York DM 078 manual Additional Factory Installed Options

Page 48

outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55 ºF. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy con- trol that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss. Available with barometric relief or power exhaust.

2.MOTORIZED OUTDOOR AIR DAMPERS – Outdoor and return air dampers that are interlocked and posi- tioned by a 2-position,spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in the design CFM of outdoor air to meet the ventila- tion requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected posi- tions – regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-energized. Dampers shall fully close on power loss.

ADDITIONAL FACTORY INSTALLED OPTIONS

ALTERNATE INDOOR BLOWER MOTOR – For appli- cations with high restrictions, units are available with optional indoor blower motors that provide higher static output and/or higher airflow.

CONVENIENCE OUTLET (POWERED/NON-POW- ERED) – Unit can be provided with an optional 120VAC GFCI outlet with cover on the corner of the unit housing the compressors.

ELECTRIC HEAT - Electric heaters range from 9 kW to 54 kW and are available in all the voltage options of the base unit.

PHASE MONITOR - Designed to prevent damage in out- of-phase condition.

COIL GUARD - Designed to prevent condenser coil damage.

BAS CONTROLS - Include supply air sensor, return air sensor, dirty filter indicator and air proving switch.

DIRTY FILTER SWITCH – This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high- pressure drop across the filters.

BREAKER – An HACR breaker can be factory installed on gas heat units or cooling units with electric heat.

DISCONNECT SWITCH - A disconnect can be factory installed on a cooling only units sized for the largest elec- tric heat available.

STAINLESS STEEL HEAT EXCHANGER – For applica- tions in a corrosive environment, this option provides a full stainless steel heat exchanger assembly.

STAINLESS STEEL DRAIN PAN – Provides years of trouble-free operation in corrosive environments.

SMOKE DETECTOR – A smoke detector can be factory mounted and wired in the supply and/or return air com- partments.

OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE

ROOF CURB - 14” and 8” high, full perimeter knockdown curb, with hinged design for quick assembly.

BAROMETRIC RELIEF DAMPER – (Unit mounted – Downflow, Duct Mounted – Horizontal) – Contains a rain hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure through the unit during economizer operation.

PROPANE CONVERSION KIT – Contains new orifices and gas valve springs to convert from natural to L.P. gas.

–60 ºF GAS HEAT KIT – Provides an electric heat kit for the gas compartment for use in extreme low ambient conditions.

ECONOMIZER (Downflow and Horizontal flow)

POWER EXHAUST – (Unit mount – Downflow, Duct mount – Horizontal flow)

DUAL ENTHALPY KIT - Provides a second input to economizer to monitor return air.

Subject to change without notice. Printed in U.S.A.

246645-YTG-C-0708

Copyright © 2008 by Johnson Controls, Inc. All rights reserved.

Supersedes: 246645-YTG-B-0606

 

 

 

 

Johnson Controls Unitary Products

5005 York Drive

Norman, OK 73069

Image 48
Contents Technical Guide Table of Contents Features YTG-C-0708 Factory Installed Options Field Installed Accessories Low Limit / Compressor Lockout Kit Accessories Part Number Description WeightYTG-C-0708 Ton York Model Number Nomenclature DM Physical Data DM Capacity Ratings Unit Voltage LimitationsRating Electric Heat Size Seasonal DB†Cooling Capacity DM078 6-1/2 TON Unit Cooling Capacity DM090 7-1/2 TON Unit 2250Cooling Capacity DM102 8-1/2 TON Unit 2550Cooling Capacity DM120 10 TON Unit Cooling Capacity DM150 12-1/2 TON Unit MCA FLA Outlet Amps Size Amps Exhaust Model No Supply Pwr Min. Circuit Electric Heat Multipliers 240480 600DM078 6-1/2 TON Side Shot Blower Performance DM090 7-1/2 TON Side Shot Blower Performance CFMDM102 8-1/2 TON Side Shot Blower Performance DM120 10 TON Side Shot Blower Performance DM150 12-1/2 TON Side Shot Blower Performance DM078 6-1/2 TON Down Shot Blower Performance RPM BHPDM090 7-1/2 TON Down Shot Blower Performance DM102 8-1/2 TON Down Shot Blower Performance DM120 10 TON Down Shot Blower Performance DM150 12-1/2 TON Down Shot Blower Performance Additional Static Resistance DM078, 120 Additional Static Resistance DM090Cooling Only Economizer† ‡ Electric Heat KW† Indoor Blower Specifications Power Exhaust SpecificationsElectric Heat Minimum Supply AIR CFM Model Location lbs Point Load Weight Unit WeightDetail a Unit ClearancesPredator Roof Curb Dimensions Detail B Detail CSunline to Predator Transition Roof Curbs Air Economizer Usage Application Cabinet Height Description ModelField Installed Horizontal Economizer W/POWER Exhaust Slab Economizer END Return W/POWER Exhaust Cooling Unit with GAS Heat Wiring 230 Volt Diagram Cooling Unit WITH/WITHOUT Electric Heat Wiring Diagram YTG-C-0708 Predator GeneralDescription GAS Heating Section if Equipped Additional Factory Installed Options Johnson Controls Unitary Products York Drive Norman, OK