SPX Cooling Technologies 7014H081 - 7014K121 Convenience and Safety Options Top Access Platform

Page 21

Marley / MC Fluid Cooler / Specifications: Options

21

Specifications

Convenience and Safety Options

Top Access Platform:

11.2Add the following paragraph in the Access section: There shall be an access platform at the top of the fluid cooler to allow access to the drift eliminators and distribution system. The platform shall be free-standing galvanized steel bar grating, sup- ported by galvanized steel framework. The platform shall be surrounded by a handrail, kneerail, and toeboard designed according to meet local safety requirements. Handrails and kneerails shall consist of 42mm O.D. x

15 gauge galvanized structural tubing, the handrail of which shall be capable of withstanding a 890 N concentrated live load in any direction. Posts are

51mm x 51mm square structural tub- ing and shall be spaced on centers of 2.44m or less. A ladder shall be per- manently attached to the platform and to the casing of the fluid cooler, rising from the base of the fluid cooler to the top of the handrail.

Ladder Extension:

11.2Add the following to the end of paragraph 11.2: Provide a ladder extension for connection to the foot of the ladder. This extension shall be long enough to rise from the roof

(grade) level to the base of the fluid cooler. The installing contractor shall be responsible for cutting the ladder to length; attaching it to the foot of the fluid cooler ladder; and anchoring it at its base.

Ladder Safety Cage:

11.3Add the following paragraph in the Access section: A heavy gauge galva- nized steel safety cage shall surround the ladder, extending from a point approximately 2150mm above the foot of the ladder to the top of the handrail.

Specification Value

Periodic inspection and maintenance of a fluid cooler distribution system is fundamental to preserving maximum cooling system effi- ciency. All fluid coolers—crossflow or counterflow—are subject to clogging to varying degrees by waterborne contaminants such as pipe scale and sediment. Therefore, safe and easy access to these components is of significant value to the operator.

Access can be provided in a number of ways, including portable ladders or scaffolding, but for maximum safety and convenience, a field installed Marley access platform with guardrails is available to make this task as safe and user-friendly as possible. Further, its loca- tion on the side of the fluid cooler does not add to the height of the unit, preserving architectural integrity. It also saves the owner time and money, in that maintenance personnel may devote their time to inspection rather than searching for ladders or erection of portable scaffolding.

Many fluid coolers are installed such that the base of the unit is 600mm or more above the roof or grade level. This makes it difficult to get up to the foot of the attached ladder. The ladder extension alle- viates this problem. Marley ladder extensions are available in stan- dard 1524mm and 3353mm lengths.

Image 21
Contents Marley MC Fluid Cooler Marley / MC Fluid Cooler / Table of Contents Marley / MC Fluid Cooler Marley / MC Fluid Cooler Side Elevation Marley / MC Fluid Cooler / Engineering Data Schematic7014H101 7014J101 3061 1041 3098 2587 1887 7014K101 Inlets 7055P081 15 x 7055Q081 4172 813 18.6 x Inlets Outlets Access Section Model Marley / MC Fluid Cooler / Engineering Data Support80MAX Marley / MC Fluid Cooler / Engineering Data HoistingAIR Inlet Elevation Fluid Cooling Recirculating Water Fluid Cooler CoilElectric Basin Heaters Indoor Storage TankMarley / MC Fluid Cooler / Engineering Data Water Quality BlowdownWater Treatment Performance Warranty Marley / MC Fluid Cooler / Specifications BaseBase Thermal PerformanceCoil Design LoadingConstruction Mechanical Equipment Warranty AccessDrift Eliminators Hot Water Distribution SystemMarley / MC Fluid Cooler / Specifications Options Stainless Steel Options Stainless Steel Collection BasinAll Stainless Fluid cooler Convenience and Safety Options Top Access Platform Ladder Safety CageLadder Extension Access Door Platform Distribution System Access Door PlatformControl Options Control System Basin Heater Vibration Limit SwitchMarley Premium VFD System Marley / MC Fluid Cooler / Specifications Options Miscellaneous Options Sound Control Discharge Hood Gregorys Bank Worcester WR3 8AB United Kingdom