SYSTEM CONTROL INSTALLATION, OPERATION AND SERVICE MANUAL

SECTION 5: TROUBLESHOOTING

DANGER

Electrical Shock Hazard

Disconnect electric before service or maintenance.

More than one disconnect switch may be required to disconnect electric to the unit.

Failure to follow these instructions can result in death or electrical shock.

WARNING

Explosion Hazard

Turn off gas supply to equipment before service or maintenance.

Failure to follow these instructions can result in death, injury or property damage.

5.1Sequence of Operation

a.On demand for heat from the thermostat, the panel will send power to the pump. The pump will begin operation.

b.Once vacuum is established, the pressure

switch at the pump will close. If the vacuum is not established within 30 seconds the pump will go into lockout (pump LED is flashing).

After one hour of lockout, the system will re- start.

c.The System Control panel sends power to the burners. The burners will go through a 45 second purge and cycle time.

d.Once flame is established, the heater will remain in operation until such time as either the heating is turned off by the thermostat, lockout conditions occur, or after 24 hours of continuous operation. After 24 hours of con-

tinuous operation, the system control will shut off and re-start to verify no faults exist in the system.

e.After the heating is turned off, the pump will continue operation for 2 minutes, post purge.

12

Image 18
Contents System Control Page Roberts-Gordon LLC Page Table of Figures Page Introduction 1.1 Safety What is a Roberts Gordon System Control?Check Installation Materials Page Specifications Pump Specifications Electrical SpecificationsBurner Electrical Ratings Outside Air Supply Blower Electrical RatingsTerminal Block Guide Select the External Wiring Diagram for the Installation InstallationInstalling the System Control Panel PreparationSystem Configuration Typical External Wiring Diagrams System ControlEP-201 or EP-301 230 V 1 Ø External Wiring Diagram208 230 V or 460 60 Hz EP-203 or EP-303 208 230 V or 460 V 3 ØOutside Air Blower External Wiring Diagram 120 60 HzTypical External Wiring Diagrams Troubleshooting System Control Troubleshooting Chart Replacement Parts System Control Internal Components DiagramSee Page 14, , Item Page Warranty is Void if ROBERTS-GORDON will not PAY forLimitations on Authority Representatives