Marley / MC Fluid Cooler / Specifications: Options

Specifications

Specification Value

23

temperature at the coil and the other for set point. Process temperature input shall be obtained using a thermal sens- ing device on the process coil and wired back to the solid state temperature controller in the control panel. Staging of multiple motors and speeds will be accomplished with an integral PLC.

Vibration Limit Switch:

6.5Add the following paragraph in the Mechanical Equipment section: A single-pole,double-throw vibration limit switch in a IP55 housing shall be installed on the mechanical equipment support for wiring into the owner’s control panel. The purpose of this switch will be to interrupt power to the motor in the event of excessive vibra- tion. It shall be adjustable for sensitiv- ity, and shall require manual reset.

Basin Heater:

11.2Add the following paragraph in the Cold Water Basin section: Provide an electric immersion heater for each cell of the fluid cooler to prevent freez- ing of water in the collection basin during periods of shutdown. The rod type heater is installed in the side of the cold water basin. Each heater will include an integral thermostat, set point nominally 4°C but adjustable to suit local operating requirements.

Fan Motor Variable Speed Drive:

Marley All Weather ACH550 System

6.4Add the following paragraph in the Mechanical Equipment section when VFD is used with customers Building Management System: A complete UL listed Variable Speed Drive system in a IP10 indoor, IP52 indoor or IP14 outdoor enclosure shall be provided. The VFD shall use PWM technology with IGBT switching and integrated bypass design.

VFD out put switching shall not cause mechanical issues with gearbox teeth or drive shafts. The VFD shall catch a fan spinning in the reverse direction without tripping. The panel shall include a main disconnect with short circuit protection and external operating handle, lockable

Unless specified otherwise, a Fire Fighting Enterprises switch will be provid- ed. A double-pole, double-throw model is also available. The requirement for manual reset assures that the fluid cooler will be visited to determine the cause of excess vibration.

The Marley basin heater components described at left represent our recommendation for a reliable automatic system for the prevention of basin freezing.They are normally shipped separately for installation at the jobsite by the installing contractor. When purchased in conjunction with the enhanced Control System option, however, they are customar- ily factory-mounted and tested.

Submerged in basin water, in which zinc ions are present, copper immersion heaters must not be used. Insist upon stainless steel.

The ambient air temperature that you insert in the specifications should be the lowest 1% level of winter temperature prevalent at site.

Marley VFD drive systems are designed to combine absolute tem- perature control with ideal energy management. The fluid cooler user selects a cold water temperature and the drive system will vary the fan speed to maintain that temperature. Precise temperature control is accomplished with far less stress to the mechanical equipment components. The improved energy management provides fast pay- back.

Image 23
Contents Marley MC Fluid Cooler Marley / MC Fluid Cooler / Table of Contents Marley / MC Fluid Cooler Marley / MC Fluid Cooler Side Elevation Marley / MC Fluid Cooler / Engineering Data Schematic7014H101 7014J101 3061 1041 3098 2587 1887 7014K101 Inlets 7055P081 15 x 7055Q081 4172 813 18.6 x Inlets Outlets Access Section Model Marley / MC Fluid Cooler / Engineering Data Support80MAX Marley / MC Fluid Cooler / Engineering Data HoistingAIR Inlet Elevation Indoor Storage Tank Fluid Cooler CoilFluid Cooling Recirculating Water Electric Basin HeatersWater Treatment Marley / MC Fluid Cooler / Engineering Data Water QualityBlowdown Thermal Performance Marley / MC Fluid Cooler / Specifications BasePerformance Warranty BaseConstruction CoilDesign Loading Mechanical Equipment Hot Water Distribution System AccessWarranty Drift EliminatorsAll Stainless Fluid cooler Marley / MC Fluid Cooler / Specifications OptionsStainless Steel Options Stainless Steel Collection Basin Ladder Extension Convenience and Safety Options Top Access PlatformLadder Safety Cage Control Options Control System Access Door PlatformDistribution System Access Door Platform Basin Heater Vibration Limit SwitchMarley Premium VFD System Marley / MC Fluid Cooler / Specifications Options Miscellaneous Options Sound Control Discharge Hood Gregorys Bank Worcester WR3 8AB United Kingdom