Toshiba RAV-SP240AT2-UL installation manual System Requirements, „ Piping Field supplied

Page 5

Outdoor Unit

Installation Manual

3 SYSTEM REQUIREMENTS

„Piping (Field supplied)

Minimum refrigerant line length between the outdoor unit and indoor unit is 16.5” (5 m)

Maximum pipe lengths

Allowable

Height difference

Number of

pipe length

(Indoor-outdoor H)

bent portions

(ft (m))

(ft (m))

 

 

 

 

 

Total length

Indoor unit:

Outdoor unit:

 

L

Upper

Lower

10 or less

164’1” (50)

98’5” (30)

98’5” (30)

 

 

 

 

 

Figure of Single

Indoor Unit

Outdoor Unit

H

L

Refrigerant sizes

Liquid side

Gas side

 

 

 

 

Outer

Thickness

Outer

Thickness

diameter

diameter

 

 

Ø3/8”

0.03”

Ø5/8”

0.04”

(9.5 mm)

(0.8 mm)

(15.9 mm)

(1.0 mm)

Flare nuts and flaring

The flare nuts and flaring are different from those for the conventional refrigerant.

Use the flare nuts supplied with the air conditioner or those for R410A.

Before performing flaring, carefully read

“REFRIGERANT PIPING”

Insulation

Both lines need to be insulated. Use a minimum 0.4” (10 mm) wall thickness.

Refrigerant charge

Length of refrigerant

Additional refrigerant

pipe connected to

indoor/outdoor unit

 

16’5” - 98’5”

None

(5 - 30 m)

 

*98’5” - 164’1”

Add 0.43 oz/ft (40 g/m) of

refrigerant for piping that exceeds

(30 - 50 m)

98’5” (30 m) up to 164’1” (50 m).

 

 

 

*Caution during addition of refrigerant

Max. amount of additional refrigerant is 1.8 lbs (800 g).

Charge the refrigerant accurately. Overcharging may cause serious trouble with the compressor.

*Minimum refrigerant pipe is 16’5”(5 m).

This may cause a malfunction of the compressor or other devices.

Metering Device is an electronic EXV (PMV) in outdoor unit.

„Connecting power and control cables (Field supplied)

The main power is supplied to the outdoor unit. The field supplied connecting cables from the outdoor unit to the indoor unit consist for 4 wires and provides the power for the indoor unit as well as the communication signal between the outdoor and indoor unit.

System interconnection wire size must be AWG12.

Breaker must have a capacity specified in the following table.

All wiring must comply with local electric codes and NEC (National Electric Code) or CEC (Canadian Electric Code).

Model RAV-

SP240

 

 

Power supply

208/230 V, 60 Hz

 

 

MCA

24 A

 

 

MOCP (MAX Fuse/CB)

40 A

 

 

Breaker

25 A

 

 

System interconnection wires

AWG12

 

 

MCA = Minimum Circuit Amps

MOCP =Maximum Over Protection Device Amps.

EN

– 4 –

4-EN

Image 5
Contents Installation manual Contents Dimension Hand this directly to the customer Accessory PartsPart name ’ty Shape Usage Installation manual „ Piping Field supplied System RequirementsBe sure to ground the equipment Precautions for SafetyEquipment Damage Hazard „ Required Tools/Equipment and Precautions for Use Installation of NEW Refrigerant AIR ConditionerNew Refrigerant Air Conditioner Installation Tools/equipment UseExample „ Installation LocationDo not install the outdoor unit in the following location Unit in mm „Required ClearancesBarrier at rear side Barrier in front Upper side is free Above unit is freeStandard installation „ Installation of Outdoor UnitInstallation Manual Barriers in front and back of unit5pcs Drain nippleFlaring Refrigerant PipingProjection margin in flaring B Unit in mm Rigid Clutch type Flaring diameter size a Unit in mmDo not apply refrigerant oil to the flared surface „ Tightening of Flare ConnectionsValve at liquid side Outer diameter of copper pipe Tightening torqueElectrical Connections „ Field wiring„ Wiring Attach the front pipe cover with 4 screws Evacuate and Dehydrate the System Using Vacuum PumpDeep Vacuum Method Triple Evacuation MethodValve handling precautions Open service valvesFinal Tubing Check Liquid side10TEST RUN 11PERIODIC MaintenanceFinishing Verifying Fault code status Outdoor control board 12TROUBLESHOOTINGD800 D801 D802 D803 D804 D805 13UNIT Pump Down 14POWER SaveProcedure EH99865401

RAV-SP240AT2-UL specifications

The Toshiba RAV-SP240AT2-UL is a state-of-the-art air conditioning unit that showcases Toshiba's commitment to energy efficiency, innovation, and comfort. Designed primarily for commercial use, it stands out as an ideal solution for businesses that require a reliable and effective climate control system.

One of the main features of the RAV-SP240AT2-UL is its powerful 24,000 BTU cooling capacity, which allows it to effectively cool larger spaces. This unit functions efficiently even in extreme weather conditions, providing optimal performance regardless of outside temperatures. The RAV-SP240AT2-UL also boasts a heating capacity, making it a versatile option for year-round climate control.

Energy efficiency is a significant characteristic of this model, as it comes equipped with an advanced inverter technology. This technology allows the unit to adjust its cooling and heating output according to the specific requirements of the space. As a result, users can expect lower energy consumption, reduced electricity bills, and a lower carbon footprint. The RAV-SP240AT2-UL has a high Energy Efficiency Ratio (EER) rating that further underscores its energy-saving capabilities.

In terms of installation, the RAV-SP240AT2-UL is designed for easy integration. Its compact size and lightweight design make it suitable for various commercial settings, including offices, retail spaces, and restaurants. The unit can be installed in both horizontal and vertical configurations, providing flexibility to meet the unique layout of any building.

The Toshiba RAV-SP240AT2-UL also includes advanced filtration systems that enhance indoor air quality. Its multi-stage air filtration process removes dust, allergens, and other particulates, ensuring a healthier environment for occupants. Additionally, the unit operates at a low noise level, providing a quiet atmosphere that enhances the comfort of any space.

Another notable technology featured in the RAV-SP240AT2-UL is the Smart Control system, which allows users to monitor and manage their air conditioning remotely. This feature adds convenience and flexibility, enabling businesses to optimize their energy use and maintain a comfortable environment, even from a distance.