Controls (continued)

operation, the pressure within the building in monitored by the OptiLogic™ controller. If the pressure rises to or above a selected turn-on pressure, the Exhaust Fan is cycled ON. The fan shall remain on as long as the pres- sure within the building remains above a selected turn- off pressure. If the building pressure falls to or below the selected turn-off pressure, the Exhaust Fan is cycled OFF. The turn-on and turn-off pressure setpoints are user selectable from the OptiLogic™ User Interface.

Powered Variable Volume Exhaust-Discharge Damper Controlled

This optional variable volume powered exhaust system consists of a fixed speed fan configured with a propor- tionally controlled discharge damper. The OptiLogic™ controller monitors the pressure inside the building and controls the Exhaust Damper and the Exhaust Fan. If the Building Pressure rises, the Exhaust Damper is pro- portionally controlled open and the Exhaust Fan is con- trolled ON. If the Building Pressure falls, the Exhaust Damper is proportionally controlled closed and the Ex- haust Fan is controlled OFF. The position of the Ex- haust Damper in which the Exhaust Fan is controlled ON and OFF as well as the Building Pressure setpoint is user selectable from the OptiLogic™ User Interface.

Powered Variable Volume Exhaust-VFD Controlled

This optional variable volume powered exhaust system consist of an Exhaust Fan driven by a Variable Fre- quency Drive (VFD), which is controlled by the OptiLogic™ controller. The OptiLogic™ controller moni- tors the pressure within the building. As the pressure rises, the VFD is controlled to increase Exhaust Fan speed. As the pressure falls, the VFD is controlled to decrease Exhaust Fan speed. The Building Pressure Setpoint is user selectable from the OptiLogic™ User Interface.

LOW AMBIENT OPERATION

The OptiLogic™ controller continuously monitors the outside air temperature to determine if mechanical cool- ing should be allowed. As a safety, if the Outside Air temperature falls to or below the Low Ambient Lockout temperature, mechanical cooling is prevented from op- erating. For units with economizers, the Low Ambient Lockout temperature is typically low enough that me- chanical cooling will rarely be required. However, for some applications mechanical cooling is required when the Outside Air temperature is lower than the Low Am- bient Lockout temperature.

For these applications, the unit can be equipped with optional Low Ambient controls. For optional Low Ambi- ent operation, the OptiLogic™ controller monitors the refrigeration system discharge pressure and controls the speed of the condenser fans. If the discharge pres- sure falls, the speeds of the condenser fans are re- duced to maintain acceptable condensing pressures in the refrigeration system. With the optional Low Ambi- ent controls, mechanical cooling is allowed down to Outside Air temperatures of 0°F.

SMOKE PURGE SEQUENCES

General

As a convenience, for when buildings catch fire or the building is inundated with smoke or fumes from manu- facturing processes, etc., the OptiLogic™ control sys- tem provides one of five ventilation override control se- quences for building purge. The five selectable purge sequences are, Shutdown, Pressurization, Exhaust, Purge and Purge with duct pressure control. Note, when any of the purge sequences are activated, cooling and heating modes are disabled. A contact closure is pro- vided which indexes the OptiLogic™ controller into the selected purge sequence.

Shutdown

When this purge sequence is selected and activated, the supply and exhaust fans are controlled OFF and the Outside Air damper is overridden closed. This idle state is maintained until the purge input is deactivated and the unit returns to normal operation.

Pressurization

When this purge sequence is selected and activated, the exhaust fan is controlled OFF and the Supply Fan is controlled ON. The Outside Air damper is opened full and the Return Air Damper is closed full. If the unit is a VAV unit, the VAV boxes are also driven full open to prevent duct over-pressurization. This mode is main- tained until the smoke purge input is deactivated and the unit returns to normal operation.

Exhaust

When this purge sequence is selected and activated, the Supply Fan is controlled OFF and the Exhaust Fan is controlled ON (Exhaust Damper driven full open). This mode is maintained until the smoke purge input is deactivated and the unit returns to normal operation.

28

YORK INTERNATIONAL

Image 28
Contents Packaged Rooftop Air Conditioning Units 407C Optimized Through 65 TonsTable of Contents Nomenclature Basic Model NumberIntroduction FEATURES/BENEFITSEcological and Economical Design Install with Ease and Safety ServiceabilityReliable Scroll Compressor Technology Introduction Physical Data Physical DataPhysical Data Cont’d Application Data LocationRigging EconomizerBuilding Exhaust Systems Harsh Environments Condenser and Evaporator Coil ProtectionRoof Curb Selection Procedure Acoustical ConsiderationsGiven Select UnitCooling Performance Data 50 Ton Model Cooling Performance Data 50 TON ModelCooling Performance Data 50 TON Model CONT’D Cooling Performance Data 55 Ton Model Cooling Performance Data 55 TON ModelCooling Performance Data 55 TON Model CONT’D Cooling Performance Data 60 Ton Model Cooling Performance Data 60 TON ModelCooling Performance Data 60 TON Model CONT’D Cooling Performance Data 65 Ton Model Cooling Performance Data 65 TON ModelCooling Performance Data 65 TON Model CONT’D 50 Through 65 TON Supply FAN Data Fan Performance50 Through 65 TON Supply FAN Data CONT’D 50 Through 65 TON Exhaust FAN Data Component Static Pressure Drops Inches of Water Column Filters Economizer Economizer Dampers Rigid Filter Manual or Electrical Service Sizing Electrical DataLoad Definitions CompressorsSupply and Exhaust FAN Motor ODP or Tefc High EfficiencyPremium Efficiency Condenser FAN Motors / EachUnoccupied / Occupied Switching ControlsControl Sequences for ALL Units GeneralVentilation Control Sequences Exhaust Control SequencesLOW Ambient Operation Smoke Purge SequencesVAV Specific Sequences Cooling OperationStand Alone Control CV Specific SequencesCooling Operation Thermostat Control Stage 1 Y1 CallPower Wiring SINGLE-POINT Power Supply WiringSINGLE-POINT Power Supply Wiring With NON-FUSED Disconnect SINGLE-POINT Power Supply Wiring with NON-FUSED DisconnectDUAL-POINT Power Supply Wiring DUAL-POINT Power Supply WiringField Control Wiring Field Control WiringDrawing General ArrangementBottom Supply Bottom Return Left or Right Rear Return Supply General Arrangement DrawingCurb Layout Drawing Curb Layout DrawingGuide Specifications ConstructionSupply AIR System Bearings and DrivesPower Supply AIR Filtering SystemAIR Inlet System Refrigeration SystemControls Accessories and OptionsEconomizers Relief System Evaporator Coil ProtectionCondenser Coil Protection Suction and Discharge Pressure Transducers moniYork International York International Proud Sponsor Olympic Team