GENERAL

Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility. YORK® Pred- ator® units are convertible single packages with a common footprint cabinet and common roof curb for all 6-1/2 through 12-1/2 ton models. All units have two compressors with inde- pendent refrigeration circuits to provide 2 stages of cooling. The units were designed for light commercial applications and can be easily installed on a roof curb, slab, or frame. All Predator® units are self-contained and assembled on rigid full perimeter base rails allowing for 3-way forklift access and overhead rigging. Every unit is completely charged, wired, piped, and tested at the factory to provide a quick and easy field installation. All units are convertible between side and down airflow. Independent economizer designs are used on side and down discharge applications, as well as all tonnage sizes. Predator® units are available in the following configura- tions: cooling only, cooling with electric heat, and cooling with gas heat. Electric heaters are available as factory-installed options and field-installed accessories.

DESCRIPTION

Units shall be factory assembled, single package, (Elec/Elec, Gas/Elec), designed for outdoor installation. Units shall have a minimum EER of 9.0. They shall have built in field convert- ible duct connections for down discharge supply/return or horizontal discharge supply/return and be available with fac- tory installed options or field installed accessories. The units shall be factory wired, piped and charged with R-22 refriger- ant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. The cooling performance shall be rated in accordance with DOE and ARI test proce- dures. Units shall be CSA certified to ANSI Z21.47 and UL 1995/CAN/CSA No. 236-M90 standards.

UNIT CABINET

Unit cabinet shall be constructed of G90 galvanized steel with exterior surfaces coated with a non-chalking, powder paint finish, certified at 1000 hours salt spray test per ASTM-B117 standards. Indoor blower sections shall be insulated with up to 1” thick insulation coated on the airside. Aluminum foil faced insulation shall be used in the unit’s compartments and be fastened to prevent insulation from entering the air stream. Cabinet doors shall be hinged with tool-less access for easy servicing and maintenance. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging, fork truck access and proper sealing on roof curb applications. Disposable 2” filters shall be furnished and be accessible through hinged access door. Fan perfor- mance measuring ports shall be provided on the outside of the cabinet to allow accurate air measurements of evaporator

fan performance without removing panels or creating bypass of the coils. Condensate pan shall be slide out design, con- structed of a non corrosive material, internally sloped and conforming to ASHRAE 62-B9 standards. Condensate con- nection shall be a minimum of ¾” I.D. female and be rigid mount connection.

INDOOR (EVAPORATOR) FAN ASSEMBLY

Fan shall be a belt drive assembly and include an adjustable pitch motor pulley. Job site selected brake horsepower shall not exceed the motors nameplate horsepower rating plus the service factor. Units shall be designed to operate within the service factor. Fan wheel shall be double inlet type with for- ward curve blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant volume. Bearings shall be sealed and permanently lubricated for longer life and no mainte- nance. Entire blower assembly and motor shall be slide out design.

OUTDOOR (CONDENSER) FAN ASSEMBLY

The outdoor fans shall be of the direct drive type, discharge air vertically, have aluminum blades riveted to corrosion resistant steel spider brackets and shall be dynamically bal- anced for smooth operation. The outdoor fan motors shall have permanently lubricated bearings internally protected against overload conditions and staged independently. A cleaning window shall be provided on two sides of the units for coil cleaning.

REFRIGERANT COMPONENTS

Compressors:

A.Shall be fully hermetic type, direct drive, internally pro- tected with internal high-pressure relief and over temper- ature protection. The hermetic motor shall be suction gas cooled and have a voltage range of + or – 10% of the unit nameplate voltage.

B.Shall have internal spring isolation and sound muffling to minimize vibration and noise, and be externally isolated on a dedicated, independent mounting.

Coils:

A.Evaporator and condenser coils shall have aluminum plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option.

B.Evaporator and condenser coils shall be of the direct expansion, draw-thru design.

46

Johnson Controls Unitary Products

Image 46
Contents Technical Guide Table of Contents Features YTG-C-0708 Factory Installed Options Field Installed Accessories Low Limit / Compressor Lockout Kit Accessories Part Number Description WeightYTG-C-0708 Ton York Model Number Nomenclature DM Physical Data Rating Electric Heat Size Seasonal DM Capacity RatingsUnit Voltage Limitations DB†Cooling Capacity DM078 6-1/2 TON Unit Cooling Capacity DM090 7-1/2 TON Unit 2250Cooling Capacity DM102 8-1/2 TON Unit 2550Cooling Capacity DM120 10 TON Unit Cooling Capacity DM150 12-1/2 TON Unit MCA FLA Outlet Amps Size Amps Exhaust Model No Supply Pwr Min. Circuit 480 Electric Heat Multipliers240 600DM078 6-1/2 TON Side Shot Blower Performance DM090 7-1/2 TON Side Shot Blower Performance CFMDM102 8-1/2 TON Side Shot Blower Performance DM120 10 TON Side Shot Blower Performance DM150 12-1/2 TON Side Shot Blower Performance DM078 6-1/2 TON Down Shot Blower Performance RPM BHPDM090 7-1/2 TON Down Shot Blower Performance DM102 8-1/2 TON Down Shot Blower Performance DM120 10 TON Down Shot Blower Performance DM150 12-1/2 TON Down Shot Blower Performance Additional Static Resistance DM090 Additional Static Resistance DM078, 120Cooling Only Economizer† ‡ Electric Heat KW† Power Exhaust Specifications Indoor Blower SpecificationsElectric Heat Minimum Supply AIR CFM Model Location lbs Detail a Point Load WeightUnit Weight Unit ClearancesPredator Roof Curb Dimensions Detail B Detail CSunline to Predator Transition Roof Curbs Air Economizer Usage Application Cabinet Height Description ModelField Installed Horizontal Economizer W/POWER Exhaust Slab Economizer END Return W/POWER Exhaust Cooling Unit with GAS Heat Wiring 230 Volt Diagram Cooling Unit WITH/WITHOUT Electric Heat Wiring Diagram YTG-C-0708 General PredatorDescription GAS Heating Section if Equipped Additional Factory Installed Options Johnson Controls Unitary Products York Drive Norman, OK