York DM 078 manual Field Installed Accessories

Page 6

246645-YTG-C-0708

Factory installed smoke detectors in the return air, may be subjected to freezing temperatures during "off" times due to out side air infiltration. These smoke detectors have an operational limit of 32 °F to 131°F. Smoke detectors installed in areas that could be out side those limitations will have to be moved to prevent having false alarms.

Phase Monitors - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of phase condition. (Standard on units with Scroll Compressors.)

Coil Guard - Customers can purchase a coil guard kit to protect the condenser coil from damage. Additionally, this kit stops animals and foreign objects from entering the space between the inner condenser coil and the main cabinet. This is not a hail guard kit.

Dirty Filter Switch - This kit includes a differential pres- sure switch that energizes the fault light on the unit ther- mostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.

Technicoat Condenser Coils - The condenser coils are coated with a phenolic coating for protection against cor- rosion due to harsh environments.

Technicoat Evaporator Coil - The evaporator coils are coated with a phenolic coating for protection against cor- rosion due to harsh environments.

BAS - Building Automation System Controls Simplic- ity™ INTELLI-Comfort™ Control - The York® Simplic- ity™ INTELLI-Comfort™ control is factory installed. It includes a supply air sensor, a return air sensor, and an outside air sensor. There are provisions for a field installed dirty filter indicator switch, an air-proving switch, an Out- side Air Humidity sensor, a Return Air Humidity sensor, an Inside IAQ sensor, and an Outside Air IAQ sensor. Con- struction mode operation, 365-day real time clock with 7 day programming plus holiday scheduling is built-in. Two different modes of demand ventilation are achieved through the INTELLI-Comfort™ using CO2 sensors. It uses an inside CO2 sensor to perform Demand Ventilation. It can also use an Outside CO2 sensor to perform Differen- tial Demand Ventilation. It uses a Patented Comfort Venti- lation algorithm to provide comfortable ventilation air temperature. The patented economizer-loading algorithm will protect the equipment when harsh operating conditions exist. Humidity in the occupied space or return duct can be monitored and controlled via humidity sensors and the on- board connection for hot gas re-heat system. It uses the INTELLI-Start™ algorithm to maximize energy savings by recovering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the Occupied Time Period to begin. The Simplicity™ INTELLI-Comfort™ bal- ances space temperature, ventilation air temperature, CO2 and humidity for ultimate comfort.

Simplicity™ INTELLI-Comfort™ with ModLINC Control - The York® Simplicity™ INTELLI-Comfort™ with ModLINC control is factory installed. It includes all the features of the INTELLI-Comfort™ control with an additional control to translate communications from MODBUS to the BACnet MSTP protocol.

Novar® BAS Control - The Novar® ETC-3 building automation system controller is factory installed. Incudes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.

Johnson Controls BAS Control - The Johnson Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.

CPC BAS Control - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building auto- mation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch and air proving switch.

Honeywell BAS Control - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch.

York Commercial Comfort System (YCCS) - Provides rooftop system integration for YCCS single zone and change-over bypass systems.

FIELD INSTALLED ACCESSORIES

YORK® offers several equipment accessories for field instal- lation, for the Predator® line.

Downflow Economizer - (With barometric relief) - The economizer is provided with a single enthalpy input. The economizer is 2% low leakage type. The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the out- door air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the standard single enthalpy input. There is an optional input dual dry bulb available. To meet regulated air standards, the economizer

control accepts an optional CO2 input for demand ventila- tion. With single enthalpy input, the economizer control monitors outdoor air. The dual enthalpy kit provides a sec- ond input used to monitor the return air. With a dual input kit installed, the economizer control compares the values of the two enthalpy or temperature inputs and positions the dampers to provide the maximum efficiency possible

Horizontal Economizer - (Without barometric relief) - All features of the downflow economizer exist except you must order the duct mount barometric relief separately.

You must order a 1EH0408 if you are installing a power exhaust. You can order a 1RD0411 Barometric Relief for horizontal flow economizer.

Slab Economizer for Energy Recovery Ventilator- (Without barometric relief or Fresh Air Hood) - The economizer is provided with a single enthalpy input. The

6

Johnson Controls Unitary Products

Image 6
Contents Technical Guide Table of Contents Features YTG-C-0708 Factory Installed Options Field Installed Accessories Low Limit / Compressor Lockout Kit Accessories Part Number Description WeightYTG-C-0708 Ton York Model Number Nomenclature DM Physical Data Rating Electric Heat Size Seasonal DM Capacity RatingsUnit Voltage Limitations DB†Cooling Capacity DM078 6-1/2 TON Unit Cooling Capacity DM090 7-1/2 TON Unit 2250Cooling Capacity DM102 8-1/2 TON Unit 2550Cooling Capacity DM120 10 TON Unit Cooling Capacity DM150 12-1/2 TON Unit MCA FLA Outlet Amps Size Amps Exhaust Model No Supply Pwr Min. Circuit 480 Electric Heat Multipliers240 600DM078 6-1/2 TON Side Shot Blower Performance DM090 7-1/2 TON Side Shot Blower Performance CFMDM102 8-1/2 TON Side Shot Blower Performance DM120 10 TON Side Shot Blower Performance DM150 12-1/2 TON Side Shot Blower Performance DM078 6-1/2 TON Down Shot Blower Performance RPM BHPDM090 7-1/2 TON Down Shot Blower Performance DM102 8-1/2 TON Down Shot Blower Performance DM120 10 TON Down Shot Blower Performance DM150 12-1/2 TON Down Shot Blower Performance Additional Static Resistance DM078, 120 Additional Static Resistance DM090Cooling Only Economizer† ‡ Electric Heat KW† Indoor Blower Specifications Power Exhaust SpecificationsElectric Heat Minimum Supply AIR CFM Model Location lbs Detail a Point Load WeightUnit Weight Unit ClearancesPredator Roof Curb Dimensions Detail B Detail CSunline to Predator Transition Roof Curbs Air Economizer Usage Application Cabinet Height Description ModelField Installed Horizontal Economizer W/POWER Exhaust Slab Economizer END Return W/POWER Exhaust Cooling Unit with GAS Heat Wiring 230 Volt Diagram Cooling Unit WITH/WITHOUT Electric Heat Wiring Diagram YTG-C-0708 Predator GeneralDescription GAS Heating Section if Equipped Additional Factory Installed Options Johnson Controls Unitary Products York Drive Norman, OK