Guide Specifications (continued)
CONTROLS
A
A single terminal strip shall be provided for all thermo- stat and customer
Unit controls shall be completely factory packaged and compatible with a room thermostat. Constant volume units shall operate with a two (2) cool/two (2) heat ther- mostat. Staging decisions shall be based upon the de- viation of space temperature from set point and the rate of change of the space temperature.
VAV units shall operate with a sensor in the supply air stream for cooling operation. Staging decisions shall be based upon the deviation of supply air temperature from set point and the rate of change of the supply air temperature.
Controllers shall have the following safeties (both VAV and CV):
•High and low pressure
•Minimum on time for compressors
•Delay between compressor stages
•
•Cooling lockout at 40° F; 0° F if equipped for low ambient operation
•Air flow proving switch requiring proper air flow for cooling operation
ACCESSORIES AND OPTIONS
Full perimeter and partial perimeter roof curbs - 14” high roof curb with wood nailer. Roof curb covers the entire perimeter of the unit (full curb) or that portion of the unit that has airflow (partial curb).
Supply Fan VFD Manual Bypass – provides full air- flow in the event of a VFD failure.
Power Supply Connections –
Supply air setpoint reset by outside air or space air temperature - Allows VAV supply air setpoint to float upward (saving energy) if the outdoor air temperature or the space temperature is sufficiently low.
Supply Fan Isolation – the entire supply fan assem- bly shall be isolated from the unit base with 2" deflec- tion springs.
Supply and Exhaust Fan Motors – high efficiency ODP, and standard and high efficiency TEFC motors are available all meeting the Energy Policy Act of 1992 (EPACT).
Low Ambient Operation – a low ambient kit is avail- able to control compressor head pressure via VFD con- denser fan speed control. Head pressure control is accomplished by monitoring head pressure with suc- tion and discharge line pressure transducers rather than less accurate temperature control.
ECONOMIZERS
Manual Damper Economizer – economizer is avail- able with a manual damper adjustable between