Toshiba Official Manual for Air Conditioner with Model RAV-SP240AT2-UL

Page 20

Outdoor Unit

Installation Manual

9 FINISHING

After the refrigerant pipe, inter-unit wires, and drain pipe have been connected, make sure they are supported and fixed in place for the entire length.

Keep the power wires and system interconnection wires away from all factory wiring and piping.

10TEST RUN

Turn on the circuit breaker at least 12 hours before starting the system to preheat the compressor and prevent damage.

To protect the compressor, power is supplied from the 208/230 VAC input to the unit to preheat the compressor.

Check the following before starting a test run:

That all pipes are connected securely without leaks.

That the valve is open.

If the compressor is operated with the valve closed, the outdoor unit will become over pressurized, which may damage the compressor or other components.

If there is a leak at a connection, air can be sucked in and the internal pressure further increases, which may cause a burst or injury.

Operate the air conditioner using the correct procedure as specified in the Owner’s Manual.

11PERIODIC MAINTENANCE

For an air conditioning system that is operated on a regular basis, cleaning and maintenance of the indoor/ outdoor units are strongly recommended.

As a general rule, if an indoor unit is operated for about 8 hours daily, the indoor/outdoor units will need to be cleaned at least once every 3 months. This cleaning and maintenance should be carried out by a qualified service person.

Failure to clean the indoor/outdoor units regularly will result in poor performance, icing, water leaking and even compressor failure.

19-EN

– 19 –

Image 20
Contents Installation manual Contents Dimension Hand this directly to the customer Accessory PartsPart name ’ty Shape Usage Installation manual System Requirements „ Piping Field suppliedPrecautions for Safety Be sure to ground the equipmentEquipment Damage Hazard Installation of NEW Refrigerant AIR Conditioner „ Required Tools/Equipment and Precautions for UseNew Refrigerant Air Conditioner Installation Tools/equipment UseExample „ Installation LocationDo not install the outdoor unit in the following location „Required Clearances Unit in mmBarrier at rear side Barrier in front Upper side is free Above unit is free„ Installation of Outdoor Unit Standard installationInstallation Manual Barriers in front and back of unitDrain nipple 5pcsRefrigerant Piping FlaringProjection margin in flaring B Unit in mm Rigid Clutch type Flaring diameter size a Unit in mm„ Tightening of Flare Connections Do not apply refrigerant oil to the flared surfaceValve at liquid side Outer diameter of copper pipe Tightening torque„ Field wiring Electrical Connections„ Wiring Attach the front pipe cover with 4 screws Using Vacuum Pump Evacuate and Dehydrate the SystemDeep Vacuum Method Triple Evacuation MethodOpen service valves Valve handling precautionsFinal Tubing Check Liquid side10TEST RUN 11PERIODIC MaintenanceFinishing 12TROUBLESHOOTING Verifying Fault code status Outdoor control boardD800 D801 D802 D803 D804 D805 13UNIT Pump Down 14POWER SaveProcedure EH99865401

RAV-SP240AT2-UL specifications

The Toshiba RAV-SP240AT2-UL is a state-of-the-art air conditioning unit that showcases Toshiba's commitment to energy efficiency, innovation, and comfort. Designed primarily for commercial use, it stands out as an ideal solution for businesses that require a reliable and effective climate control system.

One of the main features of the RAV-SP240AT2-UL is its powerful 24,000 BTU cooling capacity, which allows it to effectively cool larger spaces. This unit functions efficiently even in extreme weather conditions, providing optimal performance regardless of outside temperatures. The RAV-SP240AT2-UL also boasts a heating capacity, making it a versatile option for year-round climate control.

Energy efficiency is a significant characteristic of this model, as it comes equipped with an advanced inverter technology. This technology allows the unit to adjust its cooling and heating output according to the specific requirements of the space. As a result, users can expect lower energy consumption, reduced electricity bills, and a lower carbon footprint. The RAV-SP240AT2-UL has a high Energy Efficiency Ratio (EER) rating that further underscores its energy-saving capabilities.

In terms of installation, the RAV-SP240AT2-UL is designed for easy integration. Its compact size and lightweight design make it suitable for various commercial settings, including offices, retail spaces, and restaurants. The unit can be installed in both horizontal and vertical configurations, providing flexibility to meet the unique layout of any building.

The Toshiba RAV-SP240AT2-UL also includes advanced filtration systems that enhance indoor air quality. Its multi-stage air filtration process removes dust, allergens, and other particulates, ensuring a healthier environment for occupants. Additionally, the unit operates at a low noise level, providing a quiet atmosphere that enhances the comfort of any space.

Another notable technology featured in the RAV-SP240AT2-UL is the Smart Control system, which allows users to monitor and manage their air conditioning remotely. This feature adds convenience and flexibility, enabling businesses to optimize their energy use and maintain a comfortable environment, even from a distance.

Overall, the Toshiba RAV-SP240AT2-UL is a robust and efficient air conditioning solution tailored for commercial spaces. With its blend of power, energy efficiency, and advanced technology, it ensures an optimal climate control experience while promoting sustainability.