Toshiba RAV-SP240AT2-UL 12TROUBLESHOOTING, Verifying Fault code status Outdoor control board

Page 21

Outdoor Unit

Installation Manual

12TROUBLESHOOTING

You can perform fault diagnosis of the outdoor unit with the LEDs on the P.C. board of the outdoor unit in addition to using the check codes displayed on the wired remote controller of the indoor unit.

Use the LEDs and check codes for various checks. Details of the check codes displayed on the wired remote controller of the indoor unit are described in the Installation Manual of the indoor unit.

Verifying Fault code status (Outdoor control board)

1.Check that DIP switch SW803 is set to off.

2.Record the states (on or off) of LED 800 to LED 804 (Display mode 1).

3.Press SW800 for at least 1 second. The LED status changes to display mode 2.

4.Since display mode 1 covers multiple faults with the same code display, mode 2 must also be used to determine the final fault. Use the status recorded for LED 800 to LED 804 in display mode 1 (Item 2 above) and combine it with the status for the same LED’s in display mode 2 (Item 3 above) to determine the complete fault code using the chart below.

Verifying Fault code status stored in memory (Outdoor control board)

1.Check that DIP switch SW803 is set to on.

2.Record the states (on or off) of LED 800 to LED 804 (Display mode 1).

3.Press SW800 for at least 1 second. The LED status changes to display mode 2.

4.Since display mode 1 covers multiple faults with the same code display, mode 2 must also be used to determine the final fault. Use the status recorded for LED 800 to LED 804 in display mode 1 (Item 2 above) and combine it with the status for the same LED’s in display mode 2 (Item 3 above) to determine the complete fault code using the chart below.

NOTE

An outside air temperature (TO) sensor error can be checked only when an error occurs.

No.

Cause

 

Display mode 1

 

 

Display mode 2

 

D800

D801

D802

D803

D804

D800

D801

D802

D803

D804

 

 

1

Normal

2

Discharge (TD) sensor error

{

{

{

 

3

Heat exchanger (TE) sensor error

{

{

{

 

 

4

Heat exchanger (TL) sensor error

{

{

{

 

 

 

5

Outside air temperature (TO) sensor error

{

{

{

 

6

Suction (TS) sensor error

{

{

{

 

 

7

Heat sink (TH) sensor error

{

{

{

 

 

 

8

Outdoor temperature sensor (TE/TS) connection

{

{

{

 

 

 

 

error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

Outdoor EEPROM error

{

{

{

 

 

 

 

 

10

Compressor lock

{

{

 

11

Compressor lock

{

{

 

12

Current detection circuit error

{

{

 

 

13

Thermostat for compressor activated

{

{

 

14

Model data not set

{

{

{

 

 

(on the service P.C. board)

 

 

 

 

 

 

 

 

 

 

 

 

 

15

MCU-MCU communication error

{

{

{

 

 

 

 

16

Discharge temperature error

{

{

{

{

 

 

17

Abnormal power

{

{

{

{

 

 

(open phase detected or abnormal voltage)

 

 

 

 

 

 

 

 

 

 

 

 

 

18

Heat sink overheat

{

{

{

{

 

 

 

19

Gas leak detected

{

{

{

{

 

 

 

 

20

4-way valve reverse error

{

{

{

{

 

 

 

(●:OFF {:ON :Flashing)

EN

– 20 –

20-EN

Image 21
Contents Installation manual Contents Dimension Accessory Parts Part name ’ty Shape Usage Installation manualHand this directly to the customer „ Piping Field supplied System RequirementsBe sure to ground the equipment Precautions for SafetyEquipment Damage Hazard „ Required Tools/Equipment and Precautions for Use Installation of NEW Refrigerant AIR ConditionerNew Refrigerant Air Conditioner Installation Tools/equipment Use„ Installation Location Do not install the outdoor unit in the following locationExample Unit in mm „Required ClearancesBarrier at rear side Barrier in front Upper side is free Above unit is freeStandard installation „ Installation of Outdoor UnitInstallation Manual Barriers in front and back of unit5pcs Drain nippleFlaring Refrigerant PipingProjection margin in flaring B Unit in mm Rigid Clutch type Flaring diameter size a Unit in mmDo not apply refrigerant oil to the flared surface „ Tightening of Flare ConnectionsValve at liquid side Outer diameter of copper pipe Tightening torqueElectrical Connections „ Field wiring„ Wiring Attach the front pipe cover with 4 screws Evacuate and Dehydrate the System Using Vacuum PumpDeep Vacuum Method Triple Evacuation MethodValve handling precautions Open service valvesFinal Tubing Check Liquid side11PERIODIC Maintenance Finishing10TEST RUN Verifying Fault code status Outdoor control board 12TROUBLESHOOTINGD800 D801 D802 D803 D804 D805 14POWER Save Procedure13UNIT Pump Down EH99865401

RAV-SP240AT2-UL specifications

The Toshiba RAV-SP240AT2-UL is a state-of-the-art air conditioning unit that showcases Toshiba's commitment to energy efficiency, innovation, and comfort. Designed primarily for commercial use, it stands out as an ideal solution for businesses that require a reliable and effective climate control system.

One of the main features of the RAV-SP240AT2-UL is its powerful 24,000 BTU cooling capacity, which allows it to effectively cool larger spaces. This unit functions efficiently even in extreme weather conditions, providing optimal performance regardless of outside temperatures. The RAV-SP240AT2-UL also boasts a heating capacity, making it a versatile option for year-round climate control.

Energy efficiency is a significant characteristic of this model, as it comes equipped with an advanced inverter technology. This technology allows the unit to adjust its cooling and heating output according to the specific requirements of the space. As a result, users can expect lower energy consumption, reduced electricity bills, and a lower carbon footprint. The RAV-SP240AT2-UL has a high Energy Efficiency Ratio (EER) rating that further underscores its energy-saving capabilities.

In terms of installation, the RAV-SP240AT2-UL is designed for easy integration. Its compact size and lightweight design make it suitable for various commercial settings, including offices, retail spaces, and restaurants. The unit can be installed in both horizontal and vertical configurations, providing flexibility to meet the unique layout of any building.

The Toshiba RAV-SP240AT2-UL also includes advanced filtration systems that enhance indoor air quality. Its multi-stage air filtration process removes dust, allergens, and other particulates, ensuring a healthier environment for occupants. Additionally, the unit operates at a low noise level, providing a quiet atmosphere that enhances the comfort of any space.

Another notable technology featured in the RAV-SP240AT2-UL is the Smart Control system, which allows users to monitor and manage their air conditioning remotely. This feature adds convenience and flexibility, enabling businesses to optimize their energy use and maintain a comfortable environment, even from a distance.

Overall, the Toshiba RAV-SP240AT2-UL is a robust and efficient air conditioning solution tailored for commercial spaces. With its blend of power, energy efficiency, and advanced technology, it ensures an optimal climate control experience while promoting sustainability.