Toshiba RAV-SP240AT2-UL Evacuate and Dehydrate the System, Using Vacuum Pump, Deep Vacuum Method

Page 18

Outdoor Unit

Installation Manual

8 EVACUATE AND DEHYDRATE THE SYSTEM

CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage or improper operation.

Never use the system compressor as a vacuum pump.

Refrigerant tubes and indoor heat exchanger should be evacuated using the recommended deep vacuum method of 500 microns. The alternate triple evacuation method may be used if the procedure outlined below is followed. Always break a vacuum with dry nitrogen.

„SYSTEM VACUUM AND CHARGE

Using Vacuum Pump

1.Completely tighten flare nuts A, B, C, D, connect manifold gage charge hose to a charge port of the low side service valve.

Service Valve

Outdoor Unit

 

 

 

 

Refrigerant

 

Indoor Unit

 

 

 

A

Low Side

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

High Side

 

D

 

 

Service Valve

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.Connect charge hose to vacuum pump.

3.Fully open the low side of manifold gage.

Manifold

Manifold Gage

500 microns

Low side valve

High side valve Charge hose

Charge hose

Vacuum pump

Low side valve

4.Start vacuum pump.

5.Evacuate using either deep vacuum or triple evacuation method.

6.After evacuation is complete, fully close the low side of manifold gage and stop operation of vacuum pump.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth. The deep vacuum method is the most positive way of assuring a system is free of air and liquid water.

Deep Vacuum Graph

 

5000

 

 

 

 

 

 

 

 

4500

 

 

 

 

 

 

 

 

4000

 

 

 

 

 

 

 

 

3500

 

 

 

 

 

 

LEAK IN

 

 

 

 

 

 

 

SYSTEM

MICRONS

 

 

 

 

 

 

 

3000

 

 

 

 

 

 

 

2500

 

 

 

 

 

 

 

2000

 

 

 

 

 

 

 

1500

 

 

 

 

VACUUM TIGHT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TOO WET

 

1000

 

 

 

 

 

 

 

 

500

 

 

 

 

 

TIGHT DRY

 

 

 

 

 

 

SYSTEM

 

 

 

 

 

 

 

 

0

1

2

3

4

5

6

7

 

 

 

MINUTES

 

 

 

Triple Evacuation Method

The triple evacuation method should only be used when vacuum pump is only capable of pumping down to 28 in. of mercury vacuum and system does not contain any liquid water.

Refer to “Triple Evacuation Method chart” and proceed as follows:

1.Pump system down to 28 in. of mercury and allow pump to continue operating for an additional 15 minutes.

2.Close service valves and shut off vacuum pump.

3.Connect a nitrogen cylinder and regulator to system and open until system pressure is 2 psig.

4.Close service valve and allow system to stand for 1 hr. During this time, dry nitrogen will be able to diffuse throughout the system absorbing moisture.

5.Repeat this procedure as indicated in the chart. System will then be free of any cotaminants and water vapor.

17-EN

– 17 –

Image 18
Contents Installation manual Contents Dimension Accessory Parts Part name ’ty Shape Usage Installation manualHand this directly to the customer System Requirements „ Piping Field suppliedPrecautions for Safety Be sure to ground the equipmentEquipment Damage Hazard New Refrigerant Air Conditioner Installation Installation of NEW Refrigerant AIR Conditioner„ Required Tools/Equipment and Precautions for Use Tools/equipment Use„ Installation Location Do not install the outdoor unit in the following locationExample Barrier at rear side Barrier in front „Required ClearancesUnit in mm Upper side is free Above unit is freeInstallation Manual „ Installation of Outdoor UnitStandard installation Barriers in front and back of unitDrain nipple 5pcsProjection margin in flaring B Unit in mm Rigid Clutch type Refrigerant PipingFlaring Flaring diameter size a Unit in mmValve at liquid side „ Tightening of Flare ConnectionsDo not apply refrigerant oil to the flared surface Outer diameter of copper pipe Tightening torque„ Field wiring Electrical Connections„ Wiring Attach the front pipe cover with 4 screws Deep Vacuum Method Using Vacuum PumpEvacuate and Dehydrate the System Triple Evacuation MethodFinal Tubing Check Open service valvesValve handling precautions Liquid side11PERIODIC Maintenance Finishing10TEST RUN 12TROUBLESHOOTING Verifying Fault code status Outdoor control boardD800 D801 D802 D803 D804 D805 14POWER Save Procedure13UNIT Pump Down EH99865401

RAV-SP240AT2-UL specifications

The Toshiba RAV-SP240AT2-UL is a state-of-the-art air conditioning unit that showcases Toshiba's commitment to energy efficiency, innovation, and comfort. Designed primarily for commercial use, it stands out as an ideal solution for businesses that require a reliable and effective climate control system.

One of the main features of the RAV-SP240AT2-UL is its powerful 24,000 BTU cooling capacity, which allows it to effectively cool larger spaces. This unit functions efficiently even in extreme weather conditions, providing optimal performance regardless of outside temperatures. The RAV-SP240AT2-UL also boasts a heating capacity, making it a versatile option for year-round climate control.

Energy efficiency is a significant characteristic of this model, as it comes equipped with an advanced inverter technology. This technology allows the unit to adjust its cooling and heating output according to the specific requirements of the space. As a result, users can expect lower energy consumption, reduced electricity bills, and a lower carbon footprint. The RAV-SP240AT2-UL has a high Energy Efficiency Ratio (EER) rating that further underscores its energy-saving capabilities.

In terms of installation, the RAV-SP240AT2-UL is designed for easy integration. Its compact size and lightweight design make it suitable for various commercial settings, including offices, retail spaces, and restaurants. The unit can be installed in both horizontal and vertical configurations, providing flexibility to meet the unique layout of any building.

The Toshiba RAV-SP240AT2-UL also includes advanced filtration systems that enhance indoor air quality. Its multi-stage air filtration process removes dust, allergens, and other particulates, ensuring a healthier environment for occupants. Additionally, the unit operates at a low noise level, providing a quiet atmosphere that enhances the comfort of any space.

Another notable technology featured in the RAV-SP240AT2-UL is the Smart Control system, which allows users to monitor and manage their air conditioning remotely. This feature adds convenience and flexibility, enabling businesses to optimize their energy use and maintain a comfortable environment, even from a distance.

Overall, the Toshiba RAV-SP240AT2-UL is a robust and efficient air conditioning solution tailored for commercial spaces. With its blend of power, energy efficiency, and advanced technology, it ensures an optimal climate control experience while promoting sustainability.