SECTION 6: REPLACEMENT PARTS

6.1 Replacement Parts Instructions

DANGER

Electrical Shock Hazard

Disconnect electric before service or maintenance.

More than one disconnect switch may be required to disconnect electric to the unit.

Failure to follow these instructions can result in death or electrical shock.

See Page 14, Figure 10, Item 2.

6.1.3Microprocessor Programing

The microprocessor may be re-programed by a reprograming device.

Should the microprocessor program become suspect during troubleshooting, consult Roberts-Gordon LLC.

WARNING

Explosion Hazard

Turn off gas supply to equipment before service or maintenance.

Failure to follow these instructions can result in death, injury or property damage.

6.1.1Fuse 250 mA

See Page 14, Figure 10, Item 1.

This time delay fuse protects the System Control from power surges, lightning and incorrect wiring.

If the fuse needs replacing, the following steps must be taken.

Disconnect power to the System Control.

Remove the screws from the cover and remove the cover of the System Control. See Page 5, Section

3.2.2for details.

Locate the fuse, and remove the fuse with a fuse pull- ing tool. See Page 14, Figure 10, Item 1.

Replace with a new fuse rated at 250 mA slow blow.

6.1.2Transformer

The transformer on the board cannot be replaced.

15

Image 21
Contents System Control Page Roberts-Gordon LLC Page Table of Figures Page Introduction 1.1 Safety What is a Roberts Gordon System Control?Check Installation Materials Page Pump Specifications Electrical Specifications SpecificationsBurner Electrical Ratings Outside Air Supply Blower Electrical RatingsTerminal Block Guide Installing the System Control Panel InstallationSelect the External Wiring Diagram for the Installation PreparationSystem Configuration System Control Typical External Wiring DiagramsDiagram EP-201 or EP-301 230 V 1 Ø External WiringEP-203 or EP-303 208 230 V or 460 V 3 Ø 208 230 V or 460 60 Hz120 60 Hz Outside Air Blower External Wiring DiagramTypical External Wiring Diagrams Troubleshooting System Control Troubleshooting Chart System Control Internal Components Diagram Replacement PartsSee Page 14, , Item Page Warranty is Void if ROBERTS-GORDON will not PAY forLimitations on Authority Representatives