York DY 036 warranty Configuration, Horizontal Ducted Inlet

Page 8

 

 

 

 

 

 

 

 

 

343615-YTG-A-0807

TABLE 4: DY036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT DESCRIPTION / MODEL

 

 

 

DY036 / 3 Ton

 

 

 

 

 

CONFIGURATION

 

 

 

Horizontal Ducted Inlet

 

 

 

 

 

Indoor Blower Speed (RPM)

630

631

879

885

 

 

Blower Static Pressure (IWG)

0.2

0.3

0.2

0.7

 

 

Airflow (CFM)

1116

928

1979

1020

 

 

Blower Motor BHP

0.41

0.37

0.76

0.53

 

 

 

ID Blower

Cooling

ID Blower

Cooling

ID Blower

 

Cooling

ID Blower

Cooling

 

 

Octave Center Freq.

Operation2

Operation2

 

Operation2

Operation2

 

 

Only (dB)

(dB)

Only (dB)

(dB)

Only (dB)

 

(dB)

Only (dB)

(dB)

 

 

 

 

 

 

 

 

63

80

82

80

82

78

 

83

81

85

 

 

125

76

77

76

77

82

 

83

81

82

 

 

250

56

59

56

60

60

 

61

58

60

 

 

500

50

50

49

50

54

 

54

51

52

 

 

1000

40

43

39

42

49

 

50

44

45

 

 

2000

41

42

40

42

49

 

49

43

44

 

 

4000

41

41

41

41

49

 

49

41

41

 

 

8000

45

45

45

45

47

 

47

45

45

 

1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .

2.Cooling Operation – ID blower, compressor and outdoor fan operating.

3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

4.Test duct termination is flush with reverberation room wall.

5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

TABLE 5: DY036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)

UNIT DESCRIPTION / MODEL

 

 

 

DY036 / 3 Ton

 

 

 

CONFIGURATION

 

 

Horizontal Ducted Discharge

 

 

Indoor Blower Speed (RPM)

630

631

879

885

Blower Static Pressure (IWG)

0.2

0.3

0.2

0.7

Airflow (CFM)

1116

928

1979

1020

Blower Motor BHP

0.41

0.37

0.76

0.53

 

ID Blower

Cooling

ID Blower

Cooling

ID Blower

Cooling

ID Blower

Cooling

Octave Center Freq.

Operation2

Operation2

Operation2

Operation2

 

Only (dB)

(dB)

Only (dB)

(dB)

Only (dB)

(dB)

Only (dB)

(dB)

 

 

 

 

 

63

80

84

80

83

85

87

84

87

125

74

77

74

76

80

82

80

83

250

58

61

58

61

68

68

63

65

500

48

51

47

50

58

58

53

54

1000

41

45

39

43

55

55

49

50

2000

39

41

37

39

53

53

46

47

4000

41

41

38

38

55

55

49

49

8000

45

45

44

44

52

53

47

47

1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .

2.Cooling Operation – ID blower, compressor and outdoor fan operating.

3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).

4.Test duct termination is flush with reverberation room wall.

5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.

8

Unitary Products Group

Image 8
Contents Warranty DescriptionTable of Contents Product Nomenclature Ton Sunline Magnum Model Number NomenclatureFeatures FACTORY-INSTALLED Options Unit CutawayFIELD-INSTALLED Accessories Stage GAS Heat Ratings Capacity Ratings ARI 210/2401GAS Heat RATINGS1 Configuration Horizontal Ducted InletVertical Ducted Inlet DY048 / 4 Ton 791 794 1084 1095 DY060 / 5 Ton 834 840 1171 1194 DY036 Cooling Capacities 3 TON MBHDY048 Cooling Capacities 4 TON DY060 Cooling Capacities 5 TON 1500MED Static Resistances Electric Heater CFM LimitationsAmps Ampacity Size Each FLA Tonnage RLA LRA Motor Outlet None 34.4 2CE04510506 19.2 46.5 208-1-60 YTG-A-0807 Voltage LIMITATIONS1 DY Physical DataElectric Heat Correction Factors Typical Power Wiring Unit Dimensions 3 5 TON COOLING/GAS Heat Front View Detail a Unit Dimensions Rear View Minimum Clearances Typical Applications Center of Gravity Unit TotalOperating Weights LBS Roof Curb DimensionsGuide Specifications Indoor Evaporator FAN AssemblyOutdoor Condenser FAN Assembly Unit CabinetUnit Operating Characteristics Unit ControlsGAS Heating Section Single or 2 Stage Electric Heating SectionManual Outdoor AIR Damper Other PRE-ENGINEERED Accessories AvailableElectric Heaters YTG-A-0807 YTG-A-0807 YTG-A-0807