Factory installed smoke detectors in the return air, may be subjected to freezing temperatures during "off" times due to out side air infiltration. These smoke detectors have an operational limit of 32 °F to 131°F. Smoke detectors installed in areas that could be out side those limitations will have to be moved to prevent having false alarms.
•Phase Monitors - Designed to prevent unit damage. The phase monitor will shut the unit down in an
•Coil Guard - Customers can purchase a coil guard kit to protect the condenser coil from damage. Additionally, this kit stops animals and foreign objects from entering the space between the inner condenser coil and the main cabinet. This is not a hail guard kit.
•Dirty Filter Switch - This kit includes a differential pres- sure switch that energizes the fault light on the unit ther- mostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.
•Technicoat Condenser Coils - The condenser coils are coated with a phenolic coating for protection against cor- rosion due to harsh environments.
•Technicoat Evaporator Coil - The evaporator coils are coated with a phenolic coating for protection against cor- rosion due to harsh environments.
•BAS - Building Automation System Controls Simplic- ity™
•Simplicity™
•Novar® BAS Control - The Novar®
•Johnson Controls BAS Control - The Johnson Control
•CPC BAS Control - The Computer Process Controls Model
•Honeywell BAS Control - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch.
•York Commercial Comfort System (YCCS) - Provides rooftop system integration for YCCS single zone and
FIELD INSTALLED ACCESSORIES
YORK® offers several equipment accessories for field instal- lation, for the Predator® line.
•Downflow Economizer - (With barometric relief) - The economizer is provided with a single enthalpy input. The economizer is 2% low leakage type. The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the out- door air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the standard single enthalpy input. There is an optional input dual dry bulb available. To meet regulated air standards, the economizer
control accepts an optional CO2 input for demand ventila- tion. With single enthalpy input, the economizer control monitors outdoor air. The dual enthalpy kit provides a sec- ond input used to monitor the return air. With a dual input kit installed, the economizer control compares the values of the two enthalpy or temperature inputs and positions the dampers to provide the maximum efficiency possible
•Horizontal Economizer - (Without barometric relief) - All features of the downflow economizer exist except you must order the duct mount barometric relief separately.
You must order a 1EH0408 if you are installing a power exhaust. You can order a 1RD0411 Barometric Relief for horizontal flow economizer.
•Slab Economizer for Energy Recovery Ventilator- (Without barometric relief or Fresh Air Hood) - The economizer is provided with a single enthalpy input. The