill. Header | resistant to the |
| box shall be steel and branch arms |
|
| shall be PVC with polypropylene spray |
|
| nozzles attached to the branch arms by |
|
| an integral screw connection for ease |
|
| of removal and cleaning. The spray |
|
| system shall provide full coverage |
|
| of the coil at a flow rate sufficient to |
|
| ensure complete wetting of the coil at |
|
| all times. |
|
10.0 | Casing: |
|
10.1 | The casing shall be heavy gauge |
|
| galvanized steel and shall be capable |
|
| of withstanding the loads described in |
|
| paragraph 5.1. |
|
11.0 | Access: |
|
11.1 | A large galvanized, rectangular access |
|
| door shall be located on both end |
|
| panels for entry into the cold water |
|
| basin. Rectangular panels are shall be |
|
| provided for access to the fan plenum |
|
| area to facilitate inspection and allow |
|
| maintenance to the fan drive system |
|
12.0 | Cold Water Collection Basin: |
|
12.1 | The collection basin shall be heavy- | ■ The MC fluid cooler design offers |
| gauge galvanized steel and shall | outlets may be supplied to accommodate a variety of piping schemes. |
| include the number and type of suction | Unless so specified, the fluid cooler you may be asked to approve |
| connections required to accommodate | may only be available with one type of suction connection requiring |
| the | you to redesign your piping layout. |
| the plans. Suction connections shall be | The sloping floor and |
| equipped with debris screens. A fac- | |
| tory installed, float operated, mechani- | way to achieve |
| cal |
|
| overflow and drain connection shall be |
|
| provided in each cell of the fluid cooler. |
|
| The basin floor shall slope toward the |
|
| drain to allow complete flush out of |
|
| debris and silt which may accumulate. |
|
13.0 | Warranty: |
|
13.1 | The MC Fluid Cooler shall be free from |
|
| defects in materials and workmanship |
|
for a period of eighteen (18) months from the date of shipment.